16
Error Code
Abnormal point and detection method
Judgment and action
Case
UH
Current sensor error or input current error
·Abnormal if current sensor detects –1.0A
to 1.0A during compressor operation.
(This error is ignored during test run.)
·Abnormal if input current is detected 32A
or input current is detected 28A or more
for 10 seconds continuously.
Disconnection of compresso
wiring
Defective circuit of current
sensor on outdoor power
circuit board
Decrease of power supply volt-
age
Correct the wiring (U
•
V
•
W phase) to com-
pressor. Refer to 8-6 (Outdoor power circuit
board).
Replace outdoor power circuit board.
Check the facility of power supply.
UP
Compressor overcurrent interruption
Abnormal if overcurrent DC bus or com-
pressor is detected after compressor starts
operating for 30 seconds.
Decrease of power supply voltage
Looseness, disconnection or
converse of compressor wiring
connection
Defective fan of outdoor units
Short cycle of indoor/outdoor
units
Defective input circuit of out-
door controller board
Defective compressor
Decreased water flow
Clogged filter of water pipe
Clogged plate heat exchanger
Locked water pump
Malfunction of water pump
Check facility of power supply.
Correct the wiring (U
•
V
•
W phase) to com-
pressor. Refer to 8-6 (Outdoor power circuit
board).
Check outdoor fan.
Solve short cycle.
Replace outdoor controller circuit board.
Check compressor.
Refer to 8-4.
+
Before the replacement of the outdoor
controller circuit board, disconnect the wiring
to compressor from the outdoor power circuit
board and check the output voltage among
phases, U, V, W, during test run. No defect
on board if voltage among phases (U-V, V-W
and W-U) is same. Make sure to perform the
voltage check with same performing frequency.
~
Check water circuit and repair the defect.
Ed
Serial communication error
Abnormal if serial communication
between outdoor controller circuit
board and outdoor power circuit board
is defective.
Wire disconnection or contact
failure of connector CN2
between the outdoor controller
circuit board and the outdoor
power circuit board
Wire disconnection or contact
failure of connector CN4
between the outdoor controller
circuit board and the outdoor
power circuit board
Defective communication circuit
of outdoor power circuit board
Defective communication circuit
of outdoor controller circuit board
for outdoor power circuit board
Check connection of each connector CN2
and CN4 between the outdoor controller
circuit board and the outdoor power circuit
board.
Replace outdoor power circuit board.
Replace outdoor controller circuit board.