21
NOTE:
1. Rating conditions (ISO T1)
Cooling Indoor : D.B. 27
:
(80˚F) W.B. 19
:
(66˚F)
Outdoor : D.B. 35
:
(95˚F) W.B. 24
:
(75˚F)
Heating Indoor : D.B. 20
:
(68˚F)
Outdoor : D.B. 7
:
(45˚F)
W.B. 6
:
(43˚F)
Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range
Indoor
Outdoor
Cooling
Upper limit D.B. 35˚C, W.B. 22.5˚C D.B. 46˚C
Lower limit D.B. 19˚C, W.B. 15˚C
D.B. -5˚C
w
1
Heating
Upper limit D.B. 28˚C
D.B. 21˚C, W.B. 15˚C
Lower limit D.B. 17˚C
D.B. -11˚C, W.B. -12˚C
w
2
4. Above data are based on the indicated voltage.
w
1. If optional air protect guide installed. D.B.-15
:
w
2. For RP100 D.B. -20
:
, W.B. -20
:
Indoor unit
Single phase 230V 50Hz
Single phase 230V 50Hz
Outdoor unit
3. Guaranteed voltage
198~264V, 50Hz
Model name
Indoor unit
PKA-RP60FAL
PKA-RP71FAL
PKA-RP100FAL
Outdoor unit
PUHZ-RP60VHA2
PUHZ-RP71VHA2
PUHZ-RP100VHA2
PUHZ-RP60VHA3
PUHZ-RP71VHA3
PUHZ-RP100VHA3
Cooling
Capacity
Btu/h
20,500
24,200
34,100
kW
6.0(2.7-6.7)
7.1(3.3-8.1)
10.0(4.9-11.4)
Total input
kW
1.55
1.98
2.93
EER
3.87
3.59
3.41
Energy label class
A
A
A
SHF
0.83
0.77
0.77
Heating
Capacity
Btu/h
23,900
27,300
38,200
kW
7.0(2.8-8.2)
7.6(3.5-10.2)
11.2(4.5-14.0)
Total input
kW
2.01
2.23
3.25
COP
3.48
3.41
3.45
Energy label class
B
B
B
Booster heater
kW
-
-
-
Power supply
Phase
[
1
Cycle
Hz
50
Voltage
V
230
Breaker size
A
25
32
Indoor unit
Air flow
CMM
15-20
22-28
(Low-High)
CFM
530-705
780-990
External pressure
Pa
0
Sound level
dB(A)
39-45
41-46
(Low-High)
External finish
Munsell 3.4Y 7.7/0.8
Dimension
W : mm
1400
1680
D : mm
235
H : mm
340
W : inch
55-1/8
66-1/8
D : inch
9-1/4
H : inch
13-3/8
Weight
kg
24
28
lbs
53
62
Field drain pipe I.D.
mm
20
inch
13/16
Outdoor unit
Air flow
CMM
55
100
CFM
1,940
3,530
Sound level at cooling
dB(A)
47
49
Sound level at heating
dB(A)
48
51
External finish
Ivory Munsell 3Y 7.8/1.1
Dimension
W : mm
950
D : mm
330+30
950
330+30
H : mm
943
1350
W : inch
37-3/8
D : inch
13 + 1-3/16
37-3/8
13 + 1-3/16
H : inch
37-1/8
53-1/8
Weight
kg
75(VHA2)/68(VHA3)
121(VHA2)/116(VHA3)
lbs
165(VHA2)/150(VHA3)
267(VHA2)/256(VHA3)
Refrigerant pipe size
Gas side O.D.
mm
15.88
inch
5/8
Liquid side O.D.
mm
9.52
inch
3/8
15.88
5/8
9.52
3/8
Refrigerant pipe length
Height difference
m
Max. 30
Max. 30
Length
m
Max. 50
Max. 75
PKA-RP50FAL2
PUHZ-RP50VHA2
PUHZ-RP50VHA3
17,000
5.0(2.3-5.6)
1.66
3.01
B
0.86
20,500
6.0(2.5-7.3)
1.76
3.41
B
-
16
15-20
530-705
39-45
1400
55-1/8
24
53
35
1,240
44
46
800
300+23
600
31-1/2
11 - 13/16
23-5/8
45(VHA2)/42(VHA3)
99(VHA2)/92(VHA3)
12.7
1/2
6.35
1/4
Max. 30
Max. 50
OCS05E-1.qxp 08.3.31 9:52 AM Page 21
Содержание PUHZ-RP100VHA3
Страница 52: ...52 WIRED REMOTE CONTROLLER Unit mm 130 120 19 43 5 ...
Страница 53: ...53 WIRELESS REMOTE CONTROLLER Unit mm 159 3 55 58 19 ...
Страница 98: ...98 9 3 PLA RP AA PLA RP AA2 9 3 1 Fresh air intake amount ...
Страница 99: ...99 9 3 2 BRANCH DUCT Installation at site ...
Страница 108: ...108 PEAD RP60GA PEAD RP71GA ...
Страница 109: ...109 PEAD RP100GA ...
Страница 116: ...116 ...