13
GB
<Refrigerant piping connection examples>
[Fig.10.2.2]
<Front piping and bottom post-piping> (Sold separetely)
(Unit: mm [in])
No.
1
2
3
Shape
ø22.2
[7/8]
ID ø25.4 [1]
ID ø22.2 [7/8]
OD ø19.05 [3/4]
ø22.2
[7/8]
ID ø25.4 [1]
ID ø19.05 [3/4]
OD ø19.05 [3/4]
P72 (
-
)
-
-
-
P96 (CMY-RS200UEB)
1 pc. Low-pressure side
1 pc. High-pressure side
1 pc. High-pressure side
P120 (CMY-RS300UEB)
-
1 pc. High-pressure side
1 pc. High-pressure side
P144 (CMY-RS400UEB)
1 pc. High-pressure side
-
-
<Front pipe routing>
When not attaching a low-pressure twinning pipe
When attaching a low-pressure twinning pipe *1,*2
C
B
<A>
<B>
A
A
B
D
E
F
C
<A>
<B>
<Bottom pipe routing>
When not attaching a low-pressure twinning pipe
When attaching a low-pressure twinning pipe *1,*2
A
B
C
<A>
<B>
C
D
*3
H
I
G
<Severing portion
referral fi gure>
C
E
F
D
<A>
<B>
<A> Low-pressure side
<B> High-pressure side
A
Refrigerant service valve piping
B
On-site piping (low-pressure connecting pipe)
C
On-site piping (high-pressure connecting pipe)
D
Twinning Kit (sold separately)
E
On-site piping (low-pressure connecting pipe: to BC controller)
F
On-site piping (low-pressure connecting pipe: to outdoor unit)
G
75 mm [2-31/32 in] (reference measurement)
H
ID ø25.4 mm [1 in] side
I
Severing portion
*1 For the attachment of the Twinning pipe (sold separately), refer to the instructions included in the kit.
*2 Connection pipe is not used when the Twinning Kit is attached.
*3 Use a pipe cutter to sever.
Front pipe routing
•
P72
Expand the high-pressure side on-site piping
(ID ø15.88 mm [5/8 in]) and connect to the refrigerant
service valve piping.
P96, P120
Use the included connecting pipe
2
and elbow
3
to
connect.
P144
Use the included connecting pipe
1
to connect.
P72
Expand the low-pressure side on-site piping
(ID ø19.05 mm [3/4 in]) and connect to the refrigerant
service valve piping.
P96
Use the included connecting pipe
1
to connect.
P120,P144
Expand the low-pressure side on-site piping
(ID ø28.58 mm [1-1/8 in]) and connect to the
refrigerant service valve piping.
Bottom pipe routing
•
P72
Expand the high-pressure side on-site piping
(ID ø15.88 mm [5/8 in]) and connect to the refrigerant
service valve piping.
P96, P120
Use the included connecting pipe
2
. Expand the
on-site piping to connect to ID ø19.05 mm [3/4 in]
P144
Sever the included connecting pipe
1
as shown in
the fi gure with a pipe cutter to use. Expand the on-site
piping to connect to ID ø22.2 mm [7/8 in].
P72
Expand the low-pressure side on-site piping
(ID ø19.05 mm [3/4 in]) and connect to the refrigerant
service valve piping.
P96
Sever the included connecting pipe
1
as shown in
the fi gure with a pipe cutter to use. Expand the on-site
piping to connect to ID ø22.2 mm [7/8 in].
P120,P144
Expand the low-pressure side on-site piping
(ID ø28.58 mm [1-1/8 in]) and connect to the
refrigerant service valve piping.
WT05788X01_GB_cs2j.indd 13
12/10/2009 11:24:56 AM