GB-10
WT07282X01
(2) EP models
Model
PURY-EP200YLM-A*
3
PURY-EP250YLM-A*
3
Sound level (50/60 Hz)
59 dB <A>
60 dB <A>
External static pressure
0 Pa*
2
Indoor unit
Total capacity
50% to 150%*
1
Model
15 to 250
Quantity
R2 system
1 to 20
1 to 25
Hybrid City
Multi system
1 to 20
1 to 25
Temperature
range
(Cooling)
Indoor
W.B.
+15.0°C to +24.0°C (+59.0°F to +75.0°F)
Outdoor
D.B.
-5.0°C to +46.0°C (+23.0°F to +115.0°F)
Temperature
range
(Heating)
Indoor
D.B.
+15.0°C to +27.0°C (+59.0°F to +81.0°F)
Outdoor
W.B.
-20.0°C to +15.5°C (-4.0°F to +60.0°F)
Model
PURY-EP300YLM-A
PURY-EP350YLM-A
PURY-EP400YLM-A
PURY-EP450YLM-A
PURY-EP500YLM-A
Sound level (50/60 Hz)
62.5 dB <A>
62.5 dB <A>
62.5 dB <A>
62.5 dB <A>
63.5 dB <A>
External static pressure
0 Pa*
2
Indoor unit
Total capacity
50% to 150%*
1
Model
15 to 250
Quantity
1 to 30
1 to 35
1 to 40
1 to 45
1 to 50
Temperature range
(Cooling)
Indoor
W.B.
+15.0°C to +24.0°C (+59.0°F to +75.0°F)
Outdoor
D.B.
-5.0°C to +46.0°C (+23.0°F to +115.0°F)
Temperature range
(Heating)
Indoor
D.B.
+15.0°C to +27.0°C (+59.0°F to +81.0°F)
Outdoor
W.B.
-20.0°C to +15.5°C (-4.0°F to +60.0°F)
Model
PURY-EP500YSLM-A PURY-EP550YSLM-A PURY-EP600YSLM-A PURY-EP650YSLM-A PURY-EP700YSLM-A
Sound level (50/60 Hz)
63 dB <A>
64.5 dB <A>
65.5 dB <A>
65.5 dB <A>
65.5 dB <A>
External static pressure
0 Pa*
2
Indoor unit
Total capacity
50% to 150%*
1
Model
15 to 250
Quantity
1 to 50
2 to 50
2 to 50
2 to 50
2 to 50
Temperature range
(Cooling)
Indoor
W.B.
+15.0°C to +24.0°C (+59.0°F to +75.0°F)
Outdoor
D.B.
-5.0°C to +46.0°C (+23.0°F to +115.0°F)
Temperature range
(Heating)
Indoor
D.B.
+15.0°C to +27.0°C (+59.0°F to +81.0°F)
Outdoor
W.B.
-20.0°C to +15.5°C (-4.0°F to +60.0°F)
Model
PURY-EP750YSLM-A PURY-PE800YSLM-A PURY-EP850YSLM-A PURY-EP900YSLM-A
Sound level (50/60 Hz)
65.5 dB <A>
65.5 dB <A>
65.5 dB <A>
65.5 dB <A>
External static pressure
0 Pa*
2
Indoor unit
Total capacity
50% to 150%*
1
Model
15 to 250
Quantity
2 to 50
2 to 50
2 to 50
2 to 50
Temperature range
(Cooling)
Indoor
W.B.
+15.0°C to +24.0°C (+59.0°F to +75.0°F)
Outdoor
D.B.
-5.0°C to +46.0°C (+23.0°F to +115.0°F)
Temperature range
(Heating)
Indoor
D.B.
+15.0°C to +27.0°C (+59.0°F to +81.0°F)
Outdoor
W.B.
-20.0°C to +15.5°C (-4.0°F to +60.0°F)
*1 The maximum total capacity of indoor units operating simultaneously is 150%.
*2 To enable the high static pressure setting, set the dipswitch on the main board as follows.
SW6-4: ON
SW6-5: OFF (60 Pa) or ON (30 Pa)
*3 These models can be used for a Hybrid City Multi system.
Содержание PURY-(E)P-YLM-A (-BS)