OPERATING PROCEDURE
PHOTOS
9. Removing bypass valve coil (SV1) and bypass valve
(1) Remove the service panel. (See Photo 1)
(2) Remove the top panel. (See Photo 1)
(3) Remove 3 right side panel fixing screws (5 × 12) in the
rear of the unit and remove the right side panel.
(4) Remove the bypass valve coil fixing screw (M4 × 6).
(5) Remove the bypass valve coil by sliding the coil
upward.
(6) Disconnect the connector SV1 (gray) on the multi con-
troller circuit board in the electrical parts box.
(7) Remove the electrical parts box. (See Photo 5)
(8) Recover refrigerant.
(9) Remove the welded part of bypass valve.
Note 1: Recover refrigerant without spreading it in the air.
Note 2: The welded part can be removed easily by
removing the right side panel.
Note3: When installing the bypass valve, cover it with
a wet cloth to prevent it from heating (120°C or
more), then braze the pipes so that the inside
of pipes are not oxidized.
Photo 11
High pressure
sensor (63HS)
High pressure
switch (63H)
Low pressure
sensor (63LS)
Bypass valve
coil fixing screw
Electronic expansion
valve coil (LEV-B)
Bypass valve
coil (SV1)
Bypass valve
Electronic
expansion
valve
10. Removing the high pressure switch (63H) and high
pressure sensor (63HS)
(1) Remove the service panel. (See Photo 1)
(2) Remove the top panel. (See Photo 1)
(3) Remove 3 right side panel fixing screws (5
o
12) in the
rear of the unit and remove the right side panel.
(4) Pull out the lead wire of high pressure switch and high
pressure sensor.
(5) Remove the electrical parts box. (See Photo 5)
(6) Recover refrigerant.
(7) Remove the welded part of high pressure switch and
high pressure sensor.
Note 1: Recover refrigerant without spreading it in the air.
Note 2: The welded part can be removed easily by
removing the right side panel.
Note 3: When installing the high pressure switch and
high pressure sensor, cover them with a wet
cloth to prevent them from heating (100°C or
more), then braze the pipes so that the inside
of pipes are not oxidized.
Photo 12
Low pressure
sensor (63LS)
Electronic expansion
valve coil (LEV-A)
Electronic expan-
sion valve
11. Removing the low pressure sensor (63LS)
(1) Remove the service panel. (See Photo 1)
(2) Remove the top panel. (See Photo 1)
(3) Remove 3 right side panel fixing screws (5
o
12) in the
rear of the unit and remove the right side panel.
(4) Disconnect the connector 63LS (blue) on the multi con-
troller circuit board in the electrical parts box.
(5) Remove the electrical parts box. (See Photo 5)
(6) Recover refrigerant.
(7) Remove the welded part of low pressure sensor.
Note 1: Recover refrigerant without spreading it in the air.
Note 2: The welded part can be removed easily by
removing the right side panel.
Note 3: When installing the low pressure sensor,
cover it with a wet cloth to prevent it from
heating (100°C or more), then braze the pipes
so that the inside of pipes are not oxidized.
12. Removing electrical expansion valve (LEV-A, LEV-B)
(1) Remove the service panel. (See Photo 1)
(2) Remove the top panel. (See Photo 1)
(3) Remove 3 right side panel fixing screws (5
o
12) in the
rear of the unit and remove the right side panel.
(4) Remove the electrical expansion valve coil. (See Photo 11,12)
(5) Remove the electrical parts box. (See Photo 5)
(6) Recover refrigerant.
(7) Remove the welded part of electrical expansion valve.
154