2. SPECIFICATIONS
AIR TO WATER
2. SPECIFICATIONS
50~113°F (10~45°C)
WR2-Series
Circulating Water temp.
(for water source unit side)
Model
Power source
kW
Heating capacity
kcal / h
(Nominal )
BTU / h
*1
*1
*1
kW
A
W.B
W.B
dB<A>
in.(mm)
in.(mm)
in.(mm)
in.(mm)
in.(mm)
mm
in.
lbs(kg)
kW
-
Power input
Liquid
Gas
Current input
Outdoor temp.
Inlet Water temp. (for PWFY side)
Total capacity
Temp. range of
heating
Connectable
outdoor unit/heat source unit
Model / Quantity
Sound pressure level (measured in anechoic room)
Diameter of
refrigerant pipe
Diameter of
water pipe
Field drain pipe size
External finish
External dimension H × W × D
Net weight
Compressor
Maker
Type
Starting method
Motor output
Circulating water
Range
Protection on Internal circuit
(R134a)
High pressure protection
Inverter circuit (COMP)
Compressor
Type × original charge
Refrigerant
Control
R410A
Design pressure
R134a
Water
External
Drawing
Standard attachment
Optional parts
Remark
Note:
*1 Nominal heating conditions (PWFY conditions are indicated in the parentheses.)
<R2/H2i R2-Series>
kcal/h = kW x 860
BTU/h = kW x 3,412
cfm
= m
3
/min x 35.31
G(us) = L × 0.2642
lbs
= kg / 0.4536
psi
= MPa×145.038
Outdoor Temp. : 47°FDB / 43°FWB (8.3°CDB/6.1°CWB)
Pipe length : 25 ft (7.6 m)
Level difference : 0 ft (0 m)
(Inlet water Temp.: 149°F (65°C) Water flow rate: 9.4 gpm (2.15 m
3
/h))
<WR2-Series>
Circulating water Temp.: 70°F (21.1°C)
Pipe length : 25 ft (7.6 m)
Level difference : 0 ft (0 m)
(Inlet water Temp. for PWFY side : 149°F (65°C) Water flow rate 9.4 gpm (2.15 m
3
/h))
* Due to continuing improvement, the above specifications may be subject to change without notice.
* Install the unit in an environment where the
wet bulb Temp. will not exceed 90°F (32°C).
* The unit is not designed for outside installations.
* Please don't use the steel material for the water piping material.
* The water circuit must use the closed circuit.
* Please do not use it as a drinking water.
* Please always make water circulate or add the brine to the circulation water when the ambient temperature becomes 32°F (0°C) or less.
* Please always make water circulate or pull out the circulation water completely when not using it.
* Please do not use groundwater and well water.
* The specification data is subject
to rounding variation.
Unit converter
Lubricant
Operation volume
Inlet
Outlet
Accessory
Wiring
Document
m
3
/h
G/h
gpm
L/min
MPa
MPa
psi
psi
psi
MPa
1.00
Installation Manual, Instruction Book
800 (785 without legs) × 450 × 300
KE94C344
Inverter
1.0
Over-heat protection, Over-current protection
R134a x ( 2lbs + 7oz) ( 1.1kg )
10,100
11.7
WKB94T460
NONE
44
NO
Strainer, Heat insulation material, 2 × Washer, wire
PWFY-P36NMU-E-BU
1-phase 208-230V 60Hz
PT3/4 (27.2) Screw
MITSUBISHI ELECTRIC CORPORATION
NEO22
Φ
1-1/4 (
Φ
32)
Inverter rotary hermetic compressor
31-1/2" (30-15/16" without legs) × 17-3/4” × 11-13/16”
131 (59)
PT3/4 (27.2) Screw
12.30 - 11.12
50~100% of outdoor/heat source unit capacity
R2-Series
R2-Series (High efficiency)
H2i-Series (R2)
WR2-Series
Φ
5/8 (
Φ
15.88) Brazed
-4~90ºF (-20~32ºC) R2-Series
-13~90ºF (-25~32ºC) H2i-Series (R2)
Φ
3/8 (
Φ
9.52) Brazed
39,900
50~160°F (10~71°C)
2.48
0.6~2.15
158~568
2.6~9.4
10~36
LEV
601
4.15
522
3.60
High pressure sensor, High pressure switch at 3.60 MPa (522 psi)
Discharge thermo protection, Over-current protection
145
Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other
items shall be referred to the Installation Manual.