![Mitsubishi Electric QJ71AS92 Скачать руководство пользователя страница 44](http://html.mh-extra.com/html/mitsubishi-electric/qj71as92/qj71as92_user-manual_1811845044.webp)
3 - 23 3 - 23
MELSEC-Q
3 SPECIFICATIONS
(13) Output data to slave addresses 4B to 31B (Buffer memory address
39
H
to 3F
H
: Un\G57 to Un\G63)
Output data to I/O slaves compatible with AS-i Ver. 2.11 (System B) are stored.
The values stored into the areas corresponding to the non-connected and non-
detected slaves are invalid (ignored).
Bit
15
to 12 11 to 8 7 to 4
3 to 0
39
H
7B 6B 5B 4B
3A
H
11B
10B
9B
8B
3B
H
15B 14B 13B 12B
3C
H
19B 18B 17B 16B
3D
H
23B 22B 21B 20B
3E
H
27B 26B 25B 24B
3F
H
31B 30B 29B 28B
ON: 1, OFF: 0
Example:
Bit
15
to 12 11 to 8 7 to 4
3 to 0
39
H
O3 O2 O1 O0
O3
O2
O1
O0
Slave address 7A
O0 = ON
O1 = OFF
O2 = ON
O3 = ON
When
1
1
0
1
b 15
14
13
12
39
H
(14) List of Projected Slaves (LPS (For Write)) (Buffer memory address
49
H
to 4A
H
, 4B
H
to 4C
H
: Un\G73 to Un\G74, Un\G75 to Un\G76)
Bit 15
14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
49
H
15A 14A 13A 12A 11A 10A 9A 8A
7A 6A 5A 4A 3A 2A 1A
4A
H
31A 30A 29A 28A 27A 26A 25A 24A 23A 22A 21A 20A 19A 18A 17A 16A
4B
H
15B
14B 13B 12B 11B 10B 9B 8B
7B 6B 5B 4B 3B 2B 1B
4C
H
31B 30B 29B 28B 27B 26B 25B 24B 23B 22B 21B 20B 19B 18B 17B 16B
: Not used (0 fixed)
If the bit corresponding to the number of the slave to be communicated with and
Y13 are turned ON, data in this area will be registered in the QJ71AS92 and be
reflected into the List of projected slaves (LPS (for read)) (buffer memory
address: 19
H
to 1C
H
).
(Related item: Section 4.5 (2))
TIP
• The projected slave list (LPS (for write)) is handled as a 64-bit length in the
QJ71AS92. Therefore, if data is written to only the buffer memory address 49
H
,
the contents of the buffer memory address 4A
H
to 4C
H
are also made valid as
data.
• When communicating with the slave that has been judged as ready for
communication in the active slave list (LAS) (buffer memory addresses: 15
H
to
18
H
), easy registration of the projected slave list (LPS (for read)) and configuration
are enabled by using the command buffer <request> 201
H
.
Downloaded from