10. Additional refrigerant charge

At the time of shipping, the outdoor unit is charged with refrigerant.
This charge does not include the amount needed for extended piping and 
additional charging of each refrigerant line will be required on-site.  In order that 
future servicing may be properly provided, always keep a record of the size and 
length of each refrigerant line and the amount of additional charge by writing it in 
the space provided on the outdoor unit.

10.1. Calculation of additional refrigerant 

charge

Calculate the amount of additional charge based on the length of the piping 

extension and the size of the refrigerant line.

Use the table below as a guide for calculating the amount of additional 

charging and then charge the system accordingly.

If the calculation results in a fraction of less than 0.1 kg [4 oz], round up 

to the next 0.1 kg [4 oz].  For example, if the result of the calculation was 
27.73 kg [979 oz], round the result up to 27.8 kg [983 oz].

<Additional charge>

Additional refrigerant

charge

=

High-pressure

pipe size

Total length of 

ø28.58 mm [1-1/8 in]

+

High-pressure

pipe size

Total length of 

ø22.2 mm [7/8 in]

+

High-pressure

pipe size

Total length of 

ø19.05 mm [3/4 in]

+

High-pressure

pipe size

Total length of 

ø15.88 mm [5/8 in]

(kg) [oz]

(m) × 0.36 (kg/m)

(ft) × 3.88 (oz/ft)

(m) × 0.23 (kg/m)

(ft) × 2.48 (oz/ft)

(m) × 0.16 (kg/m)

(ft) × 1.73 (oz/ft)

(m) × 0.11 (kg/m)

(ft) × 1.19 (oz/ft)

+

Liquid Piping Size

Total length of 

ø15.88 mm [5/8 in]

+

Liquid Piping Size

Total length of 

ø12.7 mm [1/2 in]

+

Liquid Piping Size

Total length of 

ø9.52 mm [3/8 in]

+

Liquid Piping Size

Total length of 

ø6.35 mm [1/4 in]

(m) × 0.2 (kg/m)
(ft) × 2.16 (oz/ft)

(m) × 0.12 (kg/m)

(ft) × 1.30 (oz/ft)

(m) × 0.06 (kg/m)

(ft) × 0.65 (oz/ft)

(m) × 0.024 (kg/m)

(ft) × 0.26 (oz/ft)

+

Total Outdoor 

Unit

Model Name

BC controller 

(Standard/Main)

Per Unit

+

BC controller

(Main) HA-Type

+

BC controller

(Sub) Total Units

BC controller

(Sub) Per Unit

+

Total Capacity of

Connected Indoor 

Units

Per Indoor Unit

P72

3.0 kg [106 oz]

2.0 kg

1

1.0 kg [36 oz]

 

Models 

 ~ 27

 

2.0 kg [71 oz]

P96

4.5 kg [160 oz]

2

2.0 kg [71 oz]

 

Models  28 ~ 54

 

2.5 kg [89 oz]

P120

  Models  55 ~ 126

 

3.0 kg [106 oz]

P144

  Models 127 ~ 144

 

3.5 kg [124 oz]

P168

7.5 kg [265 oz]

  Models 145 ~ 180

 

4.5 kg [159 oz]

P192

9.0 kg [318 oz]

  Models 181 ~ 234

 

5.0 kg [177 oz]

P216

  Models 235 ~ 273

 

6.0 kg [212 oz]

P240

  Models 274 ~ 307

 

8.0 kg [283 oz]

P264

  Models 308 ~ 342

 

9.0 kg [318 oz]

P288

  Models 343 ~ 411

 

10.0 kg [353 oz]

 

Models 412 ~ 

 

12.0 kg [424 oz]

<C>  Pipe connection example

The distributor on the low-pressure side must be placed in the outdoor unit that has a larger capacity index of the two, regardless of the relative positions of the 
outdoor units or their addresses.

(If outdoor units that have the same capacity are used in combination, the distributor can be placed in either outdoor unit.)

If the distributor is placed in the outdoor unit that has a smaller capacity, refrigerant will not be properly distributed and compressor failure may result.

F

Twinning pipe (low-pressure side)

G

Twinning pipe (high-pressure side)

H

On-site piping (low-pressure connecting pipe: between outdoor units)

I

On-site piping (low-pressure main pipe: to BC controller)

J

On-site piping (high-pressure main pipe: to BC controller)

K

Straight run of pipe that is 500 mm [19-11/16 in] or more

F

H

G

J

K

I

Maximum refrigerant charge

There is a limit to the amount of refrigerant that can be charged into a unit. Regardless of the amount yielded by the formula above, observe the maximum refrigerant 
charge in the table below.

Total index of the
outdoor units

P72

P96

P120

P144

P168

P192

P216

P240

P264

P288

Maximum *1 
refrigerant charge

39.0kg

[86LBS]

47.3kg

[104LBS 3oz]

52.8kg

[116LBS 5oz]

58.5kg

[129LBS]

73.0kg

[161LBS]

86.3kg

[190LBS 3oz]

104.6kg

[230LBS 6oz]

107.1kg

[236LBS 2oz]

115.1kg

[253LBS 8oz]

115.1kg

[253LBS 8oz]

*1 Maximum refrigerant charge: the amount of factory-charged refrigerant and the amount of refrigerant to be added on site

WT05788X01_GB_cs2j.indd 11

12/10/2009 11:24:54 AM

Содержание PURY-P120TJMU-A

Страница 1: ... F INSTALLATION MANUAL For safe and correct use please read this installation manual thoroughly before installing the air conditioner unit MANUEL D INSTALLATION Veuillez lire le manuel d installation en entier avant d installer ce climatiseur pour éviter tout accident et vous assurer d une utilisation correcte ...

Страница 2: ...r conditioner to another site do not charge it with a refrigerant different from the refrigerant specified on the unit If a different refrigerant or air is mixed with the original refrigerant the refrigerant cycle may malfunction and the unit may be damaged If the air conditioner is installed in a small room measures must be taken to prevent the refrigerant concentration from exceeding the safety l...

Страница 3: ...ion indoors and keep both ends of the piping sealed until just before brazing Store elbows and other joints in a plastic bag If dust dirt or water enters the refrigerant cycle deterioration of the oil and compressor failure may result Apply only a small amount of ester oil ether oil or alkyl benzene to flare connections for indoor unit Infiltration of a large amount of mineral oil may cause the refr...

Страница 4: ...S PURY P288TSJMU A BS Sound level 60Hz 58dB A 58dB A 60dB A 61dB A 61dB A 61dB A 62 5dB A 63dB A 63 5dB A 64dB A External static pressure 0 Pa 2 Indoor units Total capacity 50 150 1 Model 06 96 Quantity 1 18 1 24 1 30 1 36 1 42 1 48 2 50 2 50 2 50 2 50 Operation temperature Standard type Cooling mode í5 CDB 46 CDB 23 FDB 115 FDB Heating mode í20 CWB 15 5 CWB í4 FWB 60 FWB Outside air intake type C...

Страница 5: ...riction B Side view Unit mm in A B 500 19 11 16 H h h H When the height of the walls on the front back or on the sides H exceeds the wall height limit as defined here add the height that exceeds the height limit h to the figures that are marked with an asterisk Wall height limit Front Up to the unit height Back Up to 500 mm 19 11 16 in from the unit bottom Side Up to the unit height 4 If there are o...

Страница 6: ...a space of 1000mm or more as inlet space passage space for each A units PURY P72 96 A six PURY P120 144 A three 7 Transporting the unit Use suspension ropes that will withstand the weight of the unit When moving the unit use a 4 point suspension and avoid giving impacts to the unit Do not use 2 point suspension Place protective pads on the unit where it comes in contact with the ropes to protect t...

Страница 7: ...eas in environments subject to strong winds or rain install air inlet and outlet ducting as shown in Fig 8 1 2 Note 1 Height of frame base for snow damage prevention H shall be twice as high as expected snowfall Width of frame base shall not exceed that of the unit The frame base shall be made of angle steel etc and designed so that snow and wind slip through the structure If frame base is too wid...

Страница 8: ...al for piping Failure to do so may damage the compressor Be sure to perform the non oxidation brazing with a nitrogen purge Do not use any commercially available anti oxidizing agent since it may cause pipe corrosion and degrading of the refrigerant oil Please contact Mitsubishi Electric for more details Refer to item 10 2 for details of the piping connection and valve operation 0 Always insulate ...

Страница 9: ...4 B A a b c d A B C E F E E Outdoor model P168 P288 a C b B c d f D E A e A1 unit1 unit2 A2 A G C E E E D E D E F A Note1 A Outdoor unit B BC controller standard C BC controller main D BC controller sub E Indoor unit 06 54 F Indoor unit 72 96 G Outdoor Twinning Kit Note1 F B C D g i j h ...

Страница 10: ...7 144 ø22 2 7 8 ø28 58 1 1 8 ø12 7 1 2 145 168 ø22 2 7 8 ø28 58 1 1 8 ø15 88 5 8 a b c d e f Unit mm in Model number Liquid pipe Gas pipe 06 08 12 15 18 ø6 35 1 4 ø12 7 1 2 24 27 30 36 48 54 ø9 52 3 8 ø15 88 5 8 72 ø9 52 3 8 ø19 05 3 4 96 ø9 52 3 8 ø22 2 7 8 g h i j Unit mm in Model number Liquid pipe Gas pipe g h i j 36 ø9 52 3 8 ø9 52 3 8 ø15 88 5 8 ø15 88 5 8 48 ø9 52 3 8 ø9 52 3 8 ø15 88 5 8 ø...

Страница 11: ...nits BC controller Sub Per Unit Total Capacity of Connected Indoor Units Per Indoor Unit P72 3 0 kg 106 oz 2 0 kg 1 1 0 kg 36 oz Models 27 2 0 kg 71 oz P96 4 5 kg 160 oz 2 2 0 kg 71 oz Models 28 54 2 5 kg 89 oz P120 Models 55 126 3 0 kg 106 oz P144 Models 127 144 3 5 kg 124 oz P168 7 5 kg 265 oz Models 145 180 4 5 kg 159 oz P192 9 0 kg 318 oz Models 181 234 5 0 kg 177 oz P216 Models 235 273 6 0 kg...

Страница 12: ...essure piping dimensions before connecting the refrigerant pipe Refer to item 9 2 Refrigerant piping system for piping dimensions Make sure that the refrigerant pipe is not touching other refrigerants pipes unit panels or base plates Be sure to use non oxidative brazing when connecting pipes Be careful not to burn the wiring and plate when brazing 10 2 Precautions concerning piping connection and ...

Страница 13: ...ded in the kit 2 Connection pipe is not used when the Twinning Kit is attached 3 Use a pipe cutter to sever Front pipe routing P72 Expand the high pressure side on site piping ID ø15 88 mm 5 8 in and connect to the refrigerant service valve piping P96 P120 Use the included connecting pipe 2 and elbow 3 to connect P144 Use the included connecting pipe 1 to connect P72 Expand the low pressure side o...

Страница 14: ...until refrigerant charging to the pipes to be added on site has been completed Opening the valve before charging the refrigerant may cause damage to the unit Do not use a leak detection additive Fig 10 2 3 A B A Example of closure materials field supplied B Fill the gap at the site When not attaching a low pressure twinning pipe Make sure to seal off the space around areas where the wires and refri...

Страница 15: ...osed and evacuate both the connection piping and the indoor unit from the service port provided on the valve of the outdoor unit using a vacuum pump Always evacuate from the service port of both the high pressure pipe and the low pressure pipe After the vacuum reaches 650 Pa abs 0 0943 psi 5 Torr continue evacuation for at least one hour or more Then stop the vacuum pump and leave it for 1 hour En...

Страница 16: ...lating materials themselves When insulation work is insufficient there is a possibility of condensation drip etc Pay special attention to insulation work in the ceiling plenum Fig 10 4 1 C A B D E A Steel wire B Piping C Oily mastic asphalt or asphalt D Heat insulation material A E Outer covering B Heat insulation material A Glass fiber Steel wire Adhesive Heat resistant polyethylene foam Adhesive t...

Страница 17: ...he centralized control is being conducted during the power supply shut off daisy chain TB7 on the OC and OS In the case that the outdoor unit whose power supply connector CN41 on the control board has been replaced with CN40 is out of order or the power is shut off centralized control will not be conducted even when TB7 is daisy chained 2 OC and OS of the outdoor units in the same refrigerant syst...

Страница 18: ...oller L3 L 6 L4 L 5 A B A B A B A B BC M1M2S 52 BS M1M2S 55 BC M1M2S 54 TB02 TB02 TB02 1 1 1 4 4 4 2 2 2 3 3 3 OC CN41 CN41 CN40 A Change the jumper connector from CN41 to CN40 1 B SW2 1 ON 2 Address C Keep the jumper connector on CN41 B SW2 1 ON 2 1 When the power supply unit is not connected to the transmission line for centralized control disconnect the male power supply connector CN41 from ONE...

Страница 19: ...ler 1 3Indoor units connected to BC sub controller 2 Set the indoor unit addresses so that all the addresses of 1 are smaller than those of 2 and that all the addresses of 2 are smaller than those of 3 Indoor unit Sub 01 to 50 Use an address other than that of the IC Main from among the units within the same group of indoor units This must be in sequence with the IC Main Outdoor Unit OC OS 51 to 1...

Страница 20: ... or less 13 19 PURY P96YJMU BS 3 3 12 3 3 12 20 20 20 20A 30mA or 100mA 0 1sec or less 16 26 PURY P120YJMU BS 5 3 10 5 3 10 25 25 25 25A 30mA or 100mA 0 1sec or less 23 35 PURY P144YJMU BS 5 3 10 5 3 10 30 30 30 30A 30mA or 100mA 0 1sec or less 27 43 PURY P168YSJMU BS PURY P96YJMU BS 3 3 12 3 3 12 20 20 20 20A 30mA or 100mA 0 1sec or less 16 26 PURY P72YJMU BS 2 1 14 2 1 14 15 15 15 15A 30mA or 10...

Страница 21: ...that is not performing the heating operation from being liquefied This does not imply a problem 13 Rating plate information Model PURY P72TJMU A BS PURY P96TJMU A BS PURY P120TJMU A BS PURY P144TJMU A BS Unit combination Refrigerant R410A 10 5kg 23LBS 2oz 11 8kg 26LBS 1oz 11 8kg 26LBS 1oz 11 8kg 26LBS 1oz Allowable pressure Ps HP 4 15MPa 601psi LP 2 21MPa 320psi Net weight 235kg 519LBS 265kg 585LBS...

Страница 22: ...atiseur vers un autre site ne le chargez pas avec un frigorigène différent de celui qui est spécifié sur l unité Si un autre frigorigène ou de l air est mélangé au frigorigène original le cycle frigorifique peut mal fonctionner et l unité peut être endommagée Si le climatiseur est installé dans une petite pièce des mesures doivent être prises pour empêcher la concentration en frigorigène de dépasser...

Страница 23: ...oudes et autres raccords dans un sac en plastique Si de la poussière des saletés ou de l eau pénètrent dans le cycle du frigorigène il peut en résulter une détérioration de l huile et une défaillance du compresseur Appliquez seulement une petite quantité d huile d ester huile d éther ou alkylbenzène aux connexions évasées pour l unité d intérieur L infiltration d une grande quantité d huile minéral...

Страница 24: ...62 5dB A 63dB A 63 5dB A 64dB A Pression statique externe 0 Pa 2 Unités d intérieur Capacité totale 50 150 1 Modèle 06 96 Quantité 1 18 1 24 1 30 1 36 1 42 1 48 2 50 2 50 2 50 2 50 Température de fonctionnement Type standard Mode de refroidissement í5 CDB 46 CDB 23 FDB 115 FDB Mode de chauffage í20 CWB 15 5 CWB í4 FWB 60 FWB Type de prise d air frais Mode de refroidissement 21 CDB 15 5 CWB 46 CDB ...

Страница 25: ...é Unité mm in A B 500 19 11 16 H h h H Quand la hauteur des murs à l avant au dos ou sur les côtés H dépasse la limite de hauteur de mur définie ici ajoutez la hauteur qui excède la hauteur limite h aux chiffres qui sont identifiés par un astérisque Hauteur limite du mur Avant Jusqu à la hauteur de l appareil Dos Jusqu à 500 mm 19 11 16 in du fond de l appareil Côté Jusqu à la hauteur de l appareil ...

Страница 26: ...t de circulation d air pour chaque A unités PURY P72 96 A six PURY P120 144 A trois Fig 7 0 1 1 P72 3 P120 P144 Unité m ft 8 26 8 26 40 8 26 8 26 40 7 Transport de l unité Utilisez des cordes de suspension qui résistent au poids de l appareil Pour déménager l unité utilisez une suspension en 4 points et évitez de donner des chocs à l unité n utilisez pas de suspension en 2 points Placez des garnit...

Страница 27: ...itations et des vents violents installez l entrée d air et la conduite de sortie comme indiqué sur la Fig 8 1 2 Remarque 1 La hauteur du support du bâti utilisé en prévention des dommages provoqués par la neige H doit être deux fois plus haute que le niveau de la neige attendu La largeur du support du bâti ne doit pas excéder celle de l unité Le support du bâti doit être fabriqué en acier cornier ...

Страница 28: ... Le non respect de cette instruction peut endommager le compresseur Soyez sûr d exécuter le brasage sans oxydation avec une purge d azote N utilisez aucun agent d antioxydation disponible dans le commerce puisqu il peut causer la corrosion des tubes et dégrader l huile du frigorigène Veuillez contacter Mitsubishi Electric pour plus de détails Reportez vous à 10 2 pour des détails sur la connexion ...

Страница 29: ...B C E F E E Modèle extérieur P168 P288 a C b B c d f D E A e A1 unité1 unité2 A2 A G C E E E D E D E F A Remarque1 A Unité extérieure B Contrôleur BC standard C Contrôleur BC principal D Contrôleur BC secondaire E Appareil intérieur 06 54 F Appareil intérieur 72 96 G Kit de jumelage extérieur Remarque1 F B C D g i j h ...

Страница 30: ... 88 5 8 a b c d e f Unité mm in Numéro de modèle Tube de fluide Tube de gaz 06 08 12 15 18 ø6 35 1 4 ø12 7 1 2 24 27 30 36 48 54 ø9 52 3 8 ø15 88 5 8 72 ø9 52 3 8 ø19 05 3 4 96 ø9 52 3 8 ø22 2 7 8 g h i j Unité mm in Numéro de modèle Tube de fluide Tube de gaz g h i j 36 ø9 52 3 8 ø9 52 3 8 ø15 88 5 8 ø15 88 5 8 48 ø9 52 3 8 ø9 52 3 8 ø15 88 5 8 ø15 88 5 8 54 ø9 52 3 8 ø9 52 3 8 ø15 88 5 8 ø15 88 5 ...

Страница 31: ...BC secondaire Contrôleur BC secondaire par unité Capacité totale des unités intérieures connectées Par appareil intérieur P72 3 0 kg 106 oz 2 0 kg 1 1 0 kg 36 oz Modèls 27 2 0 kg 71 oz P96 4 5 kg 160 oz 2 2 0 kg 71 oz Modèls 28 54 2 5 kg 89 oz P120 Modèls 55 126 3 0 kg 106 oz P144 Modèls 127 144 3 5 kg 124 oz P168 7 5 kg 265 oz Modèls 145 180 4 5 kg 159 oz P192 9 0 kg 318 oz Modèls 181 234 5 0 kg ...

Страница 32: ...z les dimensions de la tuyauterie haute pression basse pression avant de connecter le tube de frigorigène Reportez vous au système de tuyauterie du frigorigène en 9 2 pour des dimensions de la tuyauterie Assurez vous que le tube de frigorigène ne touche pas d autres tubes de frigorigène des panneaux de l unité ou des plaques de base Soyez sûr d utiliser un brasage non oxydant pour la connexion des...

Страница 33: ...ue le kit de jumelage est fixé 3 Utilisez un coupe tube pour la découpe Routage du tube avant P72 Étendez le côté haute pression de la tuyauterie sur site Diam int ø15 88 mm 5 8 in et reliez à la tuyauterie de la valve de frigorigène P96 P120 Utilisez le tube 2 et le coude 3 de connexion inclus pour faire le raccord P144 Utilisez le tube 1 de connexion inclus pour faire le raccord P72 Étendez le cô...

Страница 34: ...ment de frigorigène supplémentaire dans les tubes ait été complété L ouverture de la valve avant de charger le frigorigène peut endommager l unité N utilisez pas d additif de détection de fuite Fig 10 2 3 A B A Exemple de matériaux de scellement fourni sur le terrain B Remplissez l espace vide sur le site Si aucun tube de jumelage basse pression n est fixé Veillez à sceller l espace autour des zone...

Страница 35: ... la tuyauterie de connexion et l unité intérieure depuis le port de service fourni sur la valve de l unité extérieure à l aide d une pompe à vide Évacuez toujours depuis le port de service des tubes haute et basse pression Après que le vide ait atteint 650 Pa abs 0 0943 psi 5 Torr continuez l évacuation pendant au moins une heure Arrêtez ensuite la pompe à vide et laissez la pendant une heure Véri...

Страница 36: ...isolant et entre les matériaux isolants eux mêmes Quand l isolation est insuffisante il peut y avoir condensation etc Faites particulièrement attention à l isolation dans le plénum du plafond Fig 10 4 1 C A B D E A Fil d acier B Tuyauterie C Mastic huileux asphaltique ou asphalte D Matériel A d isolation thermique E Couverture externe B Matériel A d isolation thermique Fibre de verre fil d acier Adh...

Страница 37: ... Si l OC est en panne ou si la commande centralisée est exploitée pendant l interruption d alimentation connectez en série le TB7 sur l OC et l OS au cas où l unité extérieure dont le connecteur d alimentation CN41 sur le panneau de commande a été remplacé par un CN40 est en panne ou l alimentation est coupée la commande centralisée n est pas exploitable même lorsque le TB7 est connecté en série 2...

Страница 38: ... ME 155 M1M2 M1M2 S TB7 TB3 CN41 53 OC A B S Contrôleur de système L3 L 6 L4 L 5 A B A B A B A B BC M1M2S 52 BS M1M2S 55 BC M1M2S 54 TB02 TB02 TB02 1 1 1 4 4 4 2 2 2 3 3 3 OC CN41 CN41 CN40 A Changez le cavalier de CN41 à CN40 1 B SW2 1 ON marche 2 Adresse C Laissez le cavalier sur CN41 B SW2 1 ON marche 2 1 Quand l alimentation n est pas connectée à la ligne de transmission pour la commande centr...

Страница 39: ...reliées au contrôleur BC secondaire 2 Réglez les adresses des unités intérieures de sorte que toutes les adresses de 1 soient plus petites que les adresses de 2 et que les adresses de 2 soient plus petites que les adresses de 3 Appareil intérieur Secondaire 01 à 50 Utilisez une adresse autre que celle de l IC principal parmi les unités d un même groupe d appareils intérieurs Celle ci doit se trouv...

Страница 40: ...16 26 PURY P120YJMU BS 5 3 10 5 3 10 25 25 25 25A 30mA ou 100mA 0 1s ou moins 23 35 PURY P144YJMU BS 5 3 10 5 3 10 30 30 30 30A 30mA ou 100mA 0 1s ou moins 27 43 PURY P168YSJMU BS PURY P96YJMU BS 3 3 12 3 3 12 20 20 20 20A 30mA ou 100mA 0 1s ou moins 16 26 PURY P72YJMU BS 2 1 14 2 1 14 15 15 15 15A 30mA ou 100mA 0 1s ou moins 13 19 PURY P192YSJMU BS PURY P96YJMU BS 3 3 12 3 3 12 20 20 20 20A 30mA ...

Страница 41: ...stable du frigorigène émet un bruit Ceci est provisoire et n indique pas un problème De l air chaud provient d une unité intérieure qui n exécute pas de chauffage Affichage normal Le LEV est légèrement ouvert pour empêcher le frigorigène de l unité intérieure n exécutant pas le chauffage de se liquéfier Ceci n indique pas un problème 13 Informations de la plaque signalétique Modèle PURY P72TJMU A BS...

Страница 42: ...I CHIYODA KU TOKYO 100 8310 JAPAN Please be sure to put the contact address telephone number on this manual before handing it to the customer This product is designed and intended for use in the residential commercial and light industrial environment ...

Отзывы: