GB
GB-49
WT07282X01
10-5. Wiring connections in the control box
Connections must be made securely and without tension on the terminals.
-Improperly connected cables may break, overheat, or cause smoke or fire.
10-5-1. Threading power cable through the knockout hole
・
Punch out the knockout holes at the bottom of the front panel with a hammer. Use the appropriate knockout hole
according to the size of the power cable, referring to the table below.
Ⓐ
Ⓑ
Ⓒ
Power cable size (mm
2
)
Knockout hole to be used
2, 3.5, 5.5
Knockout hole 2
8, 14
Knockout hole 4
21, 26, 33
Knockout hole 3
84, 67, 53
Knockout hole 5
Ⓐ
Cable strap
Ⓑ
Power cable
Ⓒ
Transmission cable
・
If there are any gaps around the power cable, please be sure to fill these in with a suitable material.
・
When putting the power cable through the knockout hole without using a conduit tube, deburr the hole and protect
the power cable with protective tape.
・
Use a conduit tube to narrow down the opening if there is a possibility of small animals entering the unit.
・
When taking the conduit tube out from the bottom part of the unit, caulk around the tube opening to prevent water
infiltration.
Содержание PURY-(E)P-YLM-A (-BS)
Страница 2: ......
Страница 62: ...GB 60 WT07282X01 ...