128
No.
SW1 setting
Display mode
Display on the LED1, 2 (display data)
Notes
12345678
1
2
3
4
5
6
7
8
128
00000001
Actual frequency of abnormality delay
0–255 (Hz)
Display of actual frequency at time of abnormality delay
129
101
10001
Fan step number at time of abnormality delay
0–15
Display of fan step number at time of abnormality delay
131
11000001
IC1 LEV opening pulse
abnormality delay
0–2000 (pulse)
Delay of opening pulse of indoor LEV at time of abnormality delay
132
00100001
IC2 LEV opening pulse
abnormality delay
133
10100001
IC3 LEV opening pulse
abnormality delay
134
01
100001
IC4 LEV opening pulse
abnormality delay
135
11
100001
IC5 LEV opening pulse
abnormality delay
136
00010001
High pressure sensor data
at time of abnormality
delay kgf/cm2
−99.9–999.9
(kgf/cm²)
Display of data from High pressure sensor
,
all
ther
m
is
tor
s,
and
SC/
SH
at
time of abnormality delay
137
10010001
TH4 (Compressor) sensor data at time of abnormality delay
−99.9–999.9
(
:
)
138
01010001
TH6 (Suction pipe) sensor data at time of abnormality delay
139
11010001
TH3 (Outdoor liquid pipe) sensor data at time of
abnormality delay
140
001
10001
TH8 (Heat sink) sensor data at time of abnormality delay °C
141
101
10001
OC SC (cooling) at time of
abnormality delay
−99.9–999.9(
:
)
During heating: subcool (SC) During cooling: superheat (SH) (Fixed to "0" during cooling operation)
142
01
110001
IC1 SC/SH at time of abnormality delay
143
11
110001
IC2 SC/SH at time of abnormality delay
144
00001001
IC3 SC/SH at time of abnormality delay
145
10001001
IC4 SC/SH at time of abnormality delay
146
01001001
IC5 SC/SH at time of abnormality delay
147
11001001
IC9 SC/SH at time of abnormality delay
148
00100001
IC10 SC/SH at time of
abnormality delay
149
10101001
IC1
1 SC/SH at time of abnormality delay
150
01
101001
IC12 SC/SH at time of
abnormality delay
OCH632A