background image

3-3. PIPE CONNECTION

‡ )DVWHQÀDUHQXWZLWKDWRUTXHZUHQFKDVVSHFL¿HGLQWKHWDEOHUHIHUWR

‡ :KHQIDVWHQHGWRRWLJKWÀDUHQXWPD\HYHQWXDOO\EUHDNDQGFDXVHUHIULJHUDQWOHDNDJH

•  Be sure to wrap insulation around the piping. Direct contact with the bare piping may result 

in burns or frostbite.

Indoor unit connection

Connect both liquid and gas pipings to indoor unit.

‡ $SSO\DWKLQFRDWRIUHIULJHUDWLRQRLO-RQWKHÀDUHGHQGVRIWKHSLSHV'RQRWDSSO\UH

-

frigeration oil on screw threads. Excessive tightening torque will result in damage on the 

screw.

‡ 7RFRQQHFW¿UVWDOLJQWKHFHQWHUWKHQWLJKWHQWKH¿UVWWRWXUQVRIÀDUHQXWE\KDQG

•  Use tightening torque table above as a guideline for indoor unit side joints, and tighten 

XVLQJWZRZUHQFKHV([FHVVLYHWLJKWHQLQJGDPDJHVWKHÀDUHVHFWLRQ

Outdoor unit connection

Connect pipes to stop valve pipe joint of the outdoor unit following the same procedure 

detailed in Indoor unit connection.

•  For tightening, use a torque wrench or spanner.

4-1. PURGING PROCEDURES AND LEAK TEST

1) Remove service port caps from stop valves on both sides of refrigerant lines. (The stop 

valves are fully closed when shipped.) Leave closed.

2) Connect gauge manifold to ports of stop valves.

4-5. EXPLANATION TO THE USER

•  Using the OPERATING INSTRUCTIONS, explain to the user how to use the air conditioner 

WKHUHPRWHFRQWUROOHUUHPRYLQJWKHDLU¿OWHUVSODFLQJRUUHPRYLQJWKHUHPRWHFRQWUROOHUIURP

the remote controller holder, cleaning methods, precautions for operation, etc.)

•  Recommend that the user read the OPERATING INSTRUCTIONS carefully.

Stop valve for 

GAS

Stop valve cap

(Torque 15 to 

22 ft-lb, 19.6 to 

29.4 N•m, 200 

WRNJIƒFP

Vacuum pump (or the vacuum 

pump with the function to 

SUHYHQWWKHEDFNÀRZ

Gauge manifold valve 

(for R410A)

Compound pressure gauge 

(for R410A)

–14.7 psi [Gauge] 

(–0.101 Mpa)

Handle 

Low

Handle High

Adapter for 

preventing the 

EDFNÀRZ

Charge hose 

(for R410A)

*Close

*Open

Hexagonal wrench

Precautions when using the control valve When attaching the control valve to 

the service port, valve core may de-

form or loosen if excess pressure is 

applied. This may cause gas leak.

Service port

Charge hose 

Body

Close

Open

Control valve

A

When attaching the control valve to 

the service port, make sure that the 

valve core is in closed position, and 

then tighten part A. Do not tighten 

part A or turn the body when valve 

core is in open position.

Service port cap

(Torque 10 to 13 ft 

-Ib, 13.7 to 17.7 N•m, 

140 to 180 kgf•cm)

*4 to 5 turns

3) Evacuate the system to 4000 microns from both service valves. System manifold gauges 

must not be used to measure vacuum. A micron gauge must be used at all times. Break 

the vacuum with Nitrogen(N2) into the discharge service valve to 0 PSIG.

4) Evacuate  the  system  to  1500  microns.  Break  the  vacuum  with  Nitrogen(N2)  into  the 

discharge service valve to 0 PSIG.

5) Evacuate the system to 500 microns. 

6) Close gauge manifold valves, stop the pump, and conduct a 30 minute rise test.

7) System should hold 500 microns for a minimum of 1 hour.

8) Fully open all stop valves on both sides of gas pipe and liquid pipe. Operating without fully 

opening lowers the performance and this causes trouble.

9) Refer to 1-3 and charge the prescribed amount of additional refrigerant if needed. Be 

sure to charge slowly with liquid refrigerant. Otherwise composition of the refrigerant in 

the system may be changed and affect performance of the air conditioner.

10) Remove gauge manifolds and replace service port caps and tighten.

11) Leak test

4-2. TEST RUN

1) Insert power supply plug into the power outlet and/or turn on the 

breaker.

2) Press the E.O. SW once for COOL, and twice for HEAT operation. 

Test run will be performed for 30 minutes. If the left lamp of the 

operation indicator blinks every 0.5 seconds, inspect the indoor/

outdoor unit connecting wire (A) for mis-wiring. After the test run, 

emergency mode (set temperature 75°F [24°C]) will start.

3) To stop operation, press the E.O. SW several times until all LED 

lamps turn off. Refer to operating instructions for details. 

Stop valve for LIQUID

Pressure gauge

(for R410A)

Checking the remote (infrared) signal reception

Press the ON/OFF button on the remote controller (3) and listen for an audible indicator 

from the indoor unit. Press the ON/OFF button again to turn the air conditioner off.

•  Once the compressor stops, the restart preventive device operates so the compressor will 

not operate for 3 minutes to protect the air conditioner.

4-3. AUTO RESTART FUNCTION

This product is equipped with an auto restart function. When the power supply is cut off 

during operation, such as during blackouts, the function automatically starts operation in 

the previous setting once the power supply is resumed. (Refer to the operating instructions 

for details.) 

Caution:

•  After test run or remote signal reception check, turn off the unit with the E.O. SW or the 

remote controller before turning off the power supply. If this procedure is not performed, 

the unit will automatically begin operation when power supply is resumed.

To the user

•  After installing the unit, explain to the user about auto restart function. 

•  If auto restart function is unnecessary, it can be deactivated. Consult the service rep-

resentative to deactivate the function. Refer to the service manual for details.

3-4. INSULATION AND TAPING

1) Cover piping joints with pipe cover.

2) For outdoor unit side, insulate the piping, including valves.

3) Apply piping tape (G) starting from the connection on the outdoor unit.

•  When piping has to be installed through a ceiling, closet or where the temperature and 

KXPLGLW\DUHKLJKXVHDGGLWLRQDO¿HOGVXSSOLHGLQVXODWLRQWRSUHYHQWFRQGHQVDWLRQ

 WARNING

When installing the unit, securely connect the refrigerant pipes before starting 

the compressor.

4-4. SETTING THE INSTALLATION POSITION

Be sure to set the remote controller in accordance with the installed position of the indoor 

unit.

Installation position: 

Left: Distance to objects (wall, cabinet, etc.) is less  

than 19-11/16 in. (50 cm) to the left

Center: Distance to objects (wall, cabinet, etc.) is  

more than 19-11/16 in. (50 cm) to the left and right

Right: Distance to objects (wall, cabinet, etc.) is less  

than 19-11/16 in. (50 cm) to the right

(Left) (Center)(Right)

Note:

The installation position can be set only when all the following conditions are met: 

•  The remote controller is powered off. 

•  Weekly timer is not set.

•  Weekly timer is not being edited.

1) Hold down 

 on the remote controller for 2 seconds to enter the position setting mode.

2) Select the target installation position by pressing 

. (Each press of the 

 displays 

WKHSRVLWLRQVLQRUGHUFHQWHUĺULJKWĺOHIW

3) Press 

 to complete the position setting.

Installation position

Left

Center

Right

Remote controller 

display

Emergency 

operation 

switch

(E.O. SW)

4.  PURGING PROCEDURES, LEAK TEST, AND TEST RUN

Содержание Trane NTXWPH06B112A Series

Страница 1: ...e unit make sure that no substance RWKHU WKDQ WKH VSHFL HG UHIULJHUDQW 5 HQWHUV WKH UHIULJHUDQW FLUFXLW Any presence of foreign substance such as air can cause abnormal pressure rise and may result in explosion or injury The use of any refrigerant other than that VSHFL HG IRU WKH V VWHP ZLOO FDXVH PHFKDQLFDO IDLOXUH V VWHP PDOIXQFWLRQ RU XQLW breakdown In the worst case this could lead to a seriou...

Страница 2: ...ing to before use Where it can be easily drained At a distance 3 ft 1 m or more away from a TV and radio Operation of the air conditioner may interfere with UDGLR RU 79 UHFHSWLRQ Q DPSOL HU PD EH UHTXLUHG IRU the affected device Q D SODFH DV IDU DZD DV SRVVLEOH IURP ÀXRUHVFHQW DQG incandescent lights In order to make the infrared remote control operate the air conditioner normally The heat from th...

Страница 3: ...by drain water or damaged by frozen drain water 4 7 8 in 122 5 mm or more 3 3 8 in 85 mm or more 5 11 16 in 143 mm or more for left left rear piping using spacer 2 3 16 in 56 mm or more 5 1 4 in 132 5 mm or more 33 1 16 13 3 4 14 5 8 19 11 16 Air inlet Air inlet Air inlet Air inlet Air inlet 6 7 8 15 3 8 13 Air outlet 2 3 8 13 16 slot 1 9 16 40 840 175 500 Air inlet 390 330 349 371 Air outlet 2 10...

Страница 4: ...terminal of electrical parts box 7 Process the end of indoor outdoor unit connecting wire A Fig 3 Attach it to the terminal block Be careful not to make mis wiring Attach the wire to the terminal block securely so that its core cannot be seen and no external force affects the connecting section of the terminal block 8 Firmly tighten the terminal screws After tightening verify that the wires are ti...

Страница 5: ...ection to which the drain hose is to be attached at the rear of the indoor unit Fig 3 Insert a screwdriver into the hole on the cap and insert the cap fully into the drain pan 5 Insert the drain hose fully into the drain pan at the back right of the indoor unit Fig 4 Check if the hose is hooked securely to the projection of its inserting part at the drain pan 6 Insert the drain hose into wall hole...

Страница 6: ...HIHFWLYH FXW RII WKH VHFWLRQ DQG UHSHDW SURFHGXUH Terminal block Power supply cord K Indoor outdoor unit connecting wire A Make ground wire a little longer than others More than 4 in 100 mm For future servicing leave some slack in the connecting wires Be sure to attach each screw to its corre spondent terminal when securing the cord and or the wire to the terminal block Pipe diameter inch mm B inc...

Страница 7: ...Otherwise composition of the refrigerant in the system may be changed and affect performance of the air conditioner 10 Remove gauge manifolds and replace service port caps and tighten 11 Leak test 4 2 TEST RUN 1 Insert power supply plug into the power outlet and or turn on the breaker 2 Press the E O SW once for COOL and twice for HEAT operation Test run will be performed for 30 minutes If the lef...

Страница 8: ...ING THE INDOOR UNIT Remove the bottom of the indoor unit from the installation plate When releasing the corner part release both left and right bottom corner part of indoor XQLW DQG SXOO LW GRZQZDUG DQG IRUZDUG DV VKRZQ LQ WKH JXUH RQ WKH ULJKW Installation procedure 1 Install the panel assembly following the removal procedure in reverse 2 Be sure to press the positions as indicated by the arrows ...

Отзывы: