3 SPECIFICATIONS
MELSEC-Q
3.4.14 Disconnection detection flag (Un\G49)
(1) The disconnection detection flag of the corresponding channel turns to 1 when the
disconnection of the RTD or wire break is detected.
(2) Disconnection detection availabe for conversion-enabled channels only.
(3) Disconnection is detected on each channel.
(4) Disconnection detection flag is cleared when Operating Condition Setting Request
(Y9) or Error Clear Request (YF) is turned on.
(5) If disconnection is detected on any of conversion-enabled channels, the
Disconnection Detection Signal (XC) also turns on.
For a channel where disconnection is detected, a value based on the Conversion
setting for disconnection detection (buffer memory address 148: Un\G148) is
stored in the CH measured temperature value (buffer memory addresses 11 to
14, 54 to 61: Un\G11 to 14, Un\G54 to 61).
Conversion of the channels not disconnected is continued.
For the Q64RD-G, "ALM LED" flashes.
(6) The relationships between disconnection detection and conversion enable/disable
are indicated below.
Connection Status
Conversion Enable/
Disable Setting
Disconnection
Detection Flag
Conversion enable
OFF
Conversion disable
Conversion enable
ON
Conversion disable
OFF
Conversion enable
ON
Conversion disable
OFF
POINT
Any channel where no RTD is connected must be specified as "conversion
disable".
Not doing so will turn on the disconnection detection flag.
For measured temperature values to be stored when the Disconnection Detection
Signal (XC) turns ON, any of "Value immediately before disconnection", "UP
scale (maximum value of measured temperature range + 5% of measured
temperature range)", "Down scale (minimum value of measured temperature
range – 5% of measured temperature range)", or "Given value" can be selected.
(Refer to Section 3.2.2.)
Refer to Section 4.4 for the RTD wiring.
Refer to Section 8.2.7 for the troubleshooting of disconnection detection.
b15 b14 b13 b12 b11 b10
b9
b8
b7
b6
b5
b4
b3
b2
b1
b0
0
0
0
0
CH4 CH3 CH2 CH1
0: Normal
1: Disconnection
0
0
0
0
0
0
0
0
a
A
B
b
Without
disconnection
a
A
B
b
With
disconnection
a
A
B
b
Without
disconnection
Содержание Q64RD
Страница 2: ......
Страница 99: ...5 17 5 17 5 UTILITY PACKAGE GX Configurator TI MELSEC Q X Y Monitor Test 1 OMC refresh ...
Страница 108: ...6 3 6 3 6 PROGRAMMING MELSEC Q 2 Program example 6 1 2 Program example used when utility package is not used ...
Страница 113: ...6 8 6 8 6 PROGRAMMING MELSEC Q 2 Program example ...
Страница 114: ...6 9 6 9 6 PROGRAMMING MELSEC Q ...
Страница 178: ...App 19 App 19 APPENDICES MELSEC Q Appendix 3 External Dimension Diagram 1 Q64RD Q64RD G Unit mm ...
Страница 181: ...WARRANTY ...
Страница 183: ......