VIII
Test Run Mode ]
- 174 -
HWE0913A
GB
[5] Refrigerant Amount Adjust Mode
1. Procedures
Follow the procedures below to add or extract refrigerant as necessary depending on the operation mode.
When the function switch (SW4-3) on the main board on the outdoor unit (OC only) is turned to ON, the unit goes into the
refrigerant amount adjust mode, and the following sequence is followed.
SW4-3 on the OS is invalid, and the unit will not go into the refrigerant amount adjust mode.
Operation
When the unit is in the refrigerant amount adjust mode, the LEV on the indoor unit does not open as fully as it nor-
mally does during cooling operation to secure subcooling.
1) Adjust the refrigerant amount based on the values of TH4, SC11, SC16, and Tc, following the flowchart below. Check the TH4,
SC11, SC16, and Tc values on the OC, OS by following the flowchart. The TH4, SC11, SC16, and Tc values can be displayed
by setting the self-diagnosis switch (SW1) on the main board on the OC, OS.
2) There may be cases when the refrigerant amount may seem adequate for a short while after starting the unit in the refrigerant
amount adjust mode but turn out to be inadequate later on (when the refrigerant system stabilizes).
When the amount of refrigerant is truly adequate.
Subcool (SC11 and SC16) of the BC controller is 5°C [9°F] or above and SH on the indoor unit is between 5 and 15°C [9 and
27°F].
The refrigerant amount may seem adequate at the moment, but may turn out to be inadequate later on.
Subcool (SC11 and SC16) of the BC controller is 5°C [9°F] or less and SH on the indoor unit is 5°C [9°F] or less.
Wait until the Subcool (SC11 and SC16) of the BC controller reaches 5°C [9°F] or above and the SH of the indoor unit is be-
tween 5 and 15°C [9 and 27°F] to determine that the refrigerant amount is adequate.
SC11: Subcool of liquid refrigerant at BC controller inlet; SC16: Subcool of liquid refrigerant at BC controller outlet
3) High pressure must be at least 2.0MPa [290psi] to enable a proper adjustment of refrigerant amount to be made.
4) Refrigerant amount adjust mode automatically ends 90 minutes after beginning. When this happens, by turning off the SW4-
3 and turning them back on, the unit will go back into the refrigerant amount adjust mode.
Self-diagnosis swithes on TH4
Self-diagnosis swithes on SC16
Use these switches to check the TH4, SC11, and SC16.
Self-diagnosis swithes on SC11
ON
ON
1 2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10
1 2 3 4 5 6 7 8 9 10
ON
Содержание PURY-P120TJMU-A
Страница 1: ......
Страница 11: ... 2 ...
Страница 25: ... 16 ...
Страница 36: ... II Restrictions 27 HWE0913A GB ...
Страница 50: ... II Restrictions 41 41 HWE0913A GB ...
Страница 67: ... 58 II Restrictions GB HWE0913A ...
Страница 69: ... 60 ...
Страница 94: ... III Outdoor Unit Components 85 HWE0913A GB 2 RELAY BOARD RELAY 4 board 3 RELAY BOARD RELAY 10 board ...
Страница 95: ... 86 III Outdoor Unit Components GB HWE0913A ...
Страница 97: ... 88 ...
Страница 105: ... 96 IV Remote Controller GB HWE0913A ...
Страница 107: ... 98 ...
Страница 124: ... 115 HWE0913A GB VI Refrigerant Circuit 1 Refrigerant Circuit Diagram 117 2 Principal Parts and Functions 126 ...
Страница 125: ... 116 ...
Страница 145: ... 136 ...
Страница 175: ... 166 VII Control GB HWE0913A ...
Страница 177: ... 168 ...
Страница 203: ... 194 ...
Страница 363: ... 354 IX Troubleshooting GB HWE0913A ...
Страница 364: ... 355 HWE0913A GB X LED Monitor Display on the Outdoor Unit Board 1 How to Read the LED on the Service Monitor 357 ...
Страница 365: ... 356 ...
Страница 411: ......