48
2. Installation and Wiring
2.6 Control circuit
Safety stop function operation
*1
The terminal ON state shows that the terminal is conducted (the line is closed), and the OFF state shows that the terminal is not conducted (the
line is open).
*2
When not using the safety stop function, short across terminals S1 and PC and terminals S2 and PC to use the inverter. (In the initial status,
terminals S1 and PC and terminals S2 and PC are respectively shorted with shorting wires.)
*3
If any of the faults shown in the following table occurs, terminal SO, the SAFE signal, and the SAFE2 signal are turned OFF.
*4
When the internal safety circuit is operated normally (no fault occurs), terminal SO, the SAFE signal, and the SAFE2 signal remain ON until
"E.SAF" is displayed. Terminal SO, the SAFE signal, and the SAFE2 signal are turned OFF when "E.SAF" is displayed.
*5
"SA" is displayed when terminals S1 and S2 are identified as OFF due to the internal safety circuit failure.
*6
If another fault occurs when the fault E.SAF occurs, the other fault indication may be displayed.
*7
If another warning occurs when the warning SA occurs, the other warning indication may be displayed.
*8
The ON/OFF state of the output signal is the one for the positive logic. In negative logic, the signal status is opposite.
*9
To assign the functions of the SAFE signal and SAFE2 signal to output terminals, set values shown in the following table in any two parameters
from
Pr.190 to Pr.196 (Output terminal function selection)
.
*10 The use of the SAFE signal and SAFE2 signal has not been certified for compliance with safety standards.
For details, refer to the FR-E800 Instruction Manual (Functional Safety).
Input
power
Internal
safety
circuit
status
Input terminal
Output
terminal
Output signal
Inverter
operating
status
Operation panel
indication
S1
S2
SO
SAFE
SAFE2
OFF
—
—
—
OFF
OFF
OFF
Output shutoff
(Safe state)
Not
displayed
Not
displayed
ON
Normal
ON
ON
OFF
ON
Operation
enabled
Not
displayed
Not
displayed
Normal
ON
OFF
OFF
OFF
OFF
Output shutoff
(Safe state)
Displayed
Displayed
Normal
OFF
ON
OFF
OFF
OFF
Output shutoff
(Safe state)
Displayed
Displayed
Normal
OFF
OFF
ON
Output shutoff
(Safe state)
Not
displayed
Displayed
Fault
ON
ON
OFF
OFF
OFF
Output shutoff
(Safe state)
Displayed
Not
displayed
Fault
ON
OFF
OFF
OFF
OFF
Output shutoff
(Safe state)
Displayed
Displayed
Fault
OFF
ON
OFF
OFF
OFF
Output shutoff
(Safe state)
Displayed
Displayed
Fault
OFF
OFF
OFF
OFF
OFF
Output shutoff
(Safe state)
Displayed
Displayed
Fault type
Operation panel
indication
Fault type
Operation panel
indication
Option Fault
E.OPT
Overspeed occurrence
E.OS
Communication option error
E.OP1
Speed deviation excess detection
E.OSD
Parameter storage device fault (control
circuit board)
E.PE
Brake sequence fault
E.MB4 to E.MB7
Retry count excess
E.RET
CPU fault
E.CPU
Parameter storage device fault (main
circuit board)
E.PE2
E.5 to E.7
Safety circuit fault
E.SAF
Internal circuit fault
E.13
Output signal
Pr.190 to Pr.196 setting
Positive logic
Negative logic
SAFE
80
180
SAFE2
81
181