SW2 setting
Display detail
Explanation for display
Unit
Operation frequency when error occured.
0~225
0~225
(When it is 100Hz or more, hundreds digit, tens digit
and ones digit are displayed by turns.)
(Example) When 105Hz;
0.5 secs. 0.5secs. 2 secs.
1
ON
2 3 4 5 6
Hz
Fan step when error occured.
0~10
0~10
1
ON
2 3 4 5 6
Step
1
05
Ambient temperature (TH7) when error
occured.
-39~88
-39~88
(When the temperature is 0°C or less, “–” and
temperature are displayed by turns.)
(Example) When –15°C;
0.5 secs. 0.5secs. 2 secs.
Outdoor heatsink temperature (TH8)
when error occured.
-40~200
-40~200
(When the temperature is 0°C or less, “–” and
temperature are displayed by turns.)
(When the temperature is 100°C or more, hundreds
digit, tens digit and ones digit are displayed by
turns.)
1
ON
2 3 4 5 6
1
ON
2 3 4 5 6
15
1
ON
2 3 4 5 6
Pulse
LEV-A opening pulse when error
occured.
0~500
0~500
(When it is 100 pulse or more, hundreds digit, tens
digit and ones digit are displayed by turns.)
(Example) When 130 pulse;
0.5 secs. 0.5secs. 2 secs.
Water inlet temperature (TH32) when
error occured.
0~100
0~100
30
1
1
ON
2 3 4 5 6
Plate HEX liquid pipe temperature(TH6)
when error occured.
-39~88
-39~88
(When the temperature is 0°C or less, “–” and
temperature are displayed by turns.)
(Example) When –15°C;
0.5 secs. 0.5secs. 2 secs.
Condensing temperature when error
occured.
-39~88
-39~88
(When the temperature is 0°C or less, “–” and
temperature are displayed by turns.)
(Example) When –15°C;
0.5 secs. 0.5secs. 2 secs.
1
ON
2 3 4 5 6
1
ON
2 3 4 5 6
15
15
0~255
(When the temperature is 100°C or more, hundreds
digit, tens digit and ones digit are displayed by
turns.)
(Example) When 150°C;
0.5 secs. 0.5secs. 2 secs.
50
1
1
ON
2 3 4 5 6
Discharge superheat (SHd) when error
occured.
0~255
Cooling and Heating :SHd=TH4-T
63HS