 3 

-

6. Installation of interface kit

 (SC-BIKN-E)

Connecting the indoor unit's connection cable to the interface

Ԙ

Remove

   the upper
   case

ԙ

Connect the indoor unit's

    connection cable

Ԛ

 Fix the cable with the

     cable clamp

Name of each part of the interface 

Terminal for indoor unit's
connection cable 
Terminal block for wired
remote control*

CNT terminal

Clamp for clamping the connection
cable for wired remote control*

ROM terminal

Wiring inlet
(top or back)

DIP switch (SW2) : [Factory setting : all ON] 

DIP switch (SW3) : [Factory setting : all OFF] 

Rotary switch (SW1) for address setting

Terminal block for super link E board (SC-ADNA-E)*

Clamp for clamping the connection cable for
super link E board (SC-ADNA-E)*

*Either the connection cables of super link E board (SC-ADNA-E) or of wired remote control is connectable.

Accessories included in package

Be sure to check all the accessories included in package.

Part name

Quantity

No.

٨

Installation must be carried out by a qualified installer.

If you install it by yourself, it may cause an electric shock, fire and personal injury , as a result of a system malfunction.

٨

Install it in full accordance with the instruction manual.

Incorrect installation may cause an electric shock, fire and personal injury.

٨

Electrical work must be carried out by a qualified electrician in accordance with the technical standard for electrical equipment, the

    indoor wiring standard and this instruction manual.

    Incorrect installation may cause an electric shock, fire and personal injury.

٨

Use the specific cables for wiring. And connect all the cables to terminals or connectors securely and clamp them with cable clamps in

    order for external forces not to be transmitted to the terminals directly.

     Incomplete connection may cause malfunction, and lead to heat generation and fire.

٨

Use the original accessories and specified components for installation.

    If the parts other than those prescribed by us are used, it may cause an electric shock, fire and sersonal injury.

Warnings

Warning

Always go along these instruction.

Safety precautions

Before use, please read these Safety Precautions thoroughly
before installation.

٨

All the cautionary items mentioned below are important safety related items to be taken

    into consideration, so be sure to observe them at all times.

Incorrect installation could lead to serious consequences such as death, major
injury or envirommental destruction.

٨

Symbols used in these precautions

٨

After completed installation, carry out trial operation to confirm no anomaly, and  ask the

    user to keep this installation manual in a good place for future reference.

Indoor unit's connection cable (cable length: 1.8m)
Wood screws (for mounting the interface: ø4

x

 25) 

Tapping screws (for the cable clump and the interface mounting bracket)
Interface mounting bracket
Cable clamp (for the indoor unit's connection cable)

1
2
3
1
1

Ԙ

ԙ

Ԛ

ԛ

Ԝ

CNT terminal connection cable (total cable length: 0.5m)

1

ԝ

*

Interface board

Clamp for clamping indoor
unit's connection cable

Switch

SW2-1

SW2-2

Setting

ON**

OFF

ON**

OFF

Function

CNT level input
CNT Pulse input
Wired remote control : Enable
Wired remote control : Disable

Switch

SW2-3

SW2-4

Setting

ON**

OFF

ON**

OFF

Function

External input (CNT input)
Operation permission/prohibition (CNT input)
Annual cooling : Enable***
Annual cooling : Disable***

** Factory setting

 *** Indoor fan control at low outdoor air temperature in cooling

Ԙ

Remove the upper case of the interface.

     •  Remove 2 screws from the interface casing before removal of upper casing.

ԙ

Connect the indoor unit's connection cable to the interface.

     •  Connect the connector of the indoor unit connection cable to the
         connector on the interface’s circuit board.

Ԛ

Fix the indoor unit's connection cable with the cable clamp.

     •  Cable can be brought in from the top or from the back.
     •  Cut out the punch-outs for the connection cables running into the casing with cutter.

ԛ

Connect the indoor unit's connection cable to the indoor control PCB. 

     •  Connect the indoor unit's connection cable to the indoor control PCB securely.
     •  Clamp the connection cable to the indoor control box securely with the cable clamp
         provided as an accessory.
     •  Regarding the cable connection to the indoor unit, refer to the instruction manual for
         indoor unit.

* SC-BIKN-EA only

RKZ012A088B

#

Содержание SC-BIKN-E

Страница 1: ... 3 AIR CONDITIONER CONTROL SYSTEM INTERFACE KIT SC BIKN E Manual No 08 SRK T 080 updated May 24 2013 ...

Страница 2: ...component layout 1 5 System configuration 2 6 Installation of interface kit 3 7 Wired remote control 8 8 Insatallation of wired remote control 9 9 Setting functions using the wired remote control 10 10 Super link adapter 14 11 Operation permission prohibition control 16 12 External control remote display control of input signal 17 ...

Страница 3: ...ctable devices Name Type Wired remote control RC E3 Super link adapter SC ADN E Central control SC SL1N E SC SL2N E SC SL3N AE BE 3 Exterior dimensions 4 Circuit board component layout Indoor unit connection terminal DIP switch SW2 Address setting rotary switch SW1 DIP switch SW3 Wired remote control and Super link adapter terminal block CNT terminal 120 135 34 18 2 83 5 1300 ...

Страница 4: ... turn multiple air conditioning units ON or OFF For users who want to exercise central control together with a package air conditioning system such as an office Remote start and stop and remote monitoring Interface kit SC BIKN E Super link adapter SC ADN E Central control SC SL1N E SC SL2N E SC SL3N AE BE Wired remote control RC E3 1 Either wireless remote control or wired remote control can be se...

Страница 5: ...nstruction Safety precautions Before use please read these Safety Precautions thoroughly before installation ٨All the cautionary items mentioned below are important safety related items to be taken into consideration so be sure to observe them at all times Incorrect installation could lead to serious consequences such as death major injury or envirommental destruction ٨Symbols used in these precau...

Страница 6: ... 4 Deleted ...

Страница 7: ...m the indoor unit Be sure not to extend the connection cable on site If the connection cable is extended malfunction may occur Fix the interface on the wall pillar or the like Cut out the punch outs for the connection cables running into the casing with cutter ԘRecess the electrical box procured locally and connection cables in the wall ԙMount the lower casing of the interface to the electrical bo...

Страница 8: ...l remote control unit procured locally to CNT terminal ԙIn case of the pulse input switch OFF the DIP switch SW2 1 on the interface PCB ԚWhen setting operation permission prohibition mode switch OFF the DIP switch SW2 3 on the interface PCB Connection of super link E board Functions of CNT connector ԘSwitch ON the DIP switch SW2 2 Factory setting ON on the interface PCB ԙWiring connection between ...

Страница 9: ...ired remote control with reference to the attached instruction manual of wired remote control B 0 3mm2 x 2 core cable should be used for the wiring of wired remote control C Maximum length of wiring is 600m If the length of wiring exceeds 100m change the size of cable as mentioned below 100m 200m 0 5mm2 x 2 core 300m or less 0 75mm2 x 2 core 400m or less 1 25mm2 x 2 core 600m or less 2 0mm2 x 2 co...

Страница 10: ... clean operation or allergen clear operation cannot be selected FAN SPEED button This button is used to set the airflow volume AUTO HI POWER or ECONO cannot be selected Cannot be used LOUVER button This button is used to operate stop the swing louver Up down swing only This button is used to apply the timer operation setting Cannot be used Central control display Displayed when the air conditionin...

Страница 11: ... 9 ...

Страница 12: ...n is by degree C Temperature indication is by degree F In case of Single split series by connecting ventilation device to CNT of the indoor printed circuit board the operation of ventilation device is linked with the operation of indoor unit In case of Single split series by connecting ventilation device to CNT of the indoor printed circuit board you can operate stop the ventilation device indepen...

Страница 13: ...ed or cooling thermostat is OFF the fan perform extra operation for an hour After cooling is stopped or cooling thermostat is OFF the fan perform extra operation for six hours After heating is stopped or heating thermostat is OFF the fan does not perform extra operation After heating is stopped or heating thermostat is OFF the fan perform extra operation for half an hour After heating is stopped o...

Страница 14: ...f selected function is indicated For example STANDARD If 02 FAN SPEED SET is selected Press SET button SET COMPLETE will be indicated and the setting will be completed Then after No and function indication returns set as the same procedure if you want to set continuously and if to finish go to 7 When plural indoor units are connected to a remote control press the AIRCON NO button which allows you ...

Страница 15: ...g the upper limit is set upper limit value will be sent to the indoor unit But the indication is the same as the temperature set If lower limit value is set During except heating even if the value lower than the lower limit is set lower limit value will be sent to the indoor unit But the indication is the same as the temperature set 2 How to set upper and lower limit value Previous button It is po...

Страница 16: ...e remote control master slave device using the slide switch on the remote control board 5 Set up 0 to F using the address rotary switch on the indoor unit board when controlling the indoor unit with the multiple remote control Up to 1500 m for 0 75 mm2 and up to 1000 m for 1 25mm2 Do not use 2 0 mm2 It may cause an error Connect grounding on both ends of the shielding wire For the grounding method...

Страница 17: ...t the location where the ambient temperature stays within the range If it exceeds the specification make sure to provide solution such as installing a cooling fan When used outside of the range it may cause abnormal operation Check the LED 3 green and LED 2 red on the SL E board for flashing SL E board LEDs Red Off Off One flash Two flashes Three flashes Four flashes Off Flashing Flashing Flashing...

Страница 18: ...l signal b The air conditioner operation is stopped when the CnT input is changed from ON to OFF 4 When the operation permission prohibition mode is set to effective by the indoor function setting selected by the remote control the operation depends on 1 above When the DIP switch SW2 3 is ON Normal operation is enable when shipping When CnT input is set to ON the operation starts and if the input ...

Страница 19: ...12V relay provided by the customer is outputted during operation Heating output Power to engage DC 12V relay provided by the customer is outputted during the heating operation Compressor OPERATION output Power to engage DC 12V relay provided by the customer is outputted while the com pressor is operating MALFUNCTION output When any error occurs the power to engage DC 12V relay provided by the cust...

Страница 20: ... 2 AIR CONDITIONER CONTROL SYSTEM No 116 1 1A R Air Conditioning Refrigeration Systems Headquarters 16 5 2 chome Kounan Minato ku Tokyo 108 8215 Japan Fax 03 6716 5926 ...

Отзывы: