(2) System that requires more than 16 BC controller ports or with multiple BC controllers <Outdoor unit P144 model or
below.>
Unit: m [ft]
Operation
Pipe sections
Allowable length of pipes
Length
Total pipe length
A+B+C+D+E+a+b+c+d+e+f
Refer to the restrictions on the total pip-
ing length in the graphon the next page.
Total pipe length from the out-
door unit to the farthest indoor
unit
A+C+E+f
165 [541] or less
(Equivalent length 190 [623] or less)
Between outdoor unit and BC
controller
A
110 [360] or less
Between BC controller and in-
door unit
B+d or C+D+e
or C+E+f
40 [131] or less
*1
*1. When the overall pipe length between the BC controller and the farthest indoor unit exceeds 40m [131ft], observe the
restrictions in the figure titled "Restrictions on pipe length" below. (Except the P96 models)
Height
differ-
ence
Between indoor
and outdoor
units
Outdoor unit
above in-
door unit
H
50 [164] or less
Outdoor unit
below in-
door unit
H'
40 [131] or less
Between indoor unit and BC
controller
h1
15 [49](10[32]) or less
*2
*2. When the capacity of the connected indoor units is P72 or above, use the figures in the parentheses as a reference.
Between indoor units
h2
15 [49](10[32]) or less
*2
Between the BC controller
(main or sub) and the sub BC
controller
h3
15 [49] or less
Branch joint
(CMY-Y202-G2)
(CMY-Y102L-G2)
(CMY-Y102S-G2)
Branch joint
(CMY-Y102S-G2)
a
C
b
H
H'
h1
h1
B
c
d
f
h3
D
E
A
e
h1
h2
Outdoor unit
BC controller (main)
BC controller (sub)
BC controller (sub)
Indoor
Indoor
Indoor
Indoor
Indoor
Indoor
Reducer (P06 - P18 models)
(Supplied with the BC Controller)
(P06 - P54 models)
(P72 - P96 models)
Maximum of 3 units per port
Total capacity of P54 or below
Junction pipe
(CMY-R160-J)
Содержание PURY-P120TJMU-A
Страница 1: ......
Страница 11: ... 2 ...
Страница 25: ... 16 ...
Страница 36: ... II Restrictions 27 HWE0913A GB ...
Страница 50: ... II Restrictions 41 41 HWE0913A GB ...
Страница 67: ... 58 II Restrictions GB HWE0913A ...
Страница 69: ... 60 ...
Страница 94: ... III Outdoor Unit Components 85 HWE0913A GB 2 RELAY BOARD RELAY 4 board 3 RELAY BOARD RELAY 10 board ...
Страница 95: ... 86 III Outdoor Unit Components GB HWE0913A ...
Страница 97: ... 88 ...
Страница 105: ... 96 IV Remote Controller GB HWE0913A ...
Страница 107: ... 98 ...
Страница 124: ... 115 HWE0913A GB VI Refrigerant Circuit 1 Refrigerant Circuit Diagram 117 2 Principal Parts and Functions 126 ...
Страница 125: ... 116 ...
Страница 145: ... 136 ...
Страница 175: ... 166 VII Control GB HWE0913A ...
Страница 177: ... 168 ...
Страница 203: ... 194 ...
Страница 363: ... 354 IX Troubleshooting GB HWE0913A ...
Страница 364: ... 355 HWE0913A GB X LED Monitor Display on the Outdoor Unit Board 1 How to Read the LED on the Service Monitor 357 ...
Страница 365: ... 356 ...
Страница 411: ......