• If the unit cannot be operated properly after the test run, refer to the following table to find out the cause.
Symptom
Cause
Wired remote controller
LED 1, 2 (PCB in outdoor unit)
On the wireless remote controller with condition above, following phenomena take place.
• No signals from the remote controller can be received.
• Operation lamp is blinking.
• The buzzer makes a short ping sound.
Please Wait
After LED 1, 2 are lighted, LED 2 is turned
off, then only LED 1 is lighted. (Correct
operation)
Please Wait
Only LED 1 is lighted. → LED 1, 2 blink.
→
Error code
Display messages do not appear
even when operation switch is
turned ON (operation lamp does
not light up).
Only LED 1 is lighted. → LED 1 blinks
twice, LED 2 blinks once.
For about 3 minutes
after power-on
Subsequent to
about 3 minutes
after power-on
• For about 3 minutes after power-on, operation of the
remote controller is not possible due to system startup.
(Correct operation)
• Connector for the outdoor unit’s protection device is not
connected.
• Reverse or open phase wiring for the outdoor unit’s
power terminal block (~/N: L, N) (3N~: L1, L2, L3, N)
• Incorrect wiring between indoor and outdoor units.
(incorrect polarity of S1, S2, S3)
• Remote controller wire short
Note:
Operation is not possible for about 30 seconds after cancellation of function selection. (Correct operation)
For description of each LED (LED1, 2, 3) provided on the indoor controller, refer to the following table.
LED1 (power for microprocessor)
Indicates whether control power is supplied. Make sure that this LED is
always lit.
LED2 (power for remote controller)
Indicates whether power is supplied to the remote controller.
This LED lights only in the case of the indoor unit which is connected to the
outdoor unit refrigerant address “0”.
LED3 (communication between indoor and
outdoor units)
Indicates state of communication between the indoor and outdoor units.
Make sure that this LED is always blinking.
Notes:
1. If the beeper does not sound again after the initial 2 beeps to confirm the self-check start signal was received and the
OPERATION INDICATOR lamp does not come on, there are no error records.
2. If the beeper sounds 3 times continuously “beep, beep, beep (0.4 + 0.4 + 0.4 seconds)” after the initial 2 beeps to confirm the self-
check start signal was received, the specified refrigerant address is incorrect.
• On wireless remote controller
The continuous buzzer sounds from receiving section of indoor unit.
Blink of operation lamp
• On wired remote controller
Check code displayed in the LCD.