3-1. CONNECTING WIRES FOR OUTDOOR UNIT

1) Remove the service panel.

2) Remove the conduit cover.

3) Attach the conduit connectors to the conduit plate with lock nuts then secure it against unit with 

screws.

4) Connect the ground wires of indoor/outdoor unit connecting wire (A) and power supply cord (K) 

to the TB support.

5) Loosen the terminal screws, then attach indoor/outdoor unit connecting wire (A) and power sup-

ply cord (K) from the indoor unit correctly to the terminal block. Attach the wires to the terminal 

block securely so that the cores cannot be seen, and no external force affects the connecting 

section of the terminal block. 

6) Firmly tighten the terminal screws. After tightening, verify that the wires are tightly fastened.

7) Install the conduit cover.

8) Install the service panel securely.

3-2. FLARE CONNECTION

1) Cut the copper pipe as straight as possible with a pipe cutter.  (Fig. 1, 2)

2) Remove all burrs from the cut section of the pipe, ensuring that precautions are taken to avoid 

getting metal shavings into the piping. (Fig. 3)

5HPRYHÀDUHQXWVDWWDFKHGWRLQGRRUDQGRXWGRRUXQLWVWKHQSXWWKHPRQSLSH

4) Flaring work (Fig. 4, 5). Firmly hold copper pipe in the dimension shown in the table. Select A 

inch (mm) from the table according to the tool you use.

5) Check 

‡ &RPSDUHWKHÀDUHGZRUNZLWK)LJ

‡ ,IÀDUHLVGHIHFWLYHFXWRIIWKHVHFWLRQDQGUHSHDWSURFHGXUH

Terminal block

Power supply cord (K)

Indoor/outdoor unit 

connecting wire (A)

•  Make ground wire a little longer than others. 

(More than 4 in. [100 mm])

•  For future servicing, leave some slack in the 

connecting wires.

•  Be sure to attach each screw to its corre-

spondent terminal when securing the cord 

and/or the wire to the terminal block.

Pipe diameter 

inch (mm)

B inch

(mm)

A inch (mm)

Tightening torque

Clutch 

type tool 

for R410A

Clutch 

type tool 

for R22

Wing nut 

type tool 

for R22

ft-lb

(kgf•cm)

N•m

ø1/4 (6.35)

21/32 

(17)

0 to 0.02

(0 to 0.5)

0.04 to 

0.06

(1.0 to 1.5)

0.06 to 

0.08

(1.5 to 2.0)

10 to 13

(140 to 180) 13.7 to 17.7

ø3/8 (9.52)

7/8 

(22)

25 to 30

(350 to 420) 34.3 to 41.2

ø1/2 (12.7)

1-1/32 

(26)

0.08 to 

0.10

(2.0 to 2.5)

36 to 42

(500 to 575) 49.0 to 56.4

ø5/8 (15.88)

1-5/32 

(29)

54 to 58

(750 to 800) 73.5 to 78.4

Power supply cord (K)

L1 L2

Service panel

Lock nut

Conduit cover

Conduit plate

Conduit pipe

Grounding  

terminal

Copper 

pipe

Good

90°

Tilted

No good

Fig. 1

Fig. 2

Burr

Copper pipe

Spare reamer

Pipe cutter

Fig. 4

Fig. 3

Smooth all around

Even length 

all around

Inside is shin-

ing without any 

scratches.

Fig. 5

Fig. 6

Clutch type

Flaring tool

Wing nut type

Uneven Burred

TB support

<06/09/12>

<15/18>

Terminal block

to conduit cover

Power supply cord (K)

Indoor/outdoor unit 

connecting wire (A)

TB support

Grounding  

terminal

Service panel

Lock nut

Conduit cover

Conduit 

plate

Conduit pipe

B

Flare nut

Die

Copper pipe

to conduit cover

Lead 

wire

19/32 in.

(15 mm)

3. OUTDOOR UNIT INSTALLATION

Содержание Trane NTXWPH06B112A Series

Страница 1: ...e unit make sure that no substance RWKHU WKDQ WKH VSHFL HG UHIULJHUDQW 5 HQWHUV WKH UHIULJHUDQW FLUFXLW Any presence of foreign substance such as air can cause abnormal pressure rise and may result in explosion or injury The use of any refrigerant other than that VSHFL HG IRU WKH V VWHP ZLOO FDXVH PHFKDQLFDO IDLOXUH V VWHP PDOIXQFWLRQ RU XQLW breakdown In the worst case this could lead to a seriou...

Страница 2: ...ing to before use Where it can be easily drained At a distance 3 ft 1 m or more away from a TV and radio Operation of the air conditioner may interfere with UDGLR RU 79 UHFHSWLRQ Q DPSOL HU PD EH UHTXLUHG IRU the affected device Q D SODFH DV IDU DZD DV SRVVLEOH IURP ÀXRUHVFHQW DQG incandescent lights In order to make the infrared remote control operate the air conditioner normally The heat from th...

Страница 3: ...by drain water or damaged by frozen drain water 4 7 8 in 122 5 mm or more 3 3 8 in 85 mm or more 5 11 16 in 143 mm or more for left left rear piping using spacer 2 3 16 in 56 mm or more 5 1 4 in 132 5 mm or more 33 1 16 13 3 4 14 5 8 19 11 16 Air inlet Air inlet Air inlet Air inlet Air inlet 6 7 8 15 3 8 13 Air outlet 2 3 8 13 16 slot 1 9 16 40 840 175 500 Air inlet 390 330 349 371 Air outlet 2 10...

Страница 4: ...terminal of electrical parts box 7 Process the end of indoor outdoor unit connecting wire A Fig 3 Attach it to the terminal block Be careful not to make mis wiring Attach the wire to the terminal block securely so that its core cannot be seen and no external force affects the connecting section of the terminal block 8 Firmly tighten the terminal screws After tightening verify that the wires are ti...

Страница 5: ...ection to which the drain hose is to be attached at the rear of the indoor unit Fig 3 Insert a screwdriver into the hole on the cap and insert the cap fully into the drain pan 5 Insert the drain hose fully into the drain pan at the back right of the indoor unit Fig 4 Check if the hose is hooked securely to the projection of its inserting part at the drain pan 6 Insert the drain hose into wall hole...

Страница 6: ...HIHFWLYH FXW RII WKH VHFWLRQ DQG UHSHDW SURFHGXUH Terminal block Power supply cord K Indoor outdoor unit connecting wire A Make ground wire a little longer than others More than 4 in 100 mm For future servicing leave some slack in the connecting wires Be sure to attach each screw to its corre spondent terminal when securing the cord and or the wire to the terminal block Pipe diameter inch mm B inc...

Страница 7: ...Otherwise composition of the refrigerant in the system may be changed and affect performance of the air conditioner 10 Remove gauge manifolds and replace service port caps and tighten 11 Leak test 4 2 TEST RUN 1 Insert power supply plug into the power outlet and or turn on the breaker 2 Press the E O SW once for COOL and twice for HEAT operation Test run will be performed for 30 minutes If the lef...

Страница 8: ...ING THE INDOOR UNIT Remove the bottom of the indoor unit from the installation plate When releasing the corner part release both left and right bottom corner part of indoor XQLW DQG SXOO LW GRZQZDUG DQG IRUZDUG DV VKRZQ LQ WKH JXUH RQ WKH ULJKW Installation procedure 1 Install the panel assembly following the removal procedure in reverse 2 Be sure to press the positions as indicated by the arrows ...

Отзывы: