55
1
2
3
4
5
6
M
Gray
Orange
Red
Yellow
Black
1
2
3
4
5
6
M
Parts name
Check points
Disconnect the connector then measure the resistance with a tester.
(At the ambient temperature 10
:
~30
:
, 50˚F~86˚F)
Disconnect the connector then measure the resistance with a tester.
(Winding temperature 20
:
, 68˚F)
Thermistor (TH3)
<Outdoor pipe>
Thermistor (TH4)
<Discharge>
Thermistor (TH6)
<Outdoor 2-phase pipe>
Thermistor (TH7)
<Outdoor>
Thermistor (TH8)
<Heatsink>
Normal
160k
"
~410k
"
4.3k
"
~9.6k
"
39k
"
~105k
"
TH4
TH3
TH6
TH7
TH8
Abnormal
Open or short
Normal
Red - White
Red - Orange
Brown - Yellow
Brown - Blue
Abnormal
46
±
4
"
Measure the resistance between the terminals with a tester.
(At the ambient temperature 20
:
, 68˚F)
Solenoid valve coil
<Four-way valve>
(21S4)
Motor for compressor
(MC)
Linear expansion valve
(LEV-A)
For A12, 18
Linear expansion valve
(LEV-A)
For A24-42
Normal
Abnormal
Open or short
A18-36
A42
Open or short
Disconnect the connector then measure the resistance with a tester.
(Winding temperature 20
:
, 68˚F)
Measure the resistance between the terminals with a tester.
(At the ambient temperature 20
:
, 68˚F)
Normal
1450
±
150
"
Abnormal
Open or short
Solenoid valve coil
<Bypass valve>
(SV)
For A24-36 only
Refer to next page.
Fan motor(MF1,MF2)
1500
±
150
"
2350
±
170
"
A12, 18
A42
0.320
"
A24, 30, 36
0.880
"
0.266
"
Measure the resistance between the terminals with a tester.
(Winding temperature 20
:
, 68˚F)
Normal
Abnormal
Open or short
W
V
U
Red
Brown
Blue
Orange
Yellow
White
Normal
Gray - Black
Gray - Red
Gray - Yellow
Gray - Orange
Abnormal
46
±
3
"
Open or short
10-6. HOW TO CHECK THE PARTS
PUZ-A18/24/30/36/42NHA2
PUZ-A18/24/30/36/42NHA2-BS
PUY-A12/18/24/30/36/42NHA2 PUY-A12/18/24/30/36/42NHA2-BS