REFRIGERANT SYSTEM DIAGRAM
7
Distributor
TH7
Strainer(#100)
Strainer(#100)
Receiver
LEV-B
TH6
TH32
Plate HEX
Water IN
Water OUT
Strainer
(#100)
TH3
CHECK/V
CHECK/V
CHECK/V
H/P SW
TH4
TH8
P/B
LEV-A
COMP
REV/V
P-Sensor
S/V
Strainer
(#100)
Refrigerant flow in heating
Refrigerant flow in cooling
COMP
H/P SW
Plate HEX
REV/V
S/V
CHECK/V
P-Sensor
P/B
LEV-A
LEV-B
TH32
TH3
TH4
TH6
TH7
TH8
Receiver
DC inverter twin rotary compressor (Mitsubishi Electric Corporation)
For protection (OFF:4.15MPa)
ACH30 - 40 Plates (Alfa Laval)
Change the refrigerant circuit (Heating / Cooling) and for Defrosting
For production test use
High pressure / Low pressure / For production test use
For calculation of the condensing temperature from high pressure
Inverter power board
Heating:Secondary LEV
Cooling:Primary LEV
Heating:Primary LEV
Cooling:Secondary LEV
For freeze protection and for compressor frequency control
Heating:Evaporating temperature
Cooling:Sub cool liquid temperature
For LEV control and for compressor protection
Heating:Sub cool liquid temperature
Cooling:Evaporating temperature
For fan control and for compressor frequency control
For power board protection
For accumulation of refrigerant
Compressor
High pressure switch (63H)
Plate Heat Exchanger
Reversing (4-way) valve (21S4)
Solenoid valve
Check valve
Pressure sensor (63HS)
Power board
Linear expansion valve -A
Linear expansion valve -B
Inlet water temperature thermistor
Liquid temperature thermistor
Discharge temperature thermistor
Plate HEX liquid temperature thermistor
Ambient temperature thermistor
Heatsink temperature thermistor
Receiver
Symbol
Part name
Detail
PUHZ-W90VHA