Operation lamp blinks once in a fixed period.
Indoor controller board is defective.
Connection is defective.
Error was found in the signal transmitted or
received between the indoor and outdoor units.
Turn off the power supply and turn it on again to operate the unit in
cooling or heating mode.
Is the connecting wire between
the indoor and outdoor units
connected properly?
Normal
Operation lamp blinks once in a
fixed period.
Remove the devices.
Are there any devices emitting
noise near the power supply or
the connecting wire between the
indoor and outdoor units?
Operation lamp blinks twice in a fixed period.
Measure the resistance
of indoor coil thermistor.
Measure the resistance of
room temperature thermistor.
Indoor controller board is defective.
Check the room temperature thermistor.
Check the indoor coil thermistor.
Turn off the power supply and turn it on again to operate the unit in
cooling mode.
Is the connector CN20 on the
indoor controller board connected?
Connection is defective.
Connection is defective.
Connection is defective.
Is the connector CN21 on the
indoor controller board connected?
Indoor coil thermistor
is defective.
Is the resistance 0 (short circuit) or
∞
(open circuit)?
Measure the resistance
of drain sensor.
Check the drain sensor thermistor.
Is the connector CN31 on the
indoor controller board connected?
Drain sensor is defective.
Is the resistance 0 (short circuit) or
∞
(open circuit)?
Room temperature
thermistor is defective.
Is the resistance 0 (short circuit) or
∞
(open circuit)?
Normal
Operation lamp blinks twice in a
fixed period.
Check of indoor controller board and indoor fan motor
To be continued on the next page.