background image

7. Test run

Before test run

   After installation works are completed, check if there is no refrigerant leak-

age, no looseness in the power supply or control wiring, no wrong polarity, 
and no disconnection of one phase in the supply.

   Use a 500-volt megohmmeter to check that the resistance between the 

power supply terminals and ground is at least 1.0M

Ω

.

 Warning:

Do not use the air to water heat pump if the insulation resistance is less than 
1.0M

Ω

.

Insulation resistance

When installed the power source to the unit has been cut for an extended period, 
the insulation resistance may drop below 1 M

Ω

 due to the accumulation of refriger-

ant within the compressor. This is not a malfunction. Perform the following proce-
dures.
1.  Remove the wires from the compressor and measure the insulation resistance of 

the compressor.

2.  If the insulation resistance is below 1 M

Ω

, the compressor may be faulty or sim-

ply the accumulation of refrigerant in the compressor makes the resistance drop.

 

3.  After connecting the wires to the compressor, the compressor starts to warm 

up once power is supplied. After supplying power for the times indicated below, 
measure the insulation resistance again.
•  The insulation resistance drops due to the accumulation of refrigerant in the 

compressor. The resistance will rise above 1 M

Ω

 after the compressor is 

warmed up for four hours.
 (The necessary time to warm up the compressor varies according to atmo-
spheric conditions and refrigerant accumulation.)

• If the refrigerant accumulates within the compressor, the compressor must be 

warmed up at least 12 hours before starting the operation to prevent break-
down.

4.  If the insulation resistance rises above 1 M

Ω

, the compressor is not faulty.

 Caution:

•  

The compressor does not operate if the power supply phase connection is 
incorrect.

•  

Turn on the power at least 12 hours before starting operation.

-  

Starting operation immediately after turning on the main power switch can result 
in severe damage to internal parts. Keep the power switch turned on during the 
operating period.

6. Electrical work

S1

S2

S3

S1

S2

S3

 Warning:

In case of A-control wiring, there is high voltage potential on the S3 terminal caused by electrical circuit design that has no electrical insulation between power 
line and communication signal line. Therefore, please turn off the main power supply when servicing. And do not touch the S1, S2, S3 terminals when the power 
is energized. If isolator should be used between indoor unit and outdoor unit, please use 3-pole type.

Outdoor Unit

3 poles isolator

230V

Single phase

Isolator

Interface unit /
Flow temp. 
controller

6.2. Field electrical wiring

Outdoor unit power supply

~/N (single), 50 Hz, 230 V

Outdoor unit Circuit Breaker capacity

*1

25 A

Wiring 

Wire No. × 

size (mm

2

) Outdoor unit power supply, earth

3 × Min. 4

Interface unit/Flow temp. controller-Outdoor unit

*2

3 × 1.5 (polar)

Interface unit/Flow temp. controller-Outdoor unit earth

*2

1 × Min. 1.5

Remote controller-Interface unit/Flow temp. controller

2 × 0.3 (Non-polar)

Circuit rating

Outdoor unit L-N (single)

*3

AC 230 V

Interface unit/Flow temp. controller-Outdoor unit S1-S2

*3

AC 230 V

Interface unit/Flow temp. controller-Outdoor unit S2-S3

*3

DC 24 V

Remote controller-Interface unit/Flow temp. controller

*3

DC 12 V

*1. A breaker with at least 3.0 mm contact separation in each pole shall be provided. Use earth leakage breaker (NV).
*2. Max. 80 m
*3.  The fi gures are NOT always against the ground.
 

S3 terminal has DC 24 V against S2 terminal. However between S3 and S1, these terminals are NOT electrically insulated by the transformer or other device.

Notes:  1.  Wiring size must comply with the applicable local and national codes.

2.  Power supply cables and the cables between Interface unit/Flow temp. controller and outdoor unit shall not be lighter than polychloroprene sheathed 

fl exible cables. (Design 60245 IEC 57)

3.  Be sure to connect the cables between Interface unit/Flow temp. controller and outdoor unit directly to the units (no intermediate connections are al-

lowed).
Intermediate connections may result in communication errors. If water enters at the intermediate connection point, it may cause insuffi cient insula-
tion to ground or a poor electrical contact .
(If an intermediate connection is necessary, be sure to take measures to prevent water from entering the cables.)

4.  Install an earth longer than other cables.

6

Содержание PUHZ-W85VHA

Страница 1: ...εγκατάστασης της εσωτερικής μονάδας προτού εγκαταστήστε τη μονάδα MANUAL DE INSTALAÇÃO Para uma utilização segura e correcta leia atentamente este manual e o manual de instalação da unidade interior antes de instalar a unidade INSTALLATIONSMANUAL Læs af sikkerhedshensyn denne vejledning samt monteringsvejledningen til indendørsenheden grundigt før De monterer enheden INSTALLATIONSMANUAL Läs bruksa...

Страница 2: ...rly installed it may cause water leakage electric shock or fire Do not remodel the unit Consult an installer for repairs If alterations or repairs are not performed correctly it may cause water leakage electric shock or fire The user should never attempt to repair the unit or transfer it to another location If the unit is installed improperly it may cause water leakage electric shock or fire If th...

Страница 3: ...unit is not properly grounded there may be a risk to get an electric shock Make sure to use circuit breakers ground fault interrupter isolating switch B fuse and molded case circuit breaker with the specified capacity If the circuit breaker capacity is larger than the specified capacity break down or fire may result 1 4 Before starting the test run Caution Turn on the main power switch more than 1...

Страница 4: ... shows three examples of precautions against strong winds 1 Face the air outlet towards the nearest available wall keeping about 50 cm dis tance Fig 2 2 2 Install an optional air guide if the unit is installed in a location where strong winds such as a typhoon etc may directly blow to the air outlet Fig 2 3 A Air outlet guide 3 Position the unit so that the outlet air can blow at right angle to th...

Страница 5: ...que at the water piping connection is 50 N m Check if water leaks after installation Use the water pressure in more than 0 MPa gauge and less than 0 3MPa gauge Use the inlet water of higher than 5 C and lower than 55 C 5 2 Water quality condition The water in a system should be clean and with a pH value of 6 5 8 0 The followings are the maximum values Calcium 100mg L Chlorine 100mg L Iron manganes...

Страница 6: ...S1 S2 S3 Warning In case of A control wiring there is high voltage potential on the S3 terminal caused by electrical circuit design that has no electrical insulation between power line and communication signal line Therefore please turn off the main power supply when servicing And do not touch the S1 S2 S3 terminals when the power is energized If isolator should be used between indoor unit and out...

Страница 7: ... CNDM connector option on the control board of the outdoor unit The ability varies according to the outdoor temperature and conditions etc 1 Complete the circuit as shown when using the external input adapter PAC SC36NA Option 2 SW1 ON Low noise mode SW1 OFF Normal operation A Circuit diagram example low noise mode B On site arrangement C External input adapter PAC SC36NA D Outdoor unit control bo...

Страница 8: ...act address telephone number on this manual before handing it to the customer This product is designed and intended for use in the residential commercial and light industrial environment The product at hand is based on the following EU regulations Low Voltage Directive 2006 95 EC Electromagnetic Compatibility Directive 2004 108 EC ...

Отзывы: