PUHZ-HRP200YKA
COOLING
MODE
HEATING
58
SPL(dB)
59
LINE
3-2. NOISE CRITERION CURVES
Total piping length (one way)
Amount of additional refrigerant charge (kg)
30 m and less
31-40 m
41-50 m
51-60 m
61-70 m
71-80 m
No additional
charge necessary
Calculate the amount of additional refrigerant
charge using formula provided below.
For single combination
(1 indoor unit)
For twin / triple /
quadruple combination
(2-4 indoor units)
1.4 kg
2.8 kg
0.9 kg
1.8 kg
4.2 kg
5.6 kg
7.0 kg
At time
of
shipping
7.1 kg
3-1. Addition of refrigerant
When length exceeds 50 m for twin / triple / quadruple combination
When the total length of the piping exceeds 50 m, calculate the amount of additional charge based on the following requirements.
Note: If the calculation produces a negative number (i.e. a “minus” charge), of if calculation results in an amount that is less than the “Additional charage amount for 50 m”,
perform the additional charge using the amount shown in “Additional charge amount for 50 m”.
Amount of additional
charge
=
Main piping:
Liquid line size
ø12.7 overall length ×
0.17
+
+
+
–
4.3 (kg)
(kg)
(m) × 0.17 (kg/m)
Additional charge amount
for 50 meters
1.8 kg
Main piping:
Liquid line size
ø9.52 overall length ×
0.14 (Gas line: ø25.4)
(m) × 0.14 (kg/m)
Branch piping:
Liquid line size
ø9.52 overall length ×
0.05 (Gas line: ø15.88)
(m) × 0.05 (kg/m)
(m) × 0.02 (kg/m)
Branch piping:
Liquid line size
ø6.35 overall length ×
0.02
Permissible total
piping length
A+B+C+D+E
A+B or A+C
or
A+D or A+E
Charge-less
piping length
A+B+C+D+E
HRP200 : A+B+C(+D)(+E)
≤
80 m
* “D” is for triple“.
* “E” is for four (quadruple).
Indoor unit
Outdoor unit
Multi distribution pipe (option)
Height difference (Indoor unit-
Outdoor unit) Max. 30 m
Height difference (Indoor unit-
Indoor unit) Max. 1 m
A: Main piping
B, C, D, E: Branch
Max. 20m
piping
<Limits of refrigerant piping installation>
| B-C | or | B-D | or
| B-E | or | C-D | or
| C-E | or | D-E |
No. of bends
Within 15
80 m and less
70 m and less
30 m and less
8 m and less