'14 • KX-SM-202
5) 2 outdoor units combination use (Model 735)
Model 00 (Master) + (Slave)
Master unit Slave unit
CM01
CM11
(CM1)
(CM1)
Range of the compressor operation speed relative to load is as follows. Following table is applicable when CM0 starts initially.
System load range
0
1
2
Local load range
0
1
1
Master unit
CM0
0rps
20−112rps
52−120rps
Slave unit
CM
0rps
0rps
31−70rps
Model (Master) + 00 (Slave)
Master unit Slave unit
CM01
CM11
(CM1)
(CM1)
Range of the compressor operation speed relative to load is as follows. Following table is applicable when CM0 starts initially.
System load range
0
1
2
Local load range
0
1
1
Master unit
CM0
0rps
21−65rps
31−70rps
Slave unit
CM
0rps
0rps
52−120rps
6) 2 outdoor units combination use (Model 800, 850, 900)
Master unit Slave unit
CM01
CM11
(CM1)
(CM1)
Range of the compressor operation speed relative to load is as follows. Following table is applicable when CM0 starts initially.
System load range
0
1
2
Local load range
0
1
1
Master unit
CM0
0rps
20−65rps
31−120rps
Slave unit
CM
0rps
0rps
31−120rps
7) 2 outdoor units combination use (Model 950, 1000, 1060, 1120)
Master unit Slave unit
CM01
CM11
(CM1)
(CM1)
CM02
CM12
(CM2)
(CM2)
Range of the compressor operation speed relative to load is as follows. Following table is applicable when CM0 starts initially.
System load range
0
1
2
Local load range
0
1
1
2
Master
unit
CM0
0rps
20−112rps
31−112rps
31−120rps
CM0
0rps
0rps
0rps
31−120rps
Slave
unit
CM
0rps
0rps
31−112rps
31−120rps
CM
0rps
0rps
0rps
31−120rps