background image

10

5)  Assigning a remote controller to each unit (Fig. 6-8)

Each unit can be operated only by the assigned remote controller.
Make sure each pair of an indoor unit PC board and a remote controller is assigned 
to the same pair No.

6)  Wireless remote controller pair number setting operation

1

  Press the SET button with something sharp at the end.

 

Start this operation from the status of remote controller display turned off.

 

              blinks and Model No. is lighted.

2

  Press the 

min

 button twice continuously. Pair No. “0” blinks.

3

  Press the temp 

buttons to set the pair number you want to set.

If you mistook the operation, press the ON/OFF 

 button and operate again 

from procedure 2.

4

  Press the SET button with something sharp at the end.

 

Set pair number is lighted for 3 seconds then turned off.

 

A

 Pair No. of wireless remote controller

Indoor PC board

0

Initial setting

1

Cut J41

2

Cut J42

3-9

Cut J41, J42

6.  Electrical work

6.3.  Function settings 

6.3.1.  Function setting on the unit (Selecting the unit functions)

1)  For wired remote controller (Fig. 6-)

Changing the power voltage setting
•  Be sure to change the power voltage setting depending on the voltage used.

1

  Go to the function setting mode.

 

Switch OFF the remote controller.

 

Press the FILTER 

A

 and TEST RUN 

B

 buttons simultaneously and hold 

them for at least 2 seconds. FUNCTION will start to blink.

2

  Use the 

C

 buttons to set the refrigerant address (

3

) to 00.

3

  Press 

D

 button and [--] will start to blink in the unit number (

4

) display.

4

  Use the 

C

 buttons to set the unit number (

4

) to 00.

5

  Press the MODE button 

E

 to designate the refrigerant address/unit number. [--] 

will blink in the mode number (

1

) display momentarily.

6

  Press the 

F

 buttons to set the mode number (

1

) to 04.

7

  Press the 

G

 button and the current set setting number (

2

) will blink.

 

Use the 

F

 button to switch the setting number in response to the power supply 

voltage to be used.

 

Power supply voltage

  

240 V 

:  setting number = 1

  

220 V, 230 V  :  setting number = 2

8

  Press the MODE button 

E

 and mode and the setting number (

1

) and (

2

) will 

change to being on constantly and the contents of the setting can be confirmed.

9

  Press the FILTER 

A

 and TEST RUN 

B

 buttons simultaneously for at least 2 

seconds. The function selection screen will disappear momentarily and the air 
conditioner OFF display will appear.

2)  For wireless remote controller (Fig. 6-10)

Changing the power voltage setting
•  Be sure to change the power voltage setting depending on the voltage used.

1

 Going to the function select mode

 

Press the 

CHECK

 button 

F

 twice continuously.

 

(Start this operation from the status of remote controller display turned off.)

 

CHECK

 is lighted and “00” blinks.

 

Press the 

 temp button 

C

 once to set “50”. Direct the wireless remote control-

ler toward the receiver of the indoor unit and press the 

h

 button 

A

2

  Setting the unit number

 

Press the 

 

temp buttons 

C

 and 

D

 to set the unit number “00”. Direct the 

wireless remote controller toward the receiver of the indoor unit and press the 

min

 button 

B

.

3

  Selecting a mode

 

Enter 04 to change the power voltage setting using the 

 

temp buttons 

C

 

and 

D

. Direct the wireless remote controller toward the receiver of the indoor 

unit and press the 

h

 button 

A

.

 

Current setting number: 

1 = 1 beep (1 second)

 

  

2 = 2 beeps (1 second each)

 

  

3 = 3 beeps (1 second each)

4

  Selecting the setting number

 

Use the  

 

temp buttons 

C

 and 

D

 to change the power voltage setting to 

01 (240 V). Direct the wireless remote controller toward the sensor of the indoor 

unit and press the 

h

 button 

A

.

5

  To select multiple functions continuously

 

Repeat steps 

3

 and 

4

 to change multiple function settings continuously.

6

  Complete function selection

 

Direct the wireless remote controller toward the sensor of the indoor unit and 

press the 

 button 

E

.

Note: Whenever changes are made to the function settings after installation 
or maintenance, be sure to record the changes with a mark in the “Setting” 
column of the Function table.

6.3..  Function setting on the remote controller

Refer to the indoor unit operation manual.

Fig. 6-9

CHECK

CHECK

ON/OFF

  TEMP

FAN

VANE

TEST RUN

AUTO STOP

AUTO START

h

min

LOUVER

MODE

CHECK

RESET

SET

CLOCK

CHECK

Fig. 6-10

CHECK

CHECK

Mode number
Setting number
Refrigerant address
Unit number

PAR-21MAA

ON/OFF

FILTER

CHECK

OPERATION

CLEAR

TEST

TEMP.

MENU

BACK

DAY

MONITOR/SET

CLOCK

ON/OFF

Fig. 6-8

ON/OFF

  TEMP

FAN

VANE

TEST RUN

AUTO STOP

AUTO START

h

min

LOUVER

MODE

CHECK

RESET

SET

CLOCK

MODEL SELECT

MODEL SELECT

01_BH79D045K05_EN.indd   10

2012/09/18 (火)   午後 3:44:57

Содержание RP100

Страница 1: ...ente manuale ed il manuale d installazione dell unità esterna MANUAL DE INSTALACIÓN Para un uso seguro y correcto lea detalladamente este manual de instalación antes de montar la unidad de aire acondicionado MANUAL DE INSTALAÇÃO Para uma utilização segura e correcta leia atentamente este manual e o manual de instalação da unidade exte rior antes de instalar o aparelho de ar condicionado INSTALLATI...

Страница 2: ...he unit in an unusual environment If the air conditioner is in stalled in areas exposed to steam volatile oil including machine oil or sulfu ric gas areas exposed to high salt content such as the seaside the perform ance can be significantly reduced and the internal parts can be damaged Do not install the unit where combustible gases may leak be produced flow or accumulate If combustible gas accum...

Страница 3: ...tuations of temperature and humidity The dimensions of ceiling opening can be regulated within the range shown in Fig 3 2 so center the main unit against the opening of ceiling ensuring that the respective opposite sides on all sides of the clearance between them becomes identical Use M10 3 8 suspension bolts Suspension bolts are to be procured at the field Install securely ensuring that there is ...

Страница 4: ...iagram Figures given in parentheses represent the dimensions in case of installing optional multi function casement 1 In advance set the parts onto the suspension bolts in the order of the washers with insulation washers without insulation and nuts double Fit the washer with cushion so that the insulation faces downward In case of using upper washers to suspend the main unit the lower washers with...

Страница 5: ...hen commercially available copper pipes are used wrap liquid and gas pipes with commercially available insulation materials heat resistant to 100 C or more thickness of 12 mm or more The indoor parts of the drain pipe should be wrapped with polyethylene foam in sulation materials specific gravity of 0 03 thickness of 9 mm or more Apply thin layer of refrigerant oil to pipe and joint seating surfac...

Страница 6: ...2 Wrong piping K Air bleeder A Insulation 9 mm or more L Raised B Downward slope 1 100 or more M Odor trap Grouped piping D O D ø32 PVC TUBE H Downward slope 1 100 or more E Make it as large as possible I O D ø38 PVC TUBE for grouped piping 9 mm or more insulation F Indoor unit G Make the piping size large for grouped piping J Up to 85 cm 1 Connect the drain socket supplied with the unit to the dr...

Страница 7: ...140 outdoor unit application Max 45 m If 2 5 mm2 used Max 50 m If 2 5 mm2 used and S3 separated Max 80 m For 200 250 outdoor unit application Max 18 m If 2 5 mm2 used Max 30 m If 4 mm2 used and S3 separated Max 50 m If 6 mm2 used and S3 separated Max 80 m 2 The 10 m wire is attached in the remote controller accessory Max 500 m 3 The figures are NOT always against the ground S3 terminal has DC 24 V...

Страница 8: ... switch settings when using separate indoor unit outdoor unit power supplies only Indoor unit specifications Required Required Required 1 A breaker with at least 3 0 mm contact separation in each pole shall be provided Use earth leakage breaker NV The breaker shall be provided to ensure disconnection of all active phase conductors of the supply 2 Max 120 m 3 The 10 m wire is attached in the remote...

Страница 9: ...roller can be operated easily Area in which the remote controller is beyond the reach of children Installation method Fig 6 5 1 Attach the remote controller holder to the desired location using 2 tapping screws 2 Place the lower end of the controller into the holder A Remote controller B Wall C Display panel D Receiver The signal can travel up to approximately 7 meters in a straight line within 45...

Страница 10: ... Press the FILTER A and TEST RUN B buttons simultaneously for at least 2 seconds The function selection screen will disappear momentarily and the air conditioner OFF display will appear 2 For wireless remote controller Fig 6 10 Changing the power voltage setting Be sure to change the power voltage setting depending on the voltage used 1 Going to the function select mode Press the CHECK button F tw...

Страница 11: ...vanes vanes angle setup 2 3 Ο 1 When the power supply returns the air conditioner will start 3 minutes later 2 Power failure automatic recovery initial setting depends on the connecting outdoor unit 6 3 3 How to set the fixed up down air direction Only for wired remote controller and PUHZ PU H application Only the particular outlet can be fixed to certain direction with the procedures below Once f...

Страница 12: ...nward after it becomes fixed airflow direction mode Fixed airflow direction mode display Note 0 indicates all outlets MITSUBISHI ELECTRIC label Outlet No 4 Outlet No 2 Outlet No 3 Outlet No 1 Outlet No Unit No Up Down air direction Refrigerant address No To select and identify the outlet to set 1 Press Set Temperature button 5 to change number with the outlet No blinking Select outlet No to set 2 ...

Страница 13: ...et No Up Down air direction Refrigerant address No Unit No Outlet No Up Down air direction Refrigerant address No Unit No Adjust to the next unit No with Set Temperature button 5 refrigerant address No 00 is remained 2 Press Filter button 3 to send the information on remote controller 3 Wait for 15 seconds How does the air conditioner run Only air from the outlet which No displayed on remote contr...

Страница 14: ...ivate mode then check whether warm air is blown out from the unit 5 Press the FAN button and check whether fan speed changes 6 Press the VANE button and check whether the auto vane operates properly 7 Press the ON OFF button to stop the test run Note Point the remote controller towards the indoor unit receiver while following steps 2 to 7 It is not possible to run the TEST RUN in FAN DRY or AUTO m...

Страница 15: ...r unit control system error memory error etc 14 PL Refrigerant circuit abnormal No sound E0 E3 Remote controller transmission error No sound E1 E2 Remote controller control board error No sound No corresponding Output pattern B Errors detected by unit other than indoor unit outdoor unit etc Wireless remote controller Wired remote controller Symptom Remark Beeper sounds OPERATION INDICATOR lamp bli...

Страница 16: ... after power on Only LED 1 is lighted LED 1 2 blink Connector for the outdoor unit s protection device is not connected Reverse or open phase wiring for the outdoor unit s power terminal block L1 L2 L3 Display messages do not appear even when operation switch is turned ON operation lamp does not light up Only LED 1 is lighted LED 1 blinks twice LED 2 blinks once Incorrect wiring between indoor and...

Страница 17: ... 9 2 2 Removing the corner panel Fig 9 4 Remove the screw from the corner of the corner panel Slide the corner panel as indicated by the arrow 1 to remove the corner panel Fig 9 3 Fig 9 4 A Intake grille B Grille C Intake grille levers D Grille hook E Hole for the grille s hook F Corner panel G Screw H Detail 3 Selection of the air outlets For this grille the discharge direction is available in 11...

Страница 18: ...box of the unit 5 Installing the intake grille Fig Note When reinstalling the corner panels each with a safety wire attached con nect the other end of each safety wire to the grille using a screw 4 pcs 4 8 as shown in the illustration If the corner panels are not attached they may fall off while the unit is operating Perform the procedure that is described in 9 2 Preparing to attach the grille in ...

Страница 19: ...Maintenance mode operation procedures 10 Easy maintenance function For PUHZ H RP application only By using the maintenance mode you can display many types of maintenance data on the remote controller such as the heat exchanger temperature and compressor current consumption for the indoor and outdoor units This function can be used whether the air conditioner is operating or not During air conditio...

Страница 20: ...n the following EU regulations Low Voltage Directive 2006 95 EC Electromagnetic Compatibility Directive 2004 108 EC Machinery Directive 2006 42 EC Energy related Products Directive 2009 125 EC Only RP35 50 60 71 100 BH79D045K05 Printed in UNITED KINGDOM HEAD OFFICE TOKYO BLDG 2 7 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN Authorized representative in EU MITSUBISHI ELECTRIC EUROPE B V HARMAN HOUS...

Отзывы: