background image

  - 2 

-

6 Output Switch 

You can switch between level output and pulse output by changing the SW4-1 setting on the interface PWB 
Assy. 

Select level output or pulse output in accordance with the specifications of the general purpose equipment that 

  you are connecting to. 

SW4-1

Start/stop

command output

Stop

Stop

Stop

General
purpose

equipment

operating

state

General
purpose

equipment

operating

state

OFF

ON

Level output

Pulse output

Output waveform

Start/stop

command

output

Operating

Stop

Start/stop

command

output

Operating

Operating

Operating

 

 
 
 
 

7 Wiring 

 

 

 
 
 
 
 
 

[Power Supply line Specification] 

If the supply cord is damaged, it must be replaced by the manufacturer , its service agent or similarly qualified  

persons in order to avoid a hazard. 

Only use the wires specified below for the power lines and other lines connected to the general purpose machine.   

-Braided cord(cord designation 60245 IEC 51) 
-Ordinary tough rubber sheathed cord(cord designation 60245 IEC 53) 
-Flat twin tinsel cord(cord designation 60227 IEC 41) 

Use wires whose nominal cross-sectional area is 0.75 mm

2

 or more for the power lines and other lines connected   

to the general purpose machine. 

Make the ground wire from the wiring entrance to the interface connection area longer than the power supply 

 lines. 

 

[Signal Line Specifications] 

Communication mode

Old superlink connection

New superlink connection

Wire type

MVVS

MVVS

Wire diameter

0.75mm

2

-1.25mm

2

0.75mm

2

/1.25mm

2

Signal wire (total length)

Up to 1000m

Up to1500m or 1000m(*3)

Signal wire (max. length)

Up to 1000m

Up to 1000m

 

(*3) Up to 1500 m when the wire diameter is 0.75 mm2 and up to 1000 m when the diameter is 1.25 mm2. 

Do not use 2.0 mm2. Doing so can cause operation errors. 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Cautions 

when setting 

the address

 

•Set the address in the range of 000 to 047 when you are connecting to the old superlink 
(when SW3-1 is ON) and 000 to 127 when you are connecting to the new superlink (when 
SW3-1 is OFF). (The factory default setting is 000.) 
• Make sure that you do not select an address of another device already connected to the  

network. 

•Automatic address setting is not available. Set addresses manually.

Содержание SC-GIFN-E

Страница 1: ... 3 AIR CONDITIONER CONTROL SYSTEM INTERFACE KIT SC GIFN E Manual No 12 SC T 184 ...

Страница 2: ... Model 1 5 Control switch 1 6 Output switch 2 7 Wiring 2 8 Electric wiring diagram 3 9 A method of interface installation 4 10 Connectable centralized controller and gateway for connection 5 11 The number of connectable general purpose equipment 5 12 Display 6 ...

Страница 3: ... Level output ON OFF factory setting Reserved SW3 1 2 SW4 1 2 1 If the network you are connecting to is the old superlink you must change this setting Whether the actual network is the new superlink or the old superlink depends on the type of indoor units outdoor units etc Check with the agent or dealer 2 For details on switching the level pulse output see6 WARNNG CAUTION Ground the product Do not...

Страница 4: ... 53 Flat twin tinsel cord cord designation 60227 IEC 41 Use wires whose nominal cross sectional area is 0 75 mm2 or more for the power lines and other lines connected to the general purpose machine Make the ground wire from the wiring entrance to the interface connection area longer than the power supply lines Signal Line Specifications Communication mode Old superlink connection New superlink con...

Страница 5: ... 3 8 Electric Wiring Diagram 1 To detect either operation or error only 2 To detect both operation and error Connect terminal blocks 3 and 5 ...

Страница 6: ...ature range If the ambient temperature exceeds the range take measures for cooling such as installing a fan Note that using the product outside the operating temperature range can cause a malfunction Insert a circuit breaker in the power supply line Use an all pole circuit breaker whose contact gap is at least 3 mm There is risk of electric shock Make sure that the power is turned off before perfo...

Страница 7: ... purpose equipment One applicable unit can only connect with per general purpose equipment Some of the general purpose equipment can operate plural unit by connecting among each of the general purpose equipments Please refer to the instruction manual of the general purpose equipment regarding the details SC SL1NA E SC SL2NA E SC SL3NA AE BE SC SL4 AE BE SC BGWN Series SC WGWN Series SC LGWN Series...

Страница 8: ...al display Display when instructed Operation mode Off 1 Display as being instructed Anomalous status Normal Air flow rate No Data Display as being instructed Setting temperature deg Display as being instructed Room temperature Lower than 0deg Remote controller operation Unlock Display as being instructed Filter sign Off Display as being instructed Error code 1 Icon in Overview Monitor Screen is di...

Страница 9: ... 2 AIR CONDITIONER CONTROL SYSTEM Air Conditioning Refrigeration Systems Headquarters 16 5 2 chome Kounan Minato ku Tokyo 108 8215 Japan Fax 03 6716 5926 ...

Отзывы: