89
Function
Settings
No.
Mode
No.
Setting
: Initial setting (Factory setting)
- : Not available
4-Way
cassette
Ceiling suspended
Wall
mounted
PCA-GA
PKA-GA(L)
PKA-FA(L)
Filter sign
100h
1
2500h
07
2
"Clean the filter" indicator is not displayed
3
Air flow
Quiet
1
-
(Fan speed)
Standard
08
2
-
High ceiling
3
-
No.of air outlets
4 directions
1
-
-
3 directions
09
2
-
-
2 directions
3
-
-
-
-
Optional high efficiency
Not supported
10
1
-
filter
Supported
2
-
Vane setting
No vanes (Vane No.3 setting : PLA only)
1
-
Vane No.1 setting
11
2
-
Vane No.2 setting
3
-
Energy saving air
Disabled
12
1
-
flow (Heating mode)
Enabled
2
-
Optional humidifier
Not supported
13
1
-
-
(PLA only)
Supported
2
-
-
Vane differential setting
No.1 setting (TH5: 24-28
:
)
1
in heating mode
No.2 setting (Standard, TH5:28-32
:
)
14
2
(cold wind prevention)
No.3 setting (TH5: 32-38
:
)
3
Swing
23
1
2
Set temperature in heating
24
1
mode (4 deg up)
2
Fan speed when the
Extra low
1
heating thermostat is OFF
Stop
25
2
Keeping fan speed set by remote controller
3
Quiet operation mode
Disabled (Standard)
26
1
-
-
of PLA-AA(Fan speed)
Enabled (Quiet operation mode)
2
-
-
-
-
Fan speed when the
Keeping fan speed set by remote controller
27
1
cooling thermostat is OFF
Stop
2
Detection of abnormality of
Detect
28
1
the pipe temperature (P8)
Neglect
2
PLA-BA
Not available Swing
Available
Wave air flow
Available
Temperature correction: Valid
Not available Temperature correction: Invalid
}
PLA-BA
}
PLA-BA
(2) Functions available when setting the unit number to 01-03 or AL (07 in case of wireless remote controller)
• When setting functions for an indoor unit in an independent system, set the unit number to 01 referring to
4
setting the
indoor unit number.
• When setting functions for a simultaneous twin indoor unit system, set the unit number to 01 to 03 for each indoor
unit in case of selecting different functions for each unit referring to
4
setting the indoor unit number.
• When setting the same functions for an entire simultaneous Twin-indoor unit system, set refrigerant address to AL
(07 in case of wireless remote controller) referring to
4
setting the indoor unit number.
Mode No.11
Setting No.
Settings
PLA-BA
PCA-GA
1
No Vanes
Vane No.3 setting
( Downward position than the standard )
Less smudging
No vane function
2
Vane No.1 setting
Standard
Standard
3
Vane No.2 setting
( Upward position than the standard )
Less draft *
( Upward position than the standard )
Less draft *
* Be careful of the smudge on ceiling.