En-12

Even if these items are checked, when the unit does not recover from the 

trouble, stop using the air conditioner and consult your dealer.

Symptom

Explanation & Check points

Indoor Unit

The unit cannot be operated.

•  Is the breaker turned on?

•  Is the power supply plug connected?

•  Is the ON timer set? 

 Page 9 

The horizontal vane does not 

move.

•  Are the horizontal vane and the vertical vane 

installed correctly?

•  Is the fan guard deformed? 

•  When the breaker is turned on, the horizontal 

vanes’ position will be reset in about a minute. 

After the reset has completed, the normal hori-

zontal vanes’ operation resumes. The same is 

true in the emergency cooling operation.

The unit cannot be operated for 

about 3 minutes when restarted.

•  This protects the unit according to instructions 

from the microprocessor. Please wait.

Mist is discharged from the air 

outlet of the indoor unit.

•  The cool air from the unit rapidly cools moisture 

in the air inside the room, and it turns into mist.

The swing operation of the HORI-

ZONTAL VANE is suspended for a 

while, then restarted.

•  This is for the swing operation of the HORIZON-

TAL VANE to be performed normally.

When SWING is selected in 

COOL/DRY/FAN mode, the 

lower horizontal vane does not 

move.

•  It is normal that the lower horizontal vane does 

not move when SWING is selected in COOL/

DRY/FAN mode.

The airfl ow direction changes 

during operation.

The direction of the horizontal 

vane cannot be adjusted with 

the remote controller.

•  When  the  unit  is  operated  in  COOL  or  DRY 

mode, if the operation continues with air blow-

ing down for 0.5 to 1 hour, the direction of the 

airfl ow is automatically set to upward position 

to prevent water from condensing and dripping.

•  In  the  heating  operation,  if  the  airfl ow  tem-

perature is too low or when defrosting is being 

done, the horizontal vane is automatically set 

to horizontal position.

The operation stops for about 

10 minutes in the heating 

operation.

•  Outdoor unit is in defrost.

  Since  this  is  completed  in  max.10  minutes, 

please wait. (When the outside temperature is too 

low and humidity is too high, frost is formed.)

The unit starts operation by 

itself when the main power is 

turned on, but hasn’t received 

sign from the remote controller.

•  These  models  are  equipped  with  an  auto 

restart  function.  When  the  main  power  is 

turned  off  without  stopping  the  unit  with  the 

remote controller and is turned on again, the 

unit starts operation automatically in the same 

mode as the one set with the remote control-

ler just before the shutoff of the main power. 

Refer to “Auto restart function” 

 page 6 

.

The two horizontal vanes touch 

each other. The horizontal 

vanes are in an abnormal posi-

tion. The horizontal vanes do 

not return to the correct “close 

position”.

Perform one of the following: 

•  Turn off and on the breaker. Make sure the horizon-

tal vanes move to the correct “close position”.

•  Start and stop the emergency cooling operation 

and make sure the horizontal vanes move to the 

correct “close position”.

The indoor unit discolors over 

time.

•  Although plastic turns yellow due to the infl uence 

of  some  factors  such  as  ultraviolet  light  and 

temperature, this has no effect on the product 

functions.

Multi system

The indoor unit which is not 

operating becomes warm and a 

sound, similar to water fl owing, 

is heard from the unit.

•  A small amount of refrigerant continues to fl ow 

into the indoor unit even though it is not operat-

ing.

When heating operation is 

selected, operation does not 

start right away.

•  When operation is started during defrosting of 

outdoor unit is done, it takes a few minutes (max. 

10 minutes) to blow out warm air.

Outdoor Unit

The fan of the outdoor unit does 

not rotate even though the com-

pressor is running. Even if the 

fan starts to rotate, it stops soon.

•  When  the  outside  temperature  is  low  during 

cooling operation, the fan operates intermittently 

to maintain suffi cient cooling capacity.

Water leaks from the outdoor 

unit.

•  During COOL and DRY operations, pipe or pipe 

connecting sections are cooled and this causes 

water to condense.

•  In the heating operation, water condensed on 

the heat exchanger drips down.

•  In the heating operation, the defrosting operation 

makes ice forming on the outdoor unit melt and 

drip down.

White smoke is discharged from 

the outdoor unit.

•  In the heating operation, vapor generated by the 

defrosting operation looks like white smoke.

Symptom

Explanation & Check points

Remote controller

The display on the remote 

controller does not appear or it 

is dim. The indoor unit does not 

respond to the remote control 

signal.

•  Are the batteries exhausted? 

 Page 3 

•  Is  the  polarity  (+,  -)  of  the  batteries  correct?

 Page 3 

•  Are any buttons on the remote controller of other 

electric appliances being pressed?

Does not cool or heat

The room cannot be cooled or 

heated suffi ciently.

•  Is the temperature setting appropriate? 

 

 Page 6 

•  Is  the  fan  setting  appropriate?  Please  change 

fan speed to High or Super High. 

 Page 7 

•  Are the fi lters clean? 

 Page 11 

•  Is the fan or heat exchanger of the indoor unit 

clean? 

•  Are there any obstacles blocking the air inlet or 

outlet of the indoor or outdoor unit?

•  Is a window or door open?

•  It may take a certain time to reach the setting 

temperature or may not reach that depending on 

the size of the room, the ambient temperature, 

and the like.

The room cannot be cooled 

suffi ciently.

•  When a ventilation fan or a gas cooker is used 

in a room, the cooling load increases, resulting 

in an insuffi cient cooling effect.

•  When the outside temperature is high, the cooling 

effect may not be suffi cient.

The room cannot be heated 

suffi ciently.

•  When the outside temperature is low, the heating 

effect may not be suffi cient.

Air does not blow out soon in 

the heating operation.

•  Please wait as the unit is preparing to blow out 

warm air.

Airfl ow

The air from the indoor unit 

smells strange.

•  Are the fi lters clean? 

 Page 11 

•  Is the fan or heat exchanger of the indoor unit 

clean? 

•  The unit may suck in an odor adhering to the 

wall, carpet, furniture, cloth, etc. and blow it out 

with the air.

Sound

Cracking sound is heard.

•  This sound is generated by the expansion/con-

traction of the front panel, etc. due to change in 

temperature.

“Burbling” sound is heard.

•  This  sound  is  heard  when  the  outside  air  is 

absorbed from the drain hose by turning on the 

range hood or the ventilation fan, making water 

fl owing in the drain hose to spout out.

  This sound is also heard when the outside air 

blows  into  the  drain  hose  in  case  the  outside 

wind is strong.

Mechanical sound is heard 

from the indoor unit.

•  This is the switching sound in turning on/off the 

fan or the compressor.

The sound of water fl owing is 

heard.

•  This  is  the  sound  of  refrigerant  or  condensed 

water fl owing in the unit.

Hissing sound is sometimes 

heard.

•  This is the sound when the fl ow of refrigerant 

inside the unit is changed.

Timer

Weekly timer does not operate 

according to settings.

•  Is the ON/OFF timer set? 

 Pages 9, 10 

•  Transmit  the  setting  information  of  the  weekly 

timer to the indoor unit again. When the infor-

mation is successfully received, a long beep will 

sound from the indoor unit. If information fails to 

be received, 3 short beeps will be heard. Ensure 

information is successfully received. 

 Page 10 

•  When a power failure occurs and the main power 

turns  off,  the  indoor  unit  built-in  clock  will  be 

incorrect. As a result, the weekly timer may not 

work normally.

  Be  sure  to  place  the  remote  controller  where 

the  signal  can  be  received  by  the  indoor  unit.

 Page 3 

The unit starts/stops the opera-

tion by itself.

•  Is the weekly timer set? 

 Page 10 

In the following cases, stop using the air conditioner and consult your dealer.

•  When water leaks or drips from the indoor unit.

•  When the operation indicator lamp blinks. Except for when the lamp of a multi 

unit blinks while the unit is on standby.

•  When the breaker trips frequently.

•  The remote control signal is not received in a room where an electronic ON/

OFF type fl uorescent lamp (inverter-type fl uorescent lamp, etc.) is used.

•  Operation of the air conditioner interferes with radio or TV reception. An ampli-

fi er may be required for the affected device.

•  When an abnormal sound is heard.

•  When any refrigerant leakage is found.

W

HEN YOU THINK THAT TROUBLE HAS OCCURRED

JG79Y575H01_01En.indd   12

2018/07/24   15:23:08

Содержание Trane NTXWPH06A112A Series

Страница 1: ...des clients Pour avoir la certitude d utiliser cet appareil correctement et en toute sécurité veuillez lire cette notice d instructions avant de mettre le clima tiseur sous tension Español MANUAL DE INSTRUCCIONES Para los clientes Para utilizar esta unidad de forma correcta y segura lea previamente estas instrucciones de funcionamiento SPLIT TYPE AIR CONDITIONERS NTXWP06A112A NTXWP09A112A NTXWP12A...

Страница 2: ...ce and knowledge unless they have been given supervision or instruction concerning use of the appli ance by a person responsible for their safety Children should be supervised to ensure that they do not play with the appliance Do not insert your finger a stick or other objects into the air inlet or outlet This may cause injury since the fan inside rotates at high speeds during operation In case of ...

Страница 3: ...lation may cause oxygen starvation Turn the breaker OFF when you hear thunder and there is a pos sibility of a lightning strike The unit may be damaged if lightning strikes After the air conditioner is used for several seasons perform inspection and maintenance in addition to normal cleaning Dirt or dust in the unit may create an unpleasant odor contribute to growth of fungi such as mold or clog t...

Страница 4: ...uttons to set the time Each press increases decreas es the time by 1 minute 10 minutes when pressed longer 3 Press the DAY button to set the day Remote controller holder Signal transmitting section Distance of signal About 20 ft 6 m Beep s is are heard from the indoor unit when the signal is received Operation display section OFF ON stop operate button Temperature buttons Pages 4 6 8 Operation sel...

Страница 5: ...te controller display 1 Hold down on the remote controller for 2 sec onds to enter the position setting mode 2 Select the target installation position by pressing Each press of the displays the positions in order Center Right Left 3 Press to complete the position setting Note The installation position can be set only when all the following conditions are met The remote controller is powered off We...

Страница 6: ...mode is also cancelled when the VANE or WIDE VANE buttons is pressed Note Do not touch the i see sensor This may cause malfunction of the i see sen sor The intermittent operating sound is a normal sound produced when the i see sensor is moving from side to side Press during COOL DRY HEAT and AUTO mode to activate the i see control mode Press gently using a thin instrument lights Operation display ...

Страница 7: ...0 5 C Press to stop the operation Auto restart function If a power failure occurs or the main power is turned off during operation Auto restart function automatically starts operation in the same mode as the one set with the remote controller just before the shutoff of the main power When timer is set timer setting is cancelled and the unit starts operation when power is resumed If you do not want...

Страница 8: ...to mal function When the breaker is turned on the horizontal vanes position will be reset in about a minute then the operation will start The same is true in the emergency cooling operation When the horizontal vanes seem to be in an abnormal position see page 12 The right and left horizontal vanes set to the same level may not align perfectly Press to select horizontal airflow direction Each press ...

Страница 9: ...ne for COOL one for HEAT Select the appropriate temperature fan speed and airflow direction according to your room Normally the minimum temperature setting in HEAT mode is 61 F 16 C However during SMART SET operation only the minimum temperature setting is 50 F 10 C Press again to cancel SMART SET operation SMART SET operation also is cancelled when the MODE button is pressed SMART SET operation A...

Страница 10: ... downward airflow position during AUTO setting Temperature cannot be set during POWERFUL operation Press again to cancel POWERFUL operation POWERFUL operation is also cancelled automatically in 15 minutes or when the ON OFF FAN ECONO COOL NATURAL FLOW or i save button is pressed POWERFULOPERATION 1 Press or during operation to set the timer ON timer The unit turns ON at the set time OFF timer The ...

Страница 11: ...r is turned OFF Checking weekly timer setting 1 Press to enter the weekly timer setting mode blinks 2 Press or to view the setting of the particular day or number Press to exit the weekly timer setting Note When all days of the week are selected to view the settings and a different set ting is included among them will be displayed which was blink ing goes out and the current time will be displayed...

Страница 12: ...the air filter Every year Replace it with a new air cleaning filter for best performance Parts Number MAC 2330FT E Pull to remove from the air filter Deodorizing filter black Every 3 months Remove dirt by a vacuum cleaner or soak the framed filter in lukewarm water 86 to 104 F 30 to 40 C for about 15 minutes Rinse well After washing dry it well in shade Deodorizing feature recovers by cleaning the filte...

Страница 13: ...uses water to condense In the heating operation water condensed on the heat exchanger drips down In the heating operation the defrosting operation makes ice forming on the outdoor unit melt and drip down White smoke is discharged from the outdoor unit In the heating operation vapor generated by the defrosting operation looks like white smoke Symptom Explanation Check points Remote controller The d...

Страница 14: ... unit should be at least 10 ft 3 m away from the antennas for TV sets radios etc In areas where the reception is weak provide greater space between the outdoor unit and the antenna of the affected device if operation of the air conditioner interferes with radio or TV reception 1 Set to the highest temperature in manual COOL mode and operate for 3 to 4 hours Page 6 This dries the inside of the unit...

Страница 15: ...el conocimiento a menos que lo hagan bajo la supervisión o instrucción relativa al uso del aparato por una persona responsable de su seguridad Se debe supervisar a los niños para garantizar que no jueguen con el aparato Puesto que este producto tiene piezas rotatorias y piezas que pueden provocar des cargas eléctricas lea atentamente las Medidas de seguridad antes de usarlo Tome las precauciones a...

Страница 16: ...ntilación inadecuada puede originar falta de oxígeno Coloque el disyuntor en OFF si oye truenos y hay posibilidad de que caigan rayos La unidad puede resultar dañada si cae algún rayo Tras varias estaciones con el acondicionador de aire en funciona miento efectúe una inspección y el mantenimiento además de la limpieza habitual Si hay polvo o suciedad en la unidad se puede producir un olor desagra ...

Страница 17: ...moto Sección de transmisión de señales Distancia de la señal Aprox 20 pies 6 m Cuando se recibe la señal la unidad interior emite un sonido Sección de pantalla de accionamiento Botón OFF ON des activación activación de funcionamiento Botones de temperatura Páginas 4 6 8 Botón de selección del modo de fun cionamiento Página 6 Botón de desco nexión automáti ca ECONO COOL Página 8 Botón de control de...

Страница 18: ...te 2 segundos para entrar en el modo de ajuste de posición 2 Seleccione la posición de instalación de destino pulsan do Cada vez que pulse se mostrarán las posicio nes en orden Centro Derecha Izquierda 3 Pulse para completar el ajuste de la posición Nota La posición de instalación se puede ajustar solo cuando se cumplen las si guientes condiciones El controlador remoto está desactivado No se ha co...

Страница 19: ...nido de funcionamiento intermitente es un sonido normal que se produ ce cuando el sensor i see se mueve de un lado a otro 1 2 3 Para activar el modo de control i see pulse duran te el modo COOL refrigeración DRY deshumidifica ción HEAT calefacción y AUTO Púlselo suavemente usando un objeto fino Se iluminará Sección de la pantalla de accionamiento El ajuste predeterminado es activado Pulse de nuevo ...

Страница 20: ...uye la temperatura en 1 F 0 5 C Pulse para apagarlo Función de reinicio automático En caso de que se produzca un corte en el suministro eléctrico o se apague la unidad mientras esté funcionando la función de reinicio automático se activará automá ticamente en el mismo modo seleccionado con el controlador remoto antes de que se interrumpiese el funcionamiento Cuando está configurado el temporizador ...

Страница 21: ... la posición de los deflectores horizonta les se restablece en cuestión de un minuto a continuación se reanu da el funcionamiento Ocurre lo mismo durante el funcionamiento de refrigeración de emergencia Si los deflectores horizontales parecen hallarse en una posición anó mala consulte la página 12 Los difusores horizontales derecho e izquierdo ajustados al mismo nivel pueden no alinearse perfectam...

Страница 22: ... confi guración sólo con pulsar Pueden guardarse dos grupos de configuración Uno para REFRIGE RACIÓN otro para CALEFACCIÓN Seleccione la temperatura la velocidad del ventilador y la dirección del flujo de aire adecuadas para la habitación Normalmente la configuración de temperatura mínima en el modo CALEFACCIÓN es 61 F 16 C Tenga en cuenta que durante el fun cionamiento en modo SMART SET SELECCIÓN...

Страница 23: ... configuración en AUTO No es posible ajustar la temperatura durante el funcionamiento POWERFUL potente Vuelva a pulsar para cancelar el funcionamiento POWERFUL potente El funcionamiento POWERFUL potente también se cancela de forma auto mática en 15 minutos o al pulsar el botón ON OFF FAN ventilador ECONO COOL desconexión automática NATURAL FLOW flujo natural o i save FUNCIONAMIENTOPOWERFUL POTENTE...

Страница 24: ... el día de la semana cuya configuración está completa Vuelva a pulsar para la DESACTIVACIÓN del temporizador semanal se apaga Nota Las configuraciones guardadas no se borrarán al DESACTIVAR el temporizador semanal Comprobación de la configuración del temporizador semanal 1 Pulse para entrar en el modo de configuración del temporizador semanal parpadea 2 Pulse o para ver la configuración de un día o nú...

Страница 25: ...ieza de aire Filtro de enzimas antialérgico elec trostático azul Cada 3 meses Elimine la suciedad con un aspirador Si la suciedad no se puede eliminar con un aspirador Sumerja el filtro y su carcasa en agua templada antes de enjuagarlos Después de lavarlo déjelo secar completamente a la sombra Instale todas las pestañas del filtro de aire Cada año Cambie el filtro de aire por uno nuevo para un mejor ...

Страница 26: ...a REFRIGERACIÓN o la DESHUMIDIFICA CIÓN el enfriamiento de los tubos y de las conexiones de los tubos hace que se condense el agua En el modo de calefacción el agua se condensa en el intercambiador de calor y empieza a gotear En el modo de calefacción la función de desescar chado derrite el hielo adherido a la unidad exterior y el agua empieza a gotear Sale humo blanco de la unidad exterior En el ...

Страница 27: ...alidas de aire de las unidades interior exterior 3 Compruebe que el cable de tierra esté conectado correctamente 4 Consulte la sección PREPARACIÓN ANTES DE LA PUESTA EN MARCHA y siga las instrucciones Página 3 CUANDOELACONDICIONADORDEAIRENOSE VAYAAUTILIZARDURANTEMUCHOTIEMPO Para evitar los efectos de una lámpara fluores cente manténgase lo más alejado posible pared etc Lámpara fluorescente de tipo i...

Страница 28: ...tantes pour la sécurité et doivent donc impérativement être respectées Après avoir lu cette notice conservez la avec le manuel d installation à portée de main pour pouvoir la consulter aisément Symboles et leur signification AVERTISSEMENT toute manipulation incorrecte peut avoir des consé quences graves provoquer des blessures corporelles voire la mort de l utilisateur PRECAUTION toute manipulation...

Страница 29: ...oit parfaitement ventilée Une ventilation insuffisante pourrait provoquer un manque d oxygène dans la pièce Couper le disjoncteur par temps d orage La foudre pourrait endommager le climatiseur Si le climatiseur a été utilisé pendant plusieurs saisons consécutives procéder à une inspection et à un entretien rigoureux en plus du nettoyage normal Une accumulation de saletés ou de poussière à l intérie...

Страница 30: ... lorsque vous ne l utili sez pas Utilisez uniquement la télécommande fournie avec le climatiseur N en utilisez pas d autres Si plusieurs unités internes sont instal lées côté à côte il se peut que le signal envoyé à une unité interne par la télé commande soit exécuté par une autre unité interne Support de la télécommande 3 Appuyez sur la touche DAY pour régler le jour 4 Filtre à air Filtre d épura...

Страница 31: ...de la position 2 Sélectionnez la position d installation cible en appuyant sur Chaque pression sur la touche affiche les posi tions en séquence Au centre À droite À gauche 3 Appuyez sur la touche pour terminer le réglage de la position Remarque Le réglage de la position d installation n est possible que lorsque toutes les conditions suivantes sont remplies La télécommande est éteinte La minuterie h...

Страница 32: ...fonctionnement intermittent est un son normal produit par le dé placement du capteur i see d un côté à l autre 1 2 3 Appuyez sur la touche en mode REFROIDISSE MENT DÉSHUMIDIFICATION CHAUFFAGE et AUTO pour activer le contrôle i see Appuyez doucement à l aide d une pointe fine s éclaire Affichage du mode de fonctionnement Le réglage par défaut est actif Appuyez une nouvelle fois sur la touche pour a...

Страница 33: ... vous appuyez sur l interrupteur de secours E O SW le fonctionnement du climatiseur change dans l ordre suivant Fonction de redémarrage automatique En cas de coupure d électricité ou d interruption de l alimentation principale pendant le fonctionnement du climatiseur la fonction de redémarrage automatique prend auto matiquement le relais et permet de remettre le climatiseur en marche en respectant...

Страница 34: ...t Lorsque le disjoncteur est activé la position des ailettes verticales est réinitialisée en une minute environ puis l opération démarre Il en est de même en mode de refroidissement d urgence Si les ailettes horizontales semblent être dans une position anormale reportez vous à la page 12 Il est possible que même réglées au même niveau les ailettes hori zontales droites et gauches ne soient pas par...

Страница 35: ...est possible d enregistrer deux groupes de réglages Un pour RE FROIDISSEMENT un pour CHAUFFAGE Sélectionnez la température la vitesse du ventilateur et la direction du flux d air appropriées pour votre local Normalement le réglage de température minimum en mode CHAUF FAGE est de 61 F 16 C Cependant en mode SMART SET RE GLAGE INTELLIGENT seul le réglage de température minimum est de 50 F 10 C Appuy...

Страница 36: ...Appuyez une nouvelle fois sur LA TOUCHE pour annuler le mode NATURAL FLOW Une pression sur les touches POWERFUL ou ECONO COOL permet également d annuler le fonctionnement en mode NATURAL FLOW En quoi consiste le NATURAL FLOW Dans ce mode le flux d air imite une brise naturelle L inconfort provoqué par un flux d air direct constant et artificiel sera réduit Remarque Étant donné que la vitesse du venti...

Страница 37: ... la semaine pour lequel le réglage est terminé s allume Appuyez à nouveau sur pour désactiver la minute rie hebdomadaire OFF s éteint Remarque Les réglages enregistrés ne sont pas effacés lorsque la minuterie hebdomadaire est désactivée Vérification du réglage de minuterie hebdomadaire 1 Appuyez sur pour passer en mode de réglage de la minuterie hebdomadaire clignote 2 Appuyez sur ou sur pour affic...

Страница 38: ... du filtre à air Tous les ans Pour des performances optimales remplacer le filtre d épuration d air Référence MAC 2330FT E Tirez sur le panneau frontal pour le retirer du filtre à air Trou Charnière Filtre désodorisant noir Tous les 3 mois Éliminez la saleté avec un aspirateur ou immergez le filtre dans un réci pient d eau tiède 86 à 104 F 30 à 40 C pendant 15 minutes environ Rincez abondamment Après ...

Страница 39: ...ION la tuyauterie et les raccords de tuyauterie sont refroidis et un certain degré de condensation peut se produire En mode de chauffage l eau de condensation présente sur l échangeur thermique peut goutter En mode de chauffage l opération de dégivrage fait fondre la glace présente sur l unité externe et celle ci se met à goutter Symptôme Explication points à vérifier Unité externe De la fumée blan...

Страница 40: ...e disjoncteur 4 Retirez toutes les piles de la télécommande Lorsque le climatiseur doit être remis en service 1 Nettoyez le filtre à air Page 11 2 Veillez à ce que l entrée et la sortie d air des unités interne et externe ne soient pas obstruées 3 Veillez à ce que la mise à la terre soit correctement effectuée 4 Reportez vous à la section PREPARATIF D UTILISA TION et suivez les instructions Page 3 ...

Страница 41: ...A4_white_tombo indd 1 2016 04 25 10 16 47 ...

Страница 42: ...A4_white_tombo indd 1 2016 04 25 10 16 47 ...

Страница 43: ...A4_white_tombo indd 1 2016 04 25 10 16 47 ...

Страница 44: ...complete your product registration please visit us at http www metahvac com Be sure to have the model and serial number for each of your indoor and outdoor units ready before starting the registration process If you need assistance registering your products call or write to us at Mitsubishi Electric Trane HVAC US LLC ATTN Customer Care Center 1340 Satellite Boulevard Suwanee GA 30024 Phone 1 800 4...

Отзывы: