9 Interface Installation 

Use the supplied screws to install the interface above the ceiling or to a wall near the PAC for industry or general   
purpose equipment. 
If you are installing the interface to a wall, arrange the interface so that the terminal block (wiring entrance) is   
facing down. 

 

Installation location 

Install the interface in a location where it will not be affected by electromagnetic waves and away from water and   
dust. 
The operating temperature range of this product is 0°C to 40°C. Install this product where the ambient temperature   
falls within the operating temperature range. If the ambient temperature exceeds the range, take measures for   
cooling such as installing a fan. 
Note that using the product outside the operating temperature range can cause a malfunction. 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

Insert a circuit breaker* in the power supply line.  

 
 
 
 
 
 

* Use an all-pole circuit breaker whose contact gap is at least 3 mm.

 

 
 

 

There is risk of electric shock. Make sure that the power is turned off before performing work. 
Install the interface or provide support so that excessive force is not applied to the electrical wiring. 
Exercise caution not to damage the PWB Assy with screwdrivers and other objects. 
The PWB Assy is easily damaged by static electricity. Discharge any static electricity that has built 
up on your body. 
(You can discharge static electricity by touching a grounded device.)

 

Содержание SC-GIFN-E

Страница 1: ... 3 AIR CONDITIONER CONTROL SYSTEM INTERFACE KIT SC GIFN E Manual No 12 SC T 184 ...

Страница 2: ... Model 1 5 Control switch 1 6 Output switch 2 7 Wiring 2 8 Electric wiring diagram 3 9 A method of interface installation 4 10 Connectable centralized controller and gateway for connection 5 11 The number of connectable general purpose equipment 5 12 Display 6 ...

Страница 3: ... Level output ON OFF factory setting Reserved SW3 1 2 SW4 1 2 1 If the network you are connecting to is the old superlink you must change this setting Whether the actual network is the new superlink or the old superlink depends on the type of indoor units outdoor units etc Check with the agent or dealer 2 For details on switching the level pulse output see6 WARNNG CAUTION Ground the product Do not...

Страница 4: ... 53 Flat twin tinsel cord cord designation 60227 IEC 41 Use wires whose nominal cross sectional area is 0 75 mm2 or more for the power lines and other lines connected to the general purpose machine Make the ground wire from the wiring entrance to the interface connection area longer than the power supply lines Signal Line Specifications Communication mode Old superlink connection New superlink con...

Страница 5: ... 3 8 Electric Wiring Diagram 1 To detect either operation or error only 2 To detect both operation and error Connect terminal blocks 3 and 5 ...

Страница 6: ...ature range If the ambient temperature exceeds the range take measures for cooling such as installing a fan Note that using the product outside the operating temperature range can cause a malfunction Insert a circuit breaker in the power supply line Use an all pole circuit breaker whose contact gap is at least 3 mm There is risk of electric shock Make sure that the power is turned off before perfo...

Страница 7: ... purpose equipment One applicable unit can only connect with per general purpose equipment Some of the general purpose equipment can operate plural unit by connecting among each of the general purpose equipments Please refer to the instruction manual of the general purpose equipment regarding the details SC SL1NA E SC SL2NA E SC SL3NA AE BE SC SL4 AE BE SC BGWN Series SC WGWN Series SC LGWN Series...

Страница 8: ...al display Display when instructed Operation mode Off 1 Display as being instructed Anomalous status Normal Air flow rate No Data Display as being instructed Setting temperature deg Display as being instructed Room temperature Lower than 0deg Remote controller operation Unlock Display as being instructed Filter sign Off Display as being instructed Error code 1 Icon in Overview Monitor Screen is di...

Страница 9: ... 2 AIR CONDITIONER CONTROL SYSTEM Air Conditioning Refrigeration Systems Headquarters 16 5 2 chome Kounan Minato ku Tokyo 108 8215 Japan Fax 03 6716 5926 ...

Отзывы: