53
English
Step
LCD screen
Procedure
3
AUTO TEST
OVR
OFR
UVR UFR
READY FOR TEST
EXIT
AUTO TEST
OVR
TESTING
Vg 230.0V
Vp 257.0V
T S
To Step 4
Run AUTO TEST of OV protection function
Touch and release the [SELECT] button, and select
OVR using the « » arrow.
Ɣ
To skip AUTO TEST of the OV protection function,
touch and release the [SELECT] button, and select
UVR using the « » arrow.
Touch and release the [ENTER] button to start AUTO TEST.
On the «AUTO TEST OVR» screen,
TESTING
is
displayed as shown on the LCD screen at left.
When grid-connected operation starts
Vg: Displays present grid voltage
Vp: Displays
setting
value for the OV protection function. Value
becomes incrementally smaller while AUTO TEST is running.
Automatically goes to Step 4 when AUTO TEST is finished.
4
When normal
AUTO TEST
OVR
FINISHED
Vg 230.0V
Vp 229.5V
T 0.09S
When abnormal
AUTO TEST
OVR
FINISHED
Vg -------V
Vp -------V
T -------S
When AUTO TEST is finished, FINISHED is shown on the
«AUTO TEST OVR» screen as shown on the LCD screen at left.
Vg: Displays operating grid voltage for the OV
protection function.
Vp: Displays operating setting value for the OV
protection function.
T : Displays operating time for the OV protection
function.
Touch and release the [ENTER] button to return to Step 2.
Ɣ
If AUTO TEST does not finish normally, "---" is
displayed for Vg, Vp, and T. Repeat Step 3, and
run AUTO TEST again.
5
AUTO TEST
OVR OFR
UVR UFR
READY FOR TEST
EXIT
AUTO TEST
UVR
TESTING
Vg 230.0V
Vp 203.0V
T S
To Step 6
Run AUTO TEST of UV protection function
Touch and release the [SELECT] button, and select
UVR using the « » arrow.
Ɣ
To skip AUTO TEST of the UV protection function,
touch and release the [SELECT] button, and select
OFR using the « » arrow.
Touch and release the [ENTER] button to start AUTO TEST.
On the «AUTO TEST UVR» screen,
TESTING
is
displayed as shown on the LCD screen at left.
When grid-connected operation starts
Vg: Displays present grid voltage
Vp: Displays setting value for the UV protection
function. Value becomes incrementally larger
while AUTO TEST is running.
Automatically goes to Step 6 when AUTO TEST is finished.
6
When normal
AUTO TEST
UVR
FINISHED
Vg 230.0V
Vp 230.5V
T 0.09S
When abnormal
AUTO TEST
UVR
FINISHED
Vg ------V
Vp ------V
T ------S
When AUTO TEST is finished, FINISHED is shown on the
«AUTO TEST UVR» screen as shown on the LCD screen at left.
Vg: Displays operating grid voltage for the UV
protection function.
Vp: Displays operating setting value for the UV
protection function.
T : Displays operating time for the UV protection
function.
Touch and release the [ENTER] button to return to Step 2.
Ɣ
If AUTO TEST does not finish normally, "---" is
displayed for Vg, Vp, and T. Repeat Step 5, and
run AUTO TEST again.
To Step 2
Touch and release the
[ENTER] button once.
To Step 2
Touch and release the
[ENTER] button once.
Touch and release the
[ENTER] button once.
When AUTO TEST
has finished
To Step 2
Touch and release the
[ENTER] button once.
To Step 2
Touch and release the
[ENTER] button once.
When AUTO TEST
has finished
Touch and release the
[ENTER] button once.