Refrigerant pipe diameter is different according to indoor unit to be connected. When using extension pipes, refer to the
tables
below.
When the diameter of refrigerant pipe is different from that of outdoor unit union, use optional Different-diameter pipe.
For further information on Different-diameter pipe, see the appropriate parts catalog, Optional parts "DIFFERENT
DIAMETER
PIPE"(2-1.).
Unit : inch
Piping length each indoor unit (a, b, c)
82 ft. MAX.
Total piping length (a+b+c)
230 ft. MAX.
Bending point for each unit
25 MAX.
Total bending point
70 MAX.
It is irrelevant which unit is higher.
MAX. REFRIGERANT PIPING LENGTH & PIPE SIZE SELECTION
MXZ-3B24NA MXZ-3B30NA
Operating Range
MXZ-3B24NA MXZ-3B30NA
Cooling
Heating
Maximum
Minimum
Maximum
Minimum
Indoor intake air temperature
95°FDB, 71°FWB
67°FDB, 57°FWB
80°FDB, 67°FWB
70°FDB, 60°FWB
Outdoor intake air temperature
115°FDB
14°FDB
75°FDB, 65°FWB
6°FDB, 5°FWB
a
c
Outdoor
unit
Indoor
units
Max. height difference
49 ft.
33 ft.
b
49 ft.
Indoor unit class
Extension pipe diameter
09 or less
Liquid
1/4
Gas
3/8
12
Liquid
1/4
Gas
3/8
15
Liquid
1/4
Gas
1/2
17
Liquid
1/4
Gas
1/2
18
Liquid
1/4
Gas
1/2
24
(MXZ-3B30NA only)
Liquid
1/4
Gas
5/8
Outdoor unit union diameter
For
Indoor unit A
Liquid
1/4
Gas
1/2
Indoor unit B
Liquid
1/4
Gas
3/8
Indoor unit C
Liquid
1/4
Gas
3/8