3. Precautions for Use of the Inverter
3.1 Electro-magnetic interference (EMI) and leakage currents
1
2
3
4
5
6
7
8
9
10
• Specification example (ZCAT3035-1330 by TDK)
The impedance values above are reference values, and not guaranteed values.
EMI measure example
NOTE
• For compliance with the EU EMC Directive, refer to the document enclosed with the product.
Item
Description
Impedance (
Ω
)
10 to 100 MHz
80
100 to 500 MHz
150
Outline dimension drawings
(mm)
34
1
TDK
39
1
Product name
Lot number
30
1
Cable fixing band
mount
13
1
Inverter
Sensor
Use a twisted pair shielded cable.
Enclosure
Decrease carrier frequency.
Motor
M
Install
filter
Do not earth (ground) control cable.
Inverter
power
supply
Install filter on
inverter output side.
Separate inverter and
power line by more than
30 cm (at least 10 cm)
from sensor circuit.
Control
power
supply
Do not earth (ground)
enclosure directly.
Power
supply for
sensor
Use 4-core cable for motor
power cable and use one cable
as earth (ground) cable.
Do not earth (ground) shield but
connect it to signal common cable.
EMC
filter