5
Number
Name and
appearance
Description
Normal
mode
Normally OFF.
2)
Offset/gain
adjusting LEDs
CH
OFFSET
GAIN
Test
mode
The LEDs lit change every time the SELECT/SET
switch is moved to SELECT.
3)
SELECT/SET
switch
Used to make offset/gain setting in the test mode.
Use the switches in STATION NO. "10", "20" and "40" to set the tens of the
station number.
Use the switches in STATION NO. "1", "2", "4" and "8" to set the units of the
station number.
The switches are all factory-set to OFF.
Always set the station number within the range 1 to 64.
Setting any other number than 1 to 64 will result in an error, flickering the "L
ERR." LED.
You cannot set the same station number to two or more stations.
Tens
Units
Station
number
40 20 10 8 4 2 1
1 OFF OFF OFF OFF OFF OFF ON
2 OFF OFF OFF OFF OFF ON OFF
3 OFF OFF OFF OFF OFF ON ON
4 OFF OFF OFF OFF ON OFF OFF
10 OFF OFF ON OFF OFF OFF OFF
11 OFF OFF ON OFF OFF OFF ON
64 ON ON OFF OFF ON OFF OFF
(Example) To set the station number to "32", set the switches as
indicated below.
Tens
Units
Station
number
40 20 10 8 4 2 1
32 OFF ON ON OFF OFF ON OFF
4)
Station number
setting
switches
STATION NO.
40 20 10 8 4 2 1
Setting
switches
Set value
4 2 1
Transmission
speed
0 OFF OFF OFF 156kbps
1
OFF OFF
ON 625kbps
2 OFF ON OFF 2.5Mbps
3
OFF
ON
ON 5.0Mbps
4
ON
OFF OFF 10Mbps
5)
Transmission
speed setting
switches
B RATE
4 2 1
Always set the transmission speed within the above range.
The switches are all factory-set to OFF.
Making any other setting than the above will result in an error flickering
the "L ERR." LED.
6)
Terminal block Used to connect the module power supply, transmission and I/O signals.
7)
DIN rail hook
Used to mount the module to the DIN rail.