.  Installing the grille

Fig. 9-6

Ceiling

Main unit

Grille

Make sure that there are no gaps.

Adjust the nut of the main unit

 

using a wrench, etc.

Fig. 9-7

Fig. 9-8

Clamp of the main unit

Electrical box

Indoor controller board

Catch for bell mouth

Lead wire of grille

Controller board CN4Y

Controller board CN6Y

2 fasteners 

4

Fastener 

4

i-see sensor corner panel 

9

Rib for grille

Screw 

6

A

 

Main unit

C

 

Corner drain pipe area

D

 

Screw with washer 

2

 (for temporary use)

E

 

Grille

F

 

Screw with washer 

2

G

 

Socket

H

 

Bell shaped hole

A

C

D

E

F

G

H

A

A

B

B

C

C

D

D

E

G

E

Screw (4×8) 

5

Corner panel

Safety wire

Fig. 9-9

Fig. 9-10

(Enlarged)

A

A

B

B

C

D

E

F

G

C

E

D

F

H

G

I

9.4.2.  Temporary installation of the grille (Fig. 9-6)

•  Temporarily secure the grille using the bell shaped holes by putting the socket of 

the grille marked 

G

 on the corner drain pipe area of the main unit.

*  Make sure that the lead wiring of the grille does not get pinched between the 

grille and the main unit.

9.4.3.  Securing the grille (Fig. 9-7)

•  Secure the grille to the main unit by tightening the previously installed 2 screws 

(with captive washer) as well as the 2 remaining screws (with captive washer). 

*  Make sure that there are no gaps between the main unit and the grille or the 

grille and the ceiling.

Fixing gaps between the grille and the ceiling

With the grille attached, adjust the height of the main unit to close the gap.

9.4.4.  Wire connection (Fig. 9-8)

• Remove the 2 screws fixing the cover of electrical branch box of the unit and 

open the cover.

• Be sure to connect the connector(white, 20-pole) for vane motor of the grille to 

CNV connector of contoller board of the unit.

• As for PLP-6BALM(E), the connector of wireless sensor cable is also connected 

to connecor CN90 on indoor controller board.

The lead wire of grille is passed through the catch of bell mouth of the unit 
perfectly. The remaining lead wire is tied with clamp of the unit and put the cover of 
the unit again with 2 screws.

Note: 

Do not put the remaining lead wire in electrical branch box of the unit.

.5.  Installing the intake grille (Fig. - )

Note:
When reinstalling the corner panels (each with a safety wire attached), con-

nect  the  other  end  of  each  safety  wire  to  the  grille  using  a  screw  (4  pcs, 

 

4

×

8) as shown in the illustration.

*If the corner panels are not attached, they may fall off while the unit is operating.
• Perform the procedure that is described in “9.2. Preparing to attach the grille” in 

reverse order to install the intake grille and the corner panel.

• Multiple units can be installed with grille so that the position of the logo on each 

corner panel is consistent with the other units regardless of the orientation of the 
intake grille. Align the logo on the panel according to the wishes of the customer 
as shown in the diagram to the left. (The position of the grille can be changed.)

D

 Refrigerant piping of the main unit

E

 Drain piping of the main unit

F

 Initial position of the corner panel(logo attached)

* Installation in any position is possible.

G

 Initial position of the levers on the intake grille

* Although the clips can be installed in any of 4 positions, the configuration shown 

here is recommended.(It is not necessary to remove the intake grille when 
maintenance is performed on the electric component box of the main unit.)

H

 Receiver (Only PLP-6BALM, PLP-6BALME Panel)

I

 i-see sensor(PLP-6BAE, PLP-6BAMDE, PLP-6BALME panel)

.6.  Installation of i-see sensor corner panel

 

(Fig. 9-10)

For PLP-6BAE, PLP-6BAMDE, PLP-6BALME panel
•  Take the lead wires CN4Y(white) and CN6Y(red) of the i-see sensor corner panel 

from the side of the electrical box on the unit and make sure to conect them to 

the connector of the controller board.

•  Lead wires of the i-see sensor corner panel 

should be fixed at the rib of the 

grille with the fastener 

so that there is no slack.

•  Lead wires should be held together with the lead wires of the unit and fixed with 2 

of the fastener 

so that there is no slack.

•  Put the cover back on the electrical box with 3 screws.
*  Make sure wires are not caught in the cover of electric box. If they are caught, 

they will be cut.

•  Adverse procedure of “9.2. Preparing to attach the grille”  will be taken for install-

ing the i-see sensor corner panel.

*  The i-see sensor corner panel should be fixed onto the grille 

1

 with screw 

6

.

01_BH79D045K05_EN.indd   18

2012/09/18 (火)   午後 3:45:03

Содержание RP100

Страница 1: ...ente manuale ed il manuale d installazione dell unità esterna MANUAL DE INSTALACIÓN Para un uso seguro y correcto lea detalladamente este manual de instalación antes de montar la unidad de aire acondicionado MANUAL DE INSTALAÇÃO Para uma utilização segura e correcta leia atentamente este manual e o manual de instalação da unidade exte rior antes de instalar o aparelho de ar condicionado INSTALLATI...

Страница 2: ...he unit in an unusual environment If the air conditioner is in stalled in areas exposed to steam volatile oil including machine oil or sulfu ric gas areas exposed to high salt content such as the seaside the perform ance can be significantly reduced and the internal parts can be damaged Do not install the unit where combustible gases may leak be produced flow or accumulate If combustible gas accum...

Страница 3: ...tuations of temperature and humidity The dimensions of ceiling opening can be regulated within the range shown in Fig 3 2 so center the main unit against the opening of ceiling ensuring that the respective opposite sides on all sides of the clearance between them becomes identical Use M10 3 8 suspension bolts Suspension bolts are to be procured at the field Install securely ensuring that there is ...

Страница 4: ...iagram Figures given in parentheses represent the dimensions in case of installing optional multi function casement 1 In advance set the parts onto the suspension bolts in the order of the washers with insulation washers without insulation and nuts double Fit the washer with cushion so that the insulation faces downward In case of using upper washers to suspend the main unit the lower washers with...

Страница 5: ...hen commercially available copper pipes are used wrap liquid and gas pipes with commercially available insulation materials heat resistant to 100 C or more thickness of 12 mm or more The indoor parts of the drain pipe should be wrapped with polyethylene foam in sulation materials specific gravity of 0 03 thickness of 9 mm or more Apply thin layer of refrigerant oil to pipe and joint seating surfac...

Страница 6: ...2 Wrong piping K Air bleeder A Insulation 9 mm or more L Raised B Downward slope 1 100 or more M Odor trap Grouped piping D O D ø32 PVC TUBE H Downward slope 1 100 or more E Make it as large as possible I O D ø38 PVC TUBE for grouped piping 9 mm or more insulation F Indoor unit G Make the piping size large for grouped piping J Up to 85 cm 1 Connect the drain socket supplied with the unit to the dr...

Страница 7: ...140 outdoor unit application Max 45 m If 2 5 mm2 used Max 50 m If 2 5 mm2 used and S3 separated Max 80 m For 200 250 outdoor unit application Max 18 m If 2 5 mm2 used Max 30 m If 4 mm2 used and S3 separated Max 50 m If 6 mm2 used and S3 separated Max 80 m 2 The 10 m wire is attached in the remote controller accessory Max 500 m 3 The figures are NOT always against the ground S3 terminal has DC 24 V...

Страница 8: ... switch settings when using separate indoor unit outdoor unit power supplies only Indoor unit specifications Required Required Required 1 A breaker with at least 3 0 mm contact separation in each pole shall be provided Use earth leakage breaker NV The breaker shall be provided to ensure disconnection of all active phase conductors of the supply 2 Max 120 m 3 The 10 m wire is attached in the remote...

Страница 9: ...roller can be operated easily Area in which the remote controller is beyond the reach of children Installation method Fig 6 5 1 Attach the remote controller holder to the desired location using 2 tapping screws 2 Place the lower end of the controller into the holder A Remote controller B Wall C Display panel D Receiver The signal can travel up to approximately 7 meters in a straight line within 45...

Страница 10: ... Press the FILTER A and TEST RUN B buttons simultaneously for at least 2 seconds The function selection screen will disappear momentarily and the air conditioner OFF display will appear 2 For wireless remote controller Fig 6 10 Changing the power voltage setting Be sure to change the power voltage setting depending on the voltage used 1 Going to the function select mode Press the CHECK button F tw...

Страница 11: ...vanes vanes angle setup 2 3 Ο 1 When the power supply returns the air conditioner will start 3 minutes later 2 Power failure automatic recovery initial setting depends on the connecting outdoor unit 6 3 3 How to set the fixed up down air direction Only for wired remote controller and PUHZ PU H application Only the particular outlet can be fixed to certain direction with the procedures below Once f...

Страница 12: ...nward after it becomes fixed airflow direction mode Fixed airflow direction mode display Note 0 indicates all outlets MITSUBISHI ELECTRIC label Outlet No 4 Outlet No 2 Outlet No 3 Outlet No 1 Outlet No Unit No Up Down air direction Refrigerant address No To select and identify the outlet to set 1 Press Set Temperature button 5 to change number with the outlet No blinking Select outlet No to set 2 ...

Страница 13: ...et No Up Down air direction Refrigerant address No Unit No Outlet No Up Down air direction Refrigerant address No Unit No Adjust to the next unit No with Set Temperature button 5 refrigerant address No 00 is remained 2 Press Filter button 3 to send the information on remote controller 3 Wait for 15 seconds How does the air conditioner run Only air from the outlet which No displayed on remote contr...

Страница 14: ...ivate mode then check whether warm air is blown out from the unit 5 Press the FAN button and check whether fan speed changes 6 Press the VANE button and check whether the auto vane operates properly 7 Press the ON OFF button to stop the test run Note Point the remote controller towards the indoor unit receiver while following steps 2 to 7 It is not possible to run the TEST RUN in FAN DRY or AUTO m...

Страница 15: ...r unit control system error memory error etc 14 PL Refrigerant circuit abnormal No sound E0 E3 Remote controller transmission error No sound E1 E2 Remote controller control board error No sound No corresponding Output pattern B Errors detected by unit other than indoor unit outdoor unit etc Wireless remote controller Wired remote controller Symptom Remark Beeper sounds OPERATION INDICATOR lamp bli...

Страница 16: ... after power on Only LED 1 is lighted LED 1 2 blink Connector for the outdoor unit s protection device is not connected Reverse or open phase wiring for the outdoor unit s power terminal block L1 L2 L3 Display messages do not appear even when operation switch is turned ON operation lamp does not light up Only LED 1 is lighted LED 1 blinks twice LED 2 blinks once Incorrect wiring between indoor and...

Страница 17: ... 9 2 2 Removing the corner panel Fig 9 4 Remove the screw from the corner of the corner panel Slide the corner panel as indicated by the arrow 1 to remove the corner panel Fig 9 3 Fig 9 4 A Intake grille B Grille C Intake grille levers D Grille hook E Hole for the grille s hook F Corner panel G Screw H Detail 3 Selection of the air outlets For this grille the discharge direction is available in 11...

Страница 18: ...box of the unit 5 Installing the intake grille Fig Note When reinstalling the corner panels each with a safety wire attached con nect the other end of each safety wire to the grille using a screw 4 pcs 4 8 as shown in the illustration If the corner panels are not attached they may fall off while the unit is operating Perform the procedure that is described in 9 2 Preparing to attach the grille in ...

Страница 19: ...Maintenance mode operation procedures 10 Easy maintenance function For PUHZ H RP application only By using the maintenance mode you can display many types of maintenance data on the remote controller such as the heat exchanger temperature and compressor current consumption for the indoor and outdoor units This function can be used whether the air conditioner is operating or not During air conditio...

Страница 20: ...n the following EU regulations Low Voltage Directive 2006 95 EC Electromagnetic Compatibility Directive 2004 108 EC Machinery Directive 2006 42 EC Energy related Products Directive 2009 125 EC Only RP35 50 60 71 100 BH79D045K05 Printed in UNITED KINGDOM HEAD OFFICE TOKYO BLDG 2 7 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN Authorized representative in EU MITSUBISHI ELECTRIC EUROPE B V HARMAN HOUS...

Отзывы: