20
ADDITIONAL REFRIGERANT CHARGE (R410A:g)
Outdoor unit
precharged
900
1,050
14m
270
270
7m
0
0
6m
0
0
5m
0
0
11m
180
180
Models
Refrigerant piping length (one way)
Calculation : Xg=30g/m
o
(Refrigerant piping length(m) - 5)
8m
90
90
9m
120
120
10m
150
150
12m
210
210
13m
240
240
15m
300
300
20m
450
450
SUZ-KA25VA.TH
SUZ-KA25VAH.TH
SUZ-KA35VA.TH
SUZ-KA35VAH.TH
Refrigerant Piping
Max. length
A
w
Height difference should be within 12m regardless of which unit, indoor or outdoor position is high.
w
Max. Height
difference 12m
Indoor
unit
(SLZ/SEZ)
Outdoor unit
MAX. HEIGHT DIFFERENCE
MAX. REFRIGERANT PIPING LENGTH
Refrigerant piping
Max. length : m
A
20
Gas
9.52
Liquid
6.35
Piping size O.D : mm
Models
SUZ-KA25VA.TH
SUZ-KA35VA.TH
SUZ-KA25VAH.TH
SUZ-KA35VAH.TH
SUZ-KA25VA.TH SUZ-KA25VAH.TH
SUZ-KA35VA.TH SUZ-KA35VAH.TH