11
5
DATA
5-1. REFILLING REFRIGERANT CHARGE (R410A : kg)
5-2. COMPRESSOR TECHNICAL DATA
Service Ref.
Piping length (one way)
Initial
charged
10m
20m
30m
40m
50m
60m
75m
PUHZ-SW75VHA.UK
PUHZ-SW75VHA-BS.UK
3.2
3.6
4.0
4.6
—
—
—
3.2
PUHZ-SW100VHA.UK
PUHZ-SW100VHA-BS.UK
PUHZ-SW100YHA.UK
PUHZ-SW100YHA-BS.UK
4.6
4.8
5.0
5.6
6.2
6.8
7.5
4.6
PUHZ-SW120VHA.UK
PUHZ-SW120VHA-BS.UK
PUHZ-SW120YHA.UK
PUHZ-SW120YHA-BS.UK
4.6
4.8
5.0
5.6
6.2
6.8
7.5
4.6
U-V
U-W
W-V
Service Ref.
Compressor model
Winding
Resistance
(
)
ANB33FNEMT
(at 20°C)
0.19
0.19
0.19
PUHZ-SW100VHA.UK
PUHZ-SW100VHA-BS.UK
ANB33FNDMT
0.30
0.30
0.30
ANB42FNDMT
ANB42FNEMT
0.30
0.30
0.30
PUHZ-SW100YHA.UK
PUHZ-SW100YHA-BS.UK
TNB220FLHMT
0.88
0.88
0.88
PUHZ-SW75VHA.UK
PUHZ-SW75VHA-BS.UK
PUHZ-SW120YHA.UK
PUHZ-SW120YHA-BS.UK
PUHZ-SW120VHA.UK
PUHZ-SW120VHA-BS.UK
0.19
0.19
0.19
Additional charge is required for pipes
longer than 10 m.
OCH533A