15. INSTALLATION
AIR TO WATER
15-2. Selecting an installation site
Do not install outdoors. The unit is not waterproof.
Back up system is recommended in case of PWFY unit breakdown.
The unit will get hot. Do not install in a location where heat gets trapped inside.
Be sure to install unit in a place strong enough to withstand its weight.
Any lack of strength may cause unit to fall down, resulting in a personal injury.
Do not install the unit where corrosive gas is generated.
Have installation work in order to protect against earthquake.
Any installation deficiency may cause unit to fall down, resulting in a personal injury.
Pay a special attention to the place, such as a basement, etc. where refrigeration gas can stay, since refrigeration is
heavier than the air.
Do not install the unit where combustible gas may leak.
- If the gas leaks and accumulates around the unit, an explosion may result.
When installing the unit in a hospital, communication station, or similar place, provide sufficient protection against noise.
- The inverter equipment, private power generator, high-frequency medical equipment, or radio communication
equipment may cause the air conditioner to operate erroneously, or fail to operate. On the other hand, the air conditioner
may affect such equipment by creating noise that disturbs medical treatment or image broadcasting.
Do not install the unit on a structure that may cause leakage.
- When the room humidity exceeds 80% or when the drain pipe is clogged, condensation may drip from the indoor unit.
Perform collective drainage work together with the unit, as required.
It is recommended that a water pump is connected to each PWFY unit.
15-3. Securing installation and service space
Please secure the following service spaces after installation.
(All servicing can be performed from the front of the unit)
Be sure to install the unit in a location which can adequately support its weight.
- If there is insufficient strength to support the unit's weight, it could fall and cause injuries.
▪ PWFY unit
(B)
a
b
c
(C)
(A)
(A) Piping space (right side)
(B) Top view
(C) Service space (front side)
Model
a
15-3/4
(400)
11-13/16
(300)
23-5/8
(600)
15-3/4
(400)
11-13/16
(300)
23-5/8
(600)
15-3/4
(400)
PWFY-P36NMU-E-BU PWFY-P36NMU-E2-AU PWFY-P72NMU-E2-AU
Unit: in (mm)
11-13/16
(300)
23-5/8
(600)