 2 

-

70

40

240

162

7-inch wide color
LCD touch panel

USB

Upper case mounting
screws(2 screws)

Terminal block

Wall surface

5   INSTALLATION

 

 

<Way1>

<Way2>

Opening space

for the installation

Opening space

for the installation

Holes for the unit installaion

Holes for the unit installaion

4-ø6

218

6

6

186

6

6

120

154

99

Inner wall

SLA3R-BX

229

170

198

15.5

15.5

4-ø6

66

120

SLA3R-BX

Inner wall

105

4   EXTERNAL VIEW

Paint color:Pearl white

(a)  In case of installing on the control board

1)  Please use the control board of the size of 300mm 

 400mm 

 120mm or larger.

2)  Please be sure to lock the control board to protect persons from the electric shock. 

3)  Please do not use any heat insulation material on the control board.

4)  If you use it, accumulated heat will cause the center console to malfunction. 

(b)  In case of embedding in a wall

Please be sure to use the special box, SLA3R-BX (sold separately) to secure sufficient air circulation space. If the box is 

unused, the center console will not work properly because of heat buildup inside the box. Please be sure to use for protecting 

persons from the electric shock.Please check that the sufficient space is available in the wall. 

When the inside of the wall is divided and have a cavity, please create space more than 0.08m

3

. Refer to the next page.

If there is no partition on the left, right, top and bottom of the center console, please create a space that is 105mm ordeeper.

When you cannot create the sufficient space or thickness of the wall is above 15mm, please install the center console on the 

control board.

Before the installation, shut off the power supply to avoid an electric shock.

Please locate or protect so that the unit will not be forced against wiring.

(1)  Installation place

Install this unit indoors without the influence of the electromagnetic wave, or splashing such as water and dust.

Necessary clearance is 200mm or more beneath the center console and 500mm or more in front of the center console.

(2)  Installation space

Please choose one of two ways.

Содержание SC-SLA3-ER

Страница 1: ... 3 AIR CONDITIONING CONTROL SYSTEM TECHNICAL MANUAL Collection data Manual No 06 SC T 111 CENTER CONSOLE SLA 3 ER SC SLA3 ER SLB 3 ER SC SLB3 ER ...

Страница 2: ...ERNAL VIEW 2 5 INSTALLATION 2 6 FUNCTIONS 4 7 ELECTRIC WIRING 9 8 SELECTING A NEW PULSE UNIT 10 These technical manual cover Center Consoles SLA 3 ER and SLB 3 ER Concerning other air conditioning control systems see page 675 in Part 5 Air Conditioning Control System of the 06 TECHNICAL MANUAL KX 4 ...

Страница 3: ...umption calculation function is necessary use the SLB 3 ER 4 The lifetime of the keying of touch panel is one million times The lifetime of LCD is about 20 000 hours depending also upon the backlight OFF time setting The brightness will become half of the starting value 5 The touch panel has an endurance of approximately 1 million times 6 In the environment setting screen it is also possible to ch...

Страница 4: ...cient air circulation space If the box is unused the center console will not work properly because of heat buildup inside the box Please be sure to use for protecting persons from the electric shock Please check that the sufficient space is available in the wall When the inside of the wall is divided and have a cavity please create space more than 0 08m3 Refer to the next page If there is no parti...

Страница 5: ...ires to the terminal block c Confirm power supply voltage and connect correctly d Remove the upper case 1 Take out two screws using a cross slot screwdriver Don t lose the screws 2 Pull the upper case a little forward and push above Then upper case can be removed M4 screws 4 pieces accessory of the unit Fix the unit to the SLA3R BX with the M4 screws 4 places Wire separately the power supply wire ...

Страница 6: ...tions enables or disables mode setting and enables or disables temperature setting Sets Hi Me or Lo fan speed Sets auto swing ON or OFF and sets positions 1 4 Resets turns off the filter sign Operating state Mode Set temperature Room temperature Operation enabled Fan speeds Air direction Filter sign Maintenance Inspections 1 2 or backup Breakdown Monitors the operating and stopped state of the air...

Страница 7: ...tc Annual Anno Domini Month Day Hour 24 hr system Minute Displays the error occurrence and recovery history for up to 300 occasions in air conditioner units Calculates the cumulative operating hours for each air conditioner dividing them between regular hours or irregular hours and saves them Starts the fan or Prohibits operation for air conditioners which have previously been set by external dema...

Страница 8: ...Set indoor units in the blower mode to ON or OFF if you want to make them objects of proportional division As for the standby power in the case that the air conditioner is not used at night etc proportional division cannot be applied if there are no indoor units running so the standby power readings will not match Recalculate using spreadsheet software Simple software is included for editing the e...

Страница 9: ...hen the thermo is OFF and during the air supply operation Indoor unit A Indoor unit B Indoor unit C 30Hz 50Hz 70Hz Indoor unit A Indoor unit B Indoor unit C 40Hz 60Hz 70Hz Different from 1 the fixed value is accumulated irrespective of the answer Hz Accumulation is not performed when the thermo is OFF and during the Fan mode operation User login For owners the fee apportionment for multi machine a...

Страница 10: ...d the overtime in the SL 1 SL 3 system b 2 Daily cumulative pulses from meters 1 8 for each period PC input 1 Pulse meter electricity or gas group definition 2 Pulse constant definition kWh pulse m3 pulse 3 Setting of the calculation period the end of the month the 20th of the month or etc 4 Group definition for each tenant 5 Setting of energy charge the unit price and the basic charge of electric...

Страница 11: ...e round crimping terminal with the insulation sleeve for wiring to the unit Perform ground wiring Please do not connect the ground wire to the gas pipe the water pipe the lightning rod and the telephone ground wire Please do not turn on the power supply hand switch until all work finishes Please turn on the power supply two minutes or more after turning on the power supply of the indoor unit and t...

Страница 12: ... should be 1000 m or less per line Recommended signal wire list 1 5 9 11 13 15 17 19 21 23 25 39 27 29 31 33 35 37 Power input from gas meter or wattmeter 8 points in case of SLB 3 ER COM PI1 COM PI2 COM PI3 COM PI4 COM PI5 COM PI6 COM PI7 COM PI8 3 7 b The lower tier of terminal block No 1 2 3 4 Name Symbol Vinyl cabtire roung cord Vinyl cabtire round cable Control vinyl insulated vinyl sheathed ...

Страница 13: ...er pulses ask an electric meter manufacturer for details 4 Inspection while electricity consumption is at 120kWh When pulse input is highest Use 0 1kWh P then 1200P h 20P min exactly 1 minute 20 pulse 300pulses or fewer 10 minutes 200 pulses OK Use 1kWh P then 120P h 2P min exactly 1 minute 2 pulses 10 minutes 20 pulses OK Use 10kWh P then 12P h 0 2P min so 1 minute no pulses 10 minutes 2 pulses O...

Страница 14: ...lse h If you use 15m3 h 30 pulse h If you use 30m3 h 60 pulse h If you use 50m3 h 100 pulse h If you use 90m3 h 180 pulse h If you use 120m3 h 240 pulse h d Largest electric pulse input value Gas amount pulse unit 0 01kWh P 4 320kWh B 180kWh h 0 1kWh P 43 200kWh B 1 800kWh h 1kWh P 432 000kWh B 18 000kWh h 10kWh P 4320 000kWh B 180 000kWh h Note 1 Electricity meter pulse unit please select 10kWh P...

Страница 15: ... 2 No 042 2A R Air Conditioning Refrigeration Systems Headquarters 16 5 2 chome Kounan Minato ku Tokyo 108 8215 Japan Fax 03 6716 5926 ...