161
-
'14 • KX-SM-202
■
Refrigerant charge quantity calculation notes in case outdoor unit capacity is 475,500 and 560
※
.
※
The combination unit is not applicable
●
In case when the outdoor unit capacity is 475~560 and the pipe length (X,Y) is in the following conditions,
please calculate the reduction refrigerant quantity (E).
・
X
<
20m
and
Y
<
10m.
(
X
:
The length from the outdoor unit to the furthest indoor unit.
Y
:
Main pipe length.
)
①
kg
+ ②
kg
- ③
kg =
①
+
②
-
③
kg
●
The calculation of Reduction refrigerant quantity (E)
・
If total indoor units capacity is less than outdoor unit capacity, reduction refrigerant quantity (E) is 2kg.
Outdoor unit capacity
>
Total indoor units capacity
・・・・・・
・
If total indoor units capacity is same or larger than outdoor unit capacity, reduction refrigerant quantity (E) is the connecting number
of indoor units of refrigerant reduction ×0.5 (kg).
Outdoor unit capacity
≦
Total indoor units capacity
・・・・・・
・
Indoor units list of the refrigerant reduction
<
Example
>
X
=
19m
(<
20m
)
Y
=
9m
(<
10m
)
Outdoor unit capacity
=
560
Total indoor units capacity
=
643
(=
FDT90
+
FDT140
+
FDUM140
+
FDT71
+
FDU112
+
FDUM90
)
The number of indoor units of the refrigerant reduction
=
3 units (FDT140,FDUM140,FDUM90 : 3 units)
Outdoor unit capacity:560
≦
Total indoor units capacity:64
PCB011H021
※
Please calculate the additional refrigerant charge quantity
(
D)
according to the formula on the installation sheet
Total additional
refrigerant
quantity (D)
※
Factory charge
475,500,560
:
11.5kg
Reduction refrigerant
quantity (E)
Total refrigerant quantity
in the system
(Total charge)
(②-③:
Additional charge in this case
)
(
E)=2kg
(E)=Connecting number of indoor units of refrigerant reduction
×
0.5
(kg)
(
E)=3×0.5
=
1.5(kg)
FDT140
,
FDTW140
,
FDU140
,
FDUM140
,
FDT160
,
FDU160
,
FDUM160
,
FDU90
3