12. ELECTRICAL WORK
AIR TO WATER
12-3. Power cable specifications
Do not use anything other than the correct capacity breaker and fuse. Using fuse, wire or copper wire with too large ca-
pacity may cause a risk of malfunction or fire.
1-phase 2-wire,
208/230V,60Hz
Minimum wire thickness (mm
2
/AWG)
Switch (A)
Breaker for wiring
(NFB)
Breaker for current leakage
Main cable
Branch
Ground
Capacity
Fuse
PWFY-P36NMU-E-BU
2.5/12
-
2.5/12
25
25
25
25A 30mA or 100mA
0.1sec. or less
1-phase 2-wire,
208/230V,60Hz
Minimum wire thickness (mm
2
/AWG)
Switch (A)
Breaker for wiring
(NFB)
Breaker for current leakage
Main cable
Branch
Ground
Capacity
Fuse
PWFY-P36NMU-E2-AU
PWFY-P72NMU-E2-AU
1.5/14
-
1.5/14
15
15
15
15A 30mA or 100mA
0.1sec. or less
(A) Breaker for current leakage
(B) Local switch or breakers for wiring
(C) PWFY-P36NMU-E-BU
(D) PWFY-P36, 72NMU-E2-AU
(E) Pull box
(A)
(B)
(A)
(B)
(C)
(E)
(E)
PE
PE
PE
(D)
PE
(D)
(D)
PWFY-P36NMU-E-BU
PWFY-P36, 72NMU-E2-AU