45
OCH748
<Display function of inspection for outdoor unit>
The blinking patterns of both LED1 (green) and LED2 (red) indicate the types of abnormality when it occurs. Types of abnor-
mality can be indicated in details by connecting an optional part “A-Control Service Tool (PAC-SK52ST)” to connector CNM on
outdoor controller board.
F3
F5
F9
—
—
—
E6
E7
—
—
E0
E3
E4
E5
[Display]
(1)Normal condition
(2)Abnormal condition
Unit condition
Outdoor controller board
A-Control Service Tool
LED1 (Green)
LED2 (Red)
Check code
When the power is turned on
When unit stops
When compressor is warming up
When unit operates
Lit
Lit
Lit
Lit
Lit
Not lit
Indication of the display
Alternately blinking display
Operation mode
Not lit
Lit
00, etc.
08, etc.
C5, H7, etc.
Indication
Error
Check
code*
Outdoor controller board
Contents
Inspection method
LED1 (Green) LED2 (Red)
1 blinking 2 blinking
2 blinking 1 blinking
2 blinking
3 blinking
4 blinking
5 blinking
Connector(63L) is open.
Connector(63H) is open.
2 connectors are open.
Startup time over
Check code is not defined.
Incorrect connection
Miswiring of indoor/outdoor unit conne-
cting wire, excessive number of indoor
units (4 units or more)
Miswiring of indoor/outdoor unit co-
nnecting wire (converse wiring or di-
sconnection)
Indoor/outdoor unit communication error
(signal receiving error) is detected by indoor unit.
Indoor/outdoor unit communication error
(transmitting error) is detected by indoor unit.
Indoor/outdoor unit communication error
(signal receiving error) is detected by
outdoor unit.
Indoor/outdoor unit communication error
(transmitting error) is detected by outdoor unit.
Remote controller signal receiving
error is detected by remote controller.
Remote controller transmitting error
is detected by remote controller.
Remote controller signal receiving
error is detected by indoor unit.
Remote controller transmitting error
is detected by indoor unit.
Serial communication error
<Communication between outdoor
controller board and outdoor power
board>
*
Check code displayed on remote controller
** Refer to service manual for indoor unit.
1
Check if indoor/outdoor connecting wire is connected correctly.
2
Check if 4 or more indoor units are connected to outdoor unit.
3
Check if noise entered into indoor/outdoor connecting wire
or power supply.
4
Re-check error by turning off power, and on again.
1
Check if connector (63H or 63L) on the outdoor controller
board is not disconnected.
2
Check continuity of pressure switch (63H or 63L) by tester.
1
Check if connector (CN4) on outdoor controller board and
outdoor power board is not disconnected.
1
Connect I/F or FTC to the unit.
1
Check if noise entered into transmission wire of remote controller.
2
Check if noise entered into indoor/outdoor connecting wire.
3
Re-check error by turning off power, and on again.
1
Check if connecting wire of indoor unit or remote controller
is connected correctly.
2
Check if noise entered into transmission wire of remote
controller.
3
Re-check error by turning off power, and on again.
1
Check if indoor/outdoor connecting wire is connected correctly.
2
Check if noise entered into indoor/outdoor connecting wire or
power supply.
3
Check if noise entered into indoor/outdoor controller board.
4
Re-check error by turning off power, and on again.
**
P.20
**
P.21
(EA)
P.21
(Eb)
P.21
(EC)
**
**
P.26
(E8)
Detailed
reference
page
P.26
(E9)
P.25
P.26
P.25
P.26
P.26
P.21
P.26
Ed
EF
EE
9-8. OUTDOOR UNIT OPERATION MONITOR FUNCTION
PUZ-HWM140VHA PUZ-HWM140YHA
PUZ-HWM140VHA-BS PUZ-HWM140YHA-BS
(2)Abnormal condition
Indication
Error
Detailed
reference
page
Outdoor controller board
Contents
Check
code*
Inspection method
LED1 (Green) LED2 (Red)
1 blinking 2 blinking
Connector(63L) is open.
F3
1
Check if connector (63H or 63L) on the outdoor controller
board is not disconnected.
2
Check continuity of pressure switch (63H or 63L) by tester.
**
Connector(63H) is open.
F5
P.20
2 connectors are open.
F9
**
2 blinking 1 blinking
Miswiring of indoor/outdoor unit
connecting wire, excessive number
of indoor units (4 units or more)
―
1
Check if indoor/outdoor connecting wire is connected correctly.
2
Check if 4 or more indoor units are connected to outdoor unit.
3
Check if noise entered into indoor/outdoor connecting wire or
power supply.
4
Re-check error by turning off power, and on again.
P.21
(EA)
Miswiring of indoor/outdoor unit
connecting wire (converse wiring
or disconnection)
―
P.21
(Eb)
Startup time over
―
P.21
(EC)
2 blinking
Indoor/outdoor unit communica-
tion error (signal receiving error) is
detected by indoor unit.
E6
1
Check if indoor/outdoor connecting wire is connected correctly.
2
Check if noise entered into indoor/outdoor connecting wire or
power supply.
3
Check if noise entered into indoor/outdoor controller board.
4
Re-check error by turning off power, and on again.
**
Indoor/outdoor unit communication
error (transmitting error) is detect-
ed by indoor unit.
E7
**
Indoor/outdoor unit communica-
tion error (signal receiving error) is
detected by outdoor unit.
―
P.26
(E8)
Indoor/outdoor unit communication
error (transmitting error) is detect-
ed by outdoor unit.
―
P.26
(E9)
3 blinking
Remote controller signal receiving
error is detected by remote con-
troller.
E0
1
Check if connecting wire of indoor unit or remote controller is
connected correctly.
2
Check if noise entered into transmission wire of remote con-
troller.
3
Re-check error by turning off power, and on again.
P.25
Remote controller transmitting
error is detected by remote con-
troller.
E3
P.26
Remote controller signal receiving
error is detected by indoor unit.
E4
P.25
Remote controller transmitting
error is detected by indoor unit.
E5
P.26
4 blinking
Check code is not defined.
EF
1
Check if noise entered into transmission wire of remote con-
troller.
2
Check if noise entered into indoor/outdoor connecting wire.
3
Re-check error by turning off power, and on again.
P.26
Incorrect connection
EE
1
Connect I/F or FTC to the unit.
P.21
5 blinking
Serial communication error
<Communication between outdoor
controller board and outdoor power
board>
Ed
1
Check if connector (CN4) on outdoor controller board and out-
door power board is not disconnected.
P.26
* Check code displayed on remote controller
** Refer to service manual for indoor unit.