43
1
ON
2 3 4 5 6
°C
Discharge superheat SHd
0~255
Cooling = TH4-T
63HS
Heating = TH4-T
63HS
0~255
(When the temperature is 100°C or more, hundreds
digit, tens digit and ones digit are displayed by turns.)
°C
Sub cool. SC
0~130
Cooling = T
63HS
-TH3
Heating = T
63HS
-TH2
0~130
(When the temperature is 100°C or more, hundreds
digit, tens digit and ones digit are displayed by turns.)
0.1 A
Input current of outdoor unit
0~500
(When it is 100 or more, hundreds digit, tens digit
and ones digit are displayed by turns.)
Pulse
LEV-B opening pulse
0~480
0~480
(When it is 100 pulse or more, hundreds digit, tens
digit and ones digit are displayed by turns.)
Hz
Targeted operation frequency
0~255
0~255
(When it is 100Hz or more, hundreds digit, tens digit
and ones digit are displayed by turns.)
DC bus voltage
180~370
180~370
(When it is 100V or more, hundreds digit, tens digit
and ones digit are displayed by turns.)
V
1
ON
2 3 4 5 6
1
ON
2 3 4 5 6
1
ON
2 3 4 5 6
1
ON
2 3 4 5 6
1
ON
2 3 4 5 6
SW2 setting
Display detail
Explanation for display
Unit
1
ON
2 3 4 5 6
1
ON
2 3 4 5 6
1
ON
2 3 4 5 6
Pressure saturation temperature (T
63HS
)
−
39~88
Outdoor heatsink temperature (TH8)
−
40~200
:
:
:
−
39~88
(When the temperature is 0
:
or less, “–” and
temperature are displayed by turns.)
−
40~200
(When the temperature is 0
:
or less, “–” and
temperature are displayed by turns.)
(When the thermistor detects 100
:
or more,
hundreds digit, tens digit and ones digit are
displayed by turns.)
Ambient temperature (TH7)
−
39~88
−
39~88
(When the temperature is 0
:
or less, “–” and
temperature are displayed by turns.)