IX
Troubleshooting ]
- 273 -
HWE0913A
GB
In the case of MA remote controller
2. Phenomena
When the remote controller operation SW is turned on, the operation status briefly appears on the display, then it goes off,
and the display lights out immediately, and the unit stops.
(1) Cause
1) The power for the M-NET transmission line is not supplied from the outdoor unit.
2) Short circuit of the transmission line.
3) Incorrect wiring of the M-NETtransmission line on the outdoorunit.
Disconnected wire for the MA remote controller or disconnected line to the terminal block.
The indoor transmission line is connected incorrectly to the transmission terminal block for centralized controller (TB7).
The male power supply connectors on the multiple outdoor units are connected to the female power supply switch connector
(CN40).
In the system to which the power supply unit for transmission lines is connected, the male power supply connector is connect-
ed to the female power supply switch connector (CN40) on the outdoor unit.
4) Disconnected M-NET transmission line on the indoor unit side.
5) Disconnected wire between the terminal block for M-NET line (TB5) of the indoor unit and the indoor unit board (CN2M) or
disconnected connector.
(2) Check method and remedy
1)
When 2) and 3) above apply, check code 7102 will be displayed on the self-diagnosis LED.
Refer to section IX [4] -8- (2) Troubleshooting transmission power circuit of outdoor unit for how to check the first item in the
flowchart above.(page 329)(page 332)
YES
YES
YES
YES
NO
NO
NO
NO
Same symptom for all units in a
system with one outdoor unit?
Check the
self-diagnosis LED
Check 1).
Check for
2 and 3.
Check 4.
Measure voltages of the
terminal block for transmission
line (TB5) on the indoor unit.
17 - 30V?
Check 5.
Error found?
Indoor unit board or
MA remote controller failure
Correct
the error.
Correct the error.
Is the error code 7102
displayed?
Содержание PURY-P120TJMU-A
Страница 1: ......
Страница 11: ... 2 ...
Страница 25: ... 16 ...
Страница 36: ... II Restrictions 27 HWE0913A GB ...
Страница 50: ... II Restrictions 41 41 HWE0913A GB ...
Страница 67: ... 58 II Restrictions GB HWE0913A ...
Страница 69: ... 60 ...
Страница 94: ... III Outdoor Unit Components 85 HWE0913A GB 2 RELAY BOARD RELAY 4 board 3 RELAY BOARD RELAY 10 board ...
Страница 95: ... 86 III Outdoor Unit Components GB HWE0913A ...
Страница 97: ... 88 ...
Страница 105: ... 96 IV Remote Controller GB HWE0913A ...
Страница 107: ... 98 ...
Страница 124: ... 115 HWE0913A GB VI Refrigerant Circuit 1 Refrigerant Circuit Diagram 117 2 Principal Parts and Functions 126 ...
Страница 125: ... 116 ...
Страница 145: ... 136 ...
Страница 175: ... 166 VII Control GB HWE0913A ...
Страница 177: ... 168 ...
Страница 203: ... 194 ...
Страница 363: ... 354 IX Troubleshooting GB HWE0913A ...
Страница 364: ... 355 HWE0913A GB X LED Monitor Display on the Outdoor Unit Board 1 How to Read the LED on the Service Monitor 357 ...
Страница 365: ... 356 ...
Страница 411: ......