Setting method of each function by wired remote controller
Rotation setting
Select :
F1
F2
F3
F4
Rotation
TempDifTrigger
−
C
Backup only
+4°C
Cur.
t
e
s
e
R
Select "Rotation setting" with the F1 or F2 button, and press the [ ] button.
Select "Settings" with the F1 or F2 button, and press the [ ] button.
2. Set the rotation function.
Select "Rotation" with the F1 button.
Select the rotation period or "Backup only" with the F2 or F3 button.
■
"Rotation" setup
None, 1 day, 3 days,
5 days
,
7 days, 14 days,
28days, Backup only
3. Set the support function.
Select "TempDifTrigger" with the F1 button.
Select "the difference between the suction temperature and the set tempera-
ture" with the F2 or F3 button.
Select "Service" from the Main menu, and press the [ ] button.
■ PAR-41MAA
1.
Stop operation
Settings menu
Service menu:
Function setting
Rotation setting
Cursor
F1
F2
F3
F4
Rotation setting
Select :
F1
F2
F3
F4
Rotation
TempDifTrigger
−
C
Backup only
+4°C
Cur.
t
e
s
e
R
Notes:
•
When 1 to 28 days are selected, the backup function is also enabled.
•
When "Backup only" is selected, the rotation function will be disabled. The sys-
tems with refrigerant addresses of 00 or 01 (00 system/ 01 system) will be oper-
ated as a main system while the 02 system is the standby mode as backup.
4.
Update the setting.
Press the [ ] button to update the setting.
■
"TempDifTrigger" setup
None, +4ºC, +6ºC, +8ºC
Notes:
•
The support function is available only in the COOL mode. (Not available in the
HEAT, DRY and AUTO mode.)
•
The support function is enabled when any option other than "None" is selected
from the "Rotation" setup.
Reset method
•
Press the F4 button in step or to reset the operation time of the rotation function. Once it is reset, operation
will start from the 00 or 01 systems.
Note: When the 02 system is in the backup operation, the 00 or 01 systems will be operated again.
13-6. ROTATION SETTING