38
OPERATING PROCEDURE
PHOTOS
5. Removing outdoor fan motor
(1) Remove the cabinet and panels. (Refer to procedure 1.)
(2) Disconnect the following connectors:
<Inverter
P.C.
board>
CN932 (Fan motor)
(3) Remove the propeller nut. (Photo 7)
(4) Remove the propeller. (Photo 7)
(5) Remove the screws fixing the fan motor. (Photo 7)
(6) Remove the fan motor.
Photo 6
Photo 7
Photo 8
6. Removing the compressor and 4-way valve
(1) Remove the cabinet and panels. (Refer to procedure 1.)
(2) Remove the inverter assembly. (Refer to procedure 2.)
(3) Recover gas from the refrigerant circuit.
NOTE:
Recover gas from the pipes until the pressure gauge
shows 0 kg/cm² (0 MPa).
(4) Detach the welded part of the suction and the discharge pipe
connected with compressor.
(5) Remove the nuts of compressor legs.
(6) Remove the compressor.
(7) Detach the welded part of pipes connected with 4-way valve.
(Photo 8)
Defrost thermistor
Outdoor heat
exchanger tempera-
ture thermistor
Propeller nut
Screws of the outdoor fan motor
Propeller
Welded parts of 4-way valve
OCH545
Содержание SUZ-KA25VA4
Страница 13: ...13 13 7 WIRING DIAGRAM SUZ KA25VA4 TH SUZ KA35VA4 TH OCH545 ...
Страница 14: ...14 SUZ KA50VA4 TH OCH545 ...
Страница 15: ...15 SUZ KA60VA4 TH SUZ KA71VA4 TH OCH545 ...
Страница 45: ...45 OCH545 ...