(2) Silent mode control
(Note) With CnG2 terminal and 7-segment display [P10]-[3] for silent mode 1(Factory default) or with CnG2 terminal and 7-segment display [P10]-[8]
for silent mode 2 (Setting on site) It is also avilable to use other terminals as follows.
CnS2: [P08]-[3] or -[8]
CnS1: [P07]-[3] or -[8]
CnG1: [P09]-[3] or -[8]
(a) Silent mode is commanded either from the indoor unit (remore control setting) or from the master outdoor unit (CnG2).
(b) When the "Silent mode start" signals is received from one of indoor units, it enters the silent mode operation.
(c) When CnG2 of master unit is shorted after setting function [P10]-[3] (Silent mode 1) or [P10]-[8] (Silent mode 2) with
7-segment display, it enters the silent mode operation. (If the signal is input to the slave unit, it is invalid)
(Note) Silent mode 1 and 2 can not be set at same time
(Note) In case of external input of silent mode 2, following temperature conditions are disregarded.
(d) When the "Silent mode start" signal from indoor unit and the "Silent mode" signal from outdoor unit are received, it enters
the silent mode operation under "or"condition.
(e) When silent mode signals from all indoor units become "Silent mode end" and when silent mode signal input to CnG2 on
outdoor unit becomes open, the silent mode operation is reset.
(f) The operation of silent mode 1 is effective within the following temperature range.
• Cooling
• Heating
Outdoor air temperature
Outdoor air temperature
(i) Silent mode 0,1 : Effect on field A,B
(g) Silent mode setting
Silent mode setting can be changed with 7-segment “P05” on the outdoor control PCB.
(ii) Silent mode 2,3 : Effect on field B
Valid (Field B)
Valid (Field A)
Invalid
29
31°C
27
Valid (Field A)
Valid (Field B)
Invalid
2
4
6°C
P05 setting
000 (Factry default)
001
002
003
Silent mode setting
Silent mode setting 0
Silent mode setting 1
Silent mode setting 2
Silent mode setting 3
(h) Sound level (Reference data)
Model
SPL
Sound
pressure level
for cooling
SPL
Sound
pressure level
for heating
SPL
Silent
mode
setting 0
SPL
Silent
mode
setting 1
SPL
Silent
mode
setting 2
SPL
Silent
mode
setting 3
PWL
Cooling
PWL
Heating
(dB(A))
(dB(A))
(dB(A))
(dB(A))
(dB(A))
(dB(A))
(dB(A))
(dB(A))
FDC(S)280KXZE1
55
57
55
51
47
43
75
76
FDC(S)335KXZE1
61
58
61
57
53
49
81
78
FDC(S)400KXZE1
60
62
60
56
52
48
81
83
FDC(S)450KXZE1
61
62
61
57
53
49
81
83
FDC(S)475KXZE1
61
62
61
57
53
49
81
83
FDC(S)500KXZE1
61
62
61
57
53
49
81
83
FDC(S)560KXZE1
64
66
64
60
56
52
84
86
'14 • KX-SM-202