GB
2
In case of collective installation and continuous installation
•
When multiple units are installed adjacent to each other, secure enough space to allow for air circulation and passageways between groups of units as shown in the
figures.
* Leave both sides of each group of units open.
•
As with single installation, if the wall height exceeds the height limit, widen the space in the front and the back of a given group of units by the amount that exceeds
the limit (labeled <h> in the figure).
•
If there is a wall at both the front and the rear of the unit, install up to six units (three units : P500) consecutively in the side direction and provide a space of 1000 mm
or more as inlet space/passage space for each six units (three units : P500).
[Fig. 6.0.2]
(1) Side-by-side installation
<The space on both sides of a given group of units is minimum.>
<The space on both sides of a given group of units is minimum.>
h
500
300 + h
450 + h
h
30
h
500
h
450 + h
100 + h
100
*
*
*
*
Unit height
Unit height
(2) Face-to-face installation
<There are walls in the front and the back of a given group of units.>
<There is a wall on one side.>
h
h
500
h
450 + h
450
450
450
15 + h
450
100 + h
*
*
Unit height
Unit height
(3) Combination of face-to-face and side-by-side installations
<There are walls in the front and the back of a given group of units.>
<There is a wall on one side and either the front or the back of a given group of unit.>
h
500
h
500
h
500
h
300 + h
300 + h
900
900
1000
+ h
300 + h
*
*
*
*
Unit height
(Unit : mm)