background image

•  Connect wires to the appropriate terminals

•  For future servicing, leave some slack in the connecting wires.

•  Make ground wire a little longer than oth-

ers. (More than 1-9/16 in. [40 mm])

2-1. ATTACHING THE INSTALLATION PLATE 

‡ )LQGDVWXGLQWKHZDOOWRDWWDFKLQVWDOODWLRQSODWHKRUL]RQWDOO\E\WLJKWHQLQJWKH¿[LQJ

VFUHZV¿UPO\

•  To prevent installation plate (1) from vibrating, be sure to install the attachment screws in 

the holes indicated in the illustration. For added support, additional screws may also be 

installed in other holes.

•  When the indoor unit is to be attached to a concrete wall using recessed bolts, secure 

installation plate (1) using 7/16 in. x 13/16 in. · 7/16 in. x 1 in. (11 mm × 20 mm · 11 mm × 

26 mm) oval hole (17-3/4 in. [450 mm] pitch).

‡ ,IWKHUHFHVVHGEROWLVWRRORQJFKDQJHLWIRUDVKRUWHURQH¿HOGVXSSOLHG

Wall

Outdoor side

2-2. DRILLING

1) Determine where the holes will be located on the wall.

2) Drill a ø3 in. (75 mm) hole. The outdoor side should be 6/32 to 9/32 in. (5 to 7 mm) lower 

than the indoor side.

3) Insert wall hole sleeve (C).

2-3. CONNECTING WIRES FOR INDOOR UNIT

Note:

The unit should be installed by a licensed contractor/electrician. If required by applicable 

national, state and local codes; a disconnect switch will need to be installed when the 

indoor unit is powered from the outdoor unit.

1) Remove the panel assembly. (Refer to 5-1.)

2) Place the upper part of the indoor unit on the installation plate.

3) Remove corner box and electrical cover.

4) Remove display and i-see sensor assembly, conduit cover and conduit plate.

5) Attach straight joint (for rear piping) / elbow joint (for right, left, or downward piping) to 

conduit plate with lock nut. The thread of the installed conduit pipe / elbow joint appearing 

inside should be less than 3/8 in. (10 mm). (Fig. 1) Elbow joint should appear less than 

1-3/16 in. (30 mm) outside. (Fig. 2)

6) Process the end of ground wire (Fig. 3). Connect it to the ground terminal of electrical parts 

box.

7) Process the end of indoor/outdoor unit connecting wire (A) (Fig. 3). Attach it to the terminal 

block. Be careful not to make mis-wiring. Attach the wire to the terminal block securely so 

that its core cannot be seen, and no external force affects the connecting section of the 

terminal block.

8) Firmly tighten the terminal screws. After tightening, verify that the wires are tightly fastened.

9) Reinstall conduit plate, conduit cover and display panel.

10) According to the piping direction, remove the shaded part of the corner box L (Fig. 4) or 

corner box R (Fig. 5). Reinstall electrical cover, corner box R and front panel. 

Less than 3/8 in.

(10 mm)

Conduit plate

Conduit pipe or 

elbow joint

Lock nut

6/32-9/32 in.

(5-7 mm)

ø3 in.

(75 mm) 

Lead 

wire

19/32 in.

(15 mm)

Indoor terminal 

block

Fixing 

screw

Conduit cover

Lock nut

Conduit plate

Elbow joint

(for right, left, or downward piping)

Elbow joint

(for right, left, or downward piping)

Less than 1-3/16 in.  

(30 mm)

Corner 

box R

Remove corner box 

R for piping on right 

side of unit

Remove corner box R 

for piping on bottom 

side of unit

Fig. 1

Fig. 2

Fig. 3

Fig. 4

Fig. 5

Coner 

box L

Remove coner 

box L for piping 

on left side of unit

Remove coner box L 

for piping on bottom 

left side of unit

Level 

Installation plate (1)

Center of ø3 in. 

(75 mm) hole

5-1/4 in. 

(132.5 mm) 

or more 

4-7/8 in. 

(122.5 mm) 

or more 

3-3/8 in. (85 mm) or more

5-11/16 in. (143 mm) or more for left/

left rear piping (using spacer)

Ceiling

Wall

Attachment 

screw (2)

* Same for left hole.

4-3/4 in. (120 mm)

INDOOR UNIT

Terminal block

208/230 V AC 

1phase, 60 Hz

Grounding 

terminal**

Disconnect 

switch*

OUTDOOR UNIT

Grounding terminal**

Ground

Power supply 208/230 V AC, 

1phase 2wires.  

60 Hz

Terminal  block 1

Terminal  block 

Terminal block 2

Electrical cover

Electrical box

Display and i-see 

sensor assembly

Straight joint

(for rear piping)

Conduit plate

or

Wall

2.  INDOOR UNIT INSTALLATION

Insert 

the 

scale. *

Align the 

scale with 

the line. *

15/18

06/09/12

Remark:

*  A disconnect switch 

should be required. 

Check the local code.

**  Use a ring tongue termi-

nal in order to connect a 

ground wire to terminal.

Содержание Trane NTXWPH06B112A Series

Страница 1: ...e unit make sure that no substance RWKHU WKDQ WKH VSHFL HG UHIULJHUDQW 5 HQWHUV WKH UHIULJHUDQW FLUFXLW Any presence of foreign substance such as air can cause abnormal pressure rise and may result in explosion or injury The use of any refrigerant other than that VSHFL HG IRU WKH V VWHP ZLOO FDXVH PHFKDQLFDO IDLOXUH V VWHP PDOIXQFWLRQ RU XQLW breakdown In the worst case this could lead to a seriou...

Страница 2: ...ing to before use Where it can be easily drained At a distance 3 ft 1 m or more away from a TV and radio Operation of the air conditioner may interfere with UDGLR RU 79 UHFHSWLRQ Q DPSOL HU PD EH UHTXLUHG IRU the affected device Q D SODFH DV IDU DZD DV SRVVLEOH IURP ÀXRUHVFHQW DQG incandescent lights In order to make the infrared remote control operate the air conditioner normally The heat from th...

Страница 3: ...by drain water or damaged by frozen drain water 4 7 8 in 122 5 mm or more 3 3 8 in 85 mm or more 5 11 16 in 143 mm or more for left left rear piping using spacer 2 3 16 in 56 mm or more 5 1 4 in 132 5 mm or more 33 1 16 13 3 4 14 5 8 19 11 16 Air inlet Air inlet Air inlet Air inlet Air inlet 6 7 8 15 3 8 13 Air outlet 2 3 8 13 16 slot 1 9 16 40 840 175 500 Air inlet 390 330 349 371 Air outlet 2 10...

Страница 4: ...terminal of electrical parts box 7 Process the end of indoor outdoor unit connecting wire A Fig 3 Attach it to the terminal block Be careful not to make mis wiring Attach the wire to the terminal block securely so that its core cannot be seen and no external force affects the connecting section of the terminal block 8 Firmly tighten the terminal screws After tightening verify that the wires are ti...

Страница 5: ...ection to which the drain hose is to be attached at the rear of the indoor unit Fig 3 Insert a screwdriver into the hole on the cap and insert the cap fully into the drain pan 5 Insert the drain hose fully into the drain pan at the back right of the indoor unit Fig 4 Check if the hose is hooked securely to the projection of its inserting part at the drain pan 6 Insert the drain hose into wall hole...

Страница 6: ...HIHFWLYH FXW RII WKH VHFWLRQ DQG UHSHDW SURFHGXUH Terminal block Power supply cord K Indoor outdoor unit connecting wire A Make ground wire a little longer than others More than 4 in 100 mm For future servicing leave some slack in the connecting wires Be sure to attach each screw to its corre spondent terminal when securing the cord and or the wire to the terminal block Pipe diameter inch mm B inc...

Страница 7: ...Otherwise composition of the refrigerant in the system may be changed and affect performance of the air conditioner 10 Remove gauge manifolds and replace service port caps and tighten 11 Leak test 4 2 TEST RUN 1 Insert power supply plug into the power outlet and or turn on the breaker 2 Press the E O SW once for COOL and twice for HEAT operation Test run will be performed for 30 minutes If the lef...

Страница 8: ...ING THE INDOOR UNIT Remove the bottom of the indoor unit from the installation plate When releasing the corner part release both left and right bottom corner part of indoor XQLW DQG SXOO LW GRZQZDUG DQG IRUZDUG DV VKRZQ LQ WKH JXUH RQ WKH ULJKW Installation procedure 1 Install the panel assembly following the removal procedure in reverse 2 Be sure to press the positions as indicated by the arrows ...

Отзывы: