9-9. FUNCTION OF SWITCHES
Type of
Switch
Switch No.
Function
Action by the switch operation
Effective timing
ON
OFF
DIP
switch
SW1
1
Manual defrost
*1
Start
Normal
When compressor is working in heat operation
*1
2
Abnormal history clear
Clear
Normal
OFF or operating
3
Refrigerant address
setting
When power supply ON
4
5
6
SW4
1
No function
–
–
–
2
No function
–
–
–
SW8
1
No function
–
–
–
2
No function
–
–
–
3
Separate indoor/outdoor
unit power supplies
Used
Not used
When power supply ON
SW5
1
No function
–
–
–
2
Power failure
automatic recovery
*2
Auto recovery
No auto recovery
When power supply ON
3, 4
No function
–
–
–
5
Capacity operation
Passive mode
Active mode
When power supply ON
6
DHW operation
Quick mode
ECO mode
When power supply ON
SW7
*3
1
Mode select
*4
Demand function
Low noise mode
When power supply ON
2
Service check function
*5
Backup data
Normal
Always
3
No function
–
–
–
4
No function
–
–
–
5
No function
–
–
–
6
Defrost setting
For high humidity
Normal
Always
SW9
1
No function
–
–
–
2
No function
–
–
–
3,4
Starting Ambient temp.
of blink injection
Ambient temp. of ZUBADAN blink injection
becomes effective.
SW9-3 SW9-4
Ambient temp.
OFF
OFF
[
3°C (Initial setting)
OFF
ON
[
0°C
ON
OFF
[
−3°C
ON
ON
[
−6°C
Always
SW6
1
Model select
2
3
4
5
6
7
8
*1
Manual defrost should be done as follows.
1
Change the DIP SW1-1 on the outdoor controller board from OFF to ON.
2
Manual defrost will start by the above operation
1
if these conditions written below are satisfied.
• Heat mode setting
• 10 minutes have passed since compressor started operating or previous manual defrost finished.
• Pipe temperature is less than or equal to 8°C.
Manual defrost will finish if certain conditions are satisfied.
Manual defrost can be done if above conditions are satisfied when DIP SW1-1 is changed from OFF to ON.
After DIP SW1-1 is changed from OFF to ON, there is no problem if DIP SW1-1 is left ON or changed to OFF again.
This depends on the service conditions.
*2
"Power failure automatic recovery" can be set by either remote controller or this DIP SW. If one of them is set to ON, "Auto recovery" activates. Please set "Auto
recovery" basically by remote controller because all units do not have DIP SW. Please refer to the indoor unit installation manual.
*3
Please do not use SW7-2, 4, 5, 6 usually. Trouble might be caused by the usage condition.
*4
SW7-1 is setting change over of Demand. It is effective only in the case of external input. (Local wiring is necessary. Refer to the next page: Special function.)
*5
This function displays the backup data when errors occurred. (Last 4 data at the maximum)
*6
SW6-1 to 3: Function Switch
PUZ-HWM140VHA(-BS) PUZ-HWM140YHA(-BS)
The black square (
■
) indicates a switch position.
1
ON
2 3 4 5 6
1
ON
2 3 4 5 6
1
ON
2 3 4 5 6
1
ON
2 3 4 5 6
1
ON
2 3 4 5 6
1
ON
2 3 4 5 6
0
1
2
3
4
5
*6
*6
Содержание PUZ-HWM140VHA
Страница 15: ...15 OCH748 6 WIRING DIAGRAM PUZ HWM140VHA BS ...
Страница 16: ...16 OCH748 PUZ HWM140YHA BS ...